Plan Review Notes
Plan Review Notes For Permit 00011033
Permit Number 00011033
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PROVISO: PROVIDE THE FOLLOWING
 1) PROVIDE INFORMATION ON OUTSIDE AIR
 REQUIREMENTS PER ASHRAE 62-89
 2) INSUFFICIENT DETAILS ON DUCTS FOR
 A/C SYTEMS
 3) 1997 SMC 610 REQUIRES FIRE PROTECTION
 OF FLOOR/CEILING ASSEMBLY. FIRE DAMPERS
 NOT SHOWN
 THE INFORMATION ABOVE IS TO BE PROVIDED
 PRIOR TO ANY BUILDOUT, THIS PERMIT APPLI
 CATION IS FOR SHELL ONLY NO MECHANICAL
 UNTIL INFORMATION PROVIDED FOR REVIEW
 AND ACCEPTED