2001-01-08 00:00:00*****************PROVISO****************
 REVISED PLUMBING SHEETS SHOWING ALL
 CORRECTIONS SHALL BE SUBMITTED FOR
 REVIEW PRIOR TO ISSUANCE OF PLUMBING
 PERMIT.ALL SHEETS SAHLL BE SIGNED AND
 SEALED PER FLA.STATUTE.
  
 SHOW SQ.FT.OF ROOF AREA DRAINED BY EACH
 DRAIN.COMPLY W/SPC SEC.1108.1,1108.2,
 1108.3.INCLUDE 1/2 AREA OF VERTICAL WALL
 PER SPC SEC.1108.3.
  
 A PERMIT FOR THE DOMESTIC WATER AND FIRE
 SERVICE IS REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION.CONTACT PALM
 BEACH COUNT HEALTH DEPT.A PERMIT MAY
 ALSO BE REQD.FROM PALM BEACH COUNTY
 HEALTH DEPT.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.4.7.
  
 PLUMBING SHEETS SHOW DOMESTIC WATER
 SERVICE AS 3" AND CIVILS SHOW 2".CLARIFY
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED.
 COMPLY W/SPC SEC.901.2.
  
 VENTS FOR WATER CLOSETS SHALL COMPLY W/
 SPC SEC.920.2.(NO LESS THAN 1/2 THE
 DIAMETER OF THE DRAIN SERVED.)
  
 WATER HEATER ON 2ND FLOOR SHALL BE
 EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.1.
  
 DRINKING FOUNTAINS ARE NOT SHOWN ON THE
 SANITARY OR WATER RISERS.COUNTYWIDE
 AMENBDMENTS TO SPC SEC.104.2.1.