Plan Review Notes For Permit 00011033 |
Permit Number |
00011033 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PROVISO: PROVIDE THE FOLLOWING | | 1) PROVIDE INFORMATION ON OUTSIDE AIR | | REQUIREMENTS PER ASHRAE 62-89 | | 2) INSUFFICIENT DETAILS ON DUCTS FOR | | A/C SYTEMS | | 3) 1997 SMC 610 REQUIRES FIRE PROTECTION | | OF FLOOR/CEILING ASSEMBLY. FIRE DAMPERS | | NOT SHOWN | | THE INFORMATION ABOVE IS TO BE PROVIDED | | PRIOR TO ANY BUILDOUT, THIS PERMIT APPLI | | CATION IS FOR SHELL ONLY NO MECHANICAL | | UNTIL INFORMATION PROVIDED FOR REVIEW | | AND ACCEPTED |
|