Plan Review Notes
Plan Review Notes For Permit 00011033
Permit Number 00011033
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00ACCEPTED BY REVISION SEE LATEST NOTES*
  
 INSUFFICIENT INFORMATION TO REVIEW
 PROVIDE DETAILS ON OUTSIDE AIR PER
 ASHRAE 62-89
 EXHAUST FANS ON SHT M-103 ARE LABELED TO
 SERVE 1ST FLOOR WHAT SERVES SECOND FLOOR
 PROVIDE DETAIL ON DUCT PENETRATING FROM
 ROOF TO 1ST FLOOR
 INDICATE ANY REQUIREMENTS FOR FIRE PROT-
 ECTION AT ALL PENETRATIONS
 PROVIDE DETAILS ON DUCT, SIZE, MATERIAL
 AND LOCATION
 PROVIDE CONDENSATE DRAIN INFORMATION
 PROVIDE INFORMATION ON REQUIRED FAN SHUT
 DOWN BY DUCT SMOKE DETECTORS