Date |
Text |
2001-01-08 00:00:00 | JOB SPEC 15400-7-2.07(5)-SPACING OF |
| CLEANOUTS SHALL COMPLY W/SPC SEC.710.2.4 |
| |
| SPEC.15400-9-2.13-HORIZONTAL SUPPORTS |
| COPPER TUBING SHALL COMPLY W/SPC SEC. |
| 310.3.4. |
| |
| TOILET STALL DOOR IN MEN'S R.R.CANNOT |
| SWING INTO CLEAR FLOOR SPACE FOR URINAL |
| PER FACBC SEC.4.17.5. |
| |
| AN ADDITIONAL HANDICAP STALL IS REQD.IN |
| THE WOMEN'S TOILET ROOM PER FACBC SEC. |
| 4.22.4. |
| |
| DRINKING FOUNTAINS SHALL COMPLY W/FACBC |
| SEC.4.1.3.(10)(A).(PROVISIONS SHALL BE |
| MADE FOR PERSONS WHO HAVE TROUBLE |
| BENDING OR STOOPING.) |
| |
| SHT.A403.-LAVATORY REQD.IN HANDICAP |
| STALL PER FACBC SEC.4.17.3.(SEE RM.119) |
| |
| WALLS AND FLOORS TO A HEIGHT OF FOUR |
| FEET SHALL BE NONABSORBENT MATERIAL PER |
| SBC 1204.2. |
| |
| TOILET FLOOR PLAN ON A-403 DOESN'T |
| CORRELATE W/OTHER PLANS.CLARIFY. |
| |
| THE WIDTH OF THE HANDICAP STALLS SHALL |
| COMPLY W/FACBC SEC.4.17.3 (MIN.79"+2" |
| FOR CLEANING.) |
| |
| LOCATION OF BACKFLOW DETECTION DEVICE |
| SHALL BE DETERMINED BY CITY OF WPB |
| UTILITIES, |
| |
| VENTS FOR FLOOR DRAINS SHALL COMPLY W/ |
| SPC SEC.906.2.1.(VENT SHALL RISE |
| VERTICALLY TO A POINT 6" ABOVE FLOOD |
| LEVEL RIM OF FIXTURE BEFORE OFFSETTING |
| HORIZ.PROPERLY VENT FLOOR DRAINS. |
| |
| SHT.P-501-RELIEF LINE SHALL DRAIN TO |
| EXTERIOR PER COUNTYWIDE AMENDMENTS TO |
| SPC SEC.507.6(3). |
| |
| SHT.P-101- 7 W.C.'S SHOWN ON FLOOR PLAN |
| AND SIX ARE SHOWN ON ISOMETRIC.CLARIFY. |
| |
| CLEARLY SIZE ALL SECTIONS OF THE |
| SANITARY RISERPER COUNTYWIDE AMEND- |
| MENTS TO SPC SEC.104.2.1. |
| |
| INDICATE SLOPE OF PIPE FOR SANITARY |
| SYSTEM.COMPLY W/SPC TABLE 714.1,714.2. |
| SHOW FIXTURE UNIT LOAD ON SYSTEM. |
| |
| HOSE BIBBS REQUIRE SHUT-OFF VALVES PER |
| SPC SEC.610.4.1. |
| |
| SUBMIT ISOMETRIC FOR COMPLETE STORM |
| SYSTEM.SHOW SQ.FOOTAGE OF ROOF AREA |
| DRAINED BY EA.DRAIN.COMPLY W/SPC SEC. |
| 1108.1,1108.2. |
| |
| SUBMIT CALCULATIONS FOR SECONDARY DRAIN- |
| AGE.INCLUDE 1/2 VERTICAL AREA OF PARAPET |
| WALL PER SPC SEC.1108.3.,1109.1,1109.2, |
| 1109.3.AND APPENDIX "A". |
| |
| APPROVALS REQD.FROM ENGINEERING FOR |
| STORM WATER DRAINAGE AND FROM P.B.COUNTY |
| HEALTH DEPT.FOR WATER MAIN INSTALLATION. |
| SPC 101.4.7. |