Plan Review Notes For Permit 00011000 |
Permit Number |
00011000 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** PROVISO***************** | | | | 1)NOTE:PLEASE REVISE RISER DIAGRAM. | | YOU SHOW 250 AMP 2 POLE GOING TO A 250A | | MLO PANEL WITH 1/0 WIRE. AS PER 310-16 | | 1/0 IS NOT RATED FOR 250AMPS. | | ALSO PLEASE CHECK LOAD CALCUALTION FOR | | CODE COMPLIANCE. AN OPTIONAL METHOD | | CALCULATION CAN BE USED FOR HEAT. | | BATH CIRCUT DOES NOT NEED TO BE FIGURED | | SEPARATE. CAN BE FIG. AS LIGHTING LOAD. | | | | PLEASE CLARIFY MAIN PANEL/DISCONNECT. | | | | 2)NOTE:MISSING OUTLET IN BEDROOM #3 | | | | PLEASE SUBMIT NEW RISER DIAGRAM FOR | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | ELECTRICAL INSPECTION IS CALLED IN. | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 659-8096 EXT 8372 |
|