Plan Review Notes For Permit 00011033 |
Permit Number |
00011033 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE:AS REQ`D BY 240-13 OF THE NEC. | | GFI PROTECTION FOR 1000AMPS OR MORE IS | | REQ`DPLEASE SUBMIT PLANS SHOWING | | MAIN BUS/EQUIPMENT MEETING THAT | | REQ`MENT. | | | | 2)NOTE: PLEASE SHOW COMPLETE GROUNDING | | ELECTRODE SYSTEM BEING INSTALLED. TO | | INCLUDE ALL BLDG.STEEL,CWP,AND FOUND-TIO | | -ATION STEEL. AS REQ`D PER 250-81 | | | | 3)NOTE: PAGE E-107 PLEASE NOTE ROOF TOP | | GFI REC. REQ`D BY 210-63 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW AND APPROVAL. | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 659-8096 EXT 8372 |
|