Plan Review Notes
Plan Review Notes For Permit 00011033
Permit Number 00011033
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00JOB SPEC 15400-7-2.07(5)-SPACING OF
 CLEANOUTS SHALL COMPLY W/SPC SEC.710.2.4
  
 SPEC.15400-9-2.13-HORIZONTAL SUPPORTS
 COPPER TUBING SHALL COMPLY W/SPC SEC.
 310.3.4.
  
 TOILET STALL DOOR IN MEN'S R.R.CANNOT
 SWING INTO CLEAR FLOOR SPACE FOR URINAL
 PER FACBC SEC.4.17.5.
  
 AN ADDITIONAL HANDICAP STALL IS REQD.IN
 THE WOMEN'S TOILET ROOM PER FACBC SEC.
 4.22.4.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).(PROVISIONS SHALL BE
 MADE FOR PERSONS WHO HAVE TROUBLE
 BENDING OR STOOPING.)
  
 SHT.A403.-LAVATORY REQD.IN HANDICAP
 STALL PER FACBC SEC.4.17.3.(SEE RM.119)
  
 WALLS AND FLOORS TO A HEIGHT OF FOUR
 FEET SHALL BE NONABSORBENT MATERIAL PER
 SBC 1204.2.
  
 TOILET FLOOR PLAN ON A-403 DOESN'T
 CORRELATE W/OTHER PLANS.CLARIFY.
  
 THE WIDTH OF THE HANDICAP STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3 (MIN.79"+2"
 FOR CLEANING.)
  
 LOCATION OF BACKFLOW DETECTION DEVICE
 SHALL BE DETERMINED BY CITY OF WPB
 UTILITIES,
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.906.2.1.(VENT SHALL RISE
 VERTICALLY TO A POINT 6" ABOVE FLOOD
 LEVEL RIM OF FIXTURE BEFORE OFFSETTING
 HORIZ.PROPERLY VENT FLOOR DRAINS.
  
 SHT.P-501-RELIEF LINE SHALL DRAIN TO
 EXTERIOR PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.507.6(3).
  
 SHT.P-101- 7 W.C.'S SHOWN ON FLOOR PLAN
 AND SIX ARE SHOWN ON ISOMETRIC.CLARIFY.
  
 CLEARLY SIZE ALL SECTIONS OF THE
 SANITARY RISERPER COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 INDICATE SLOPE OF PIPE FOR SANITARY
 SYSTEM.COMPLY W/SPC TABLE 714.1,714.2.
 SHOW FIXTURE UNIT LOAD ON SYSTEM.
  
 HOSE BIBBS REQUIRE SHUT-OFF VALVES PER
 SPC SEC.610.4.1.
  
 SUBMIT ISOMETRIC FOR COMPLETE STORM
 SYSTEM.SHOW SQ.FOOTAGE OF ROOF AREA
 DRAINED BY EA.DRAIN.COMPLY W/SPC SEC.
 1108.1,1108.2.
  
 SUBMIT CALCULATIONS FOR SECONDARY DRAIN-
 AGE.INCLUDE 1/2 VERTICAL AREA OF PARAPET
 WALL PER SPC SEC.1108.3.,1109.1,1109.2,
 1109.3.AND APPENDIX "A".
  
 APPROVALS REQD.FROM ENGINEERING FOR
 STORM WATER DRAINAGE AND FROM P.B.COUNTY
 HEALTH DEPT.FOR WATER MAIN INSTALLATION.
 SPC 101.4.7.