2001-01-08 00:00:00PLANS NOT DESIGNED TO THE 1997 SBC.
 NOTES THROUGHOUT PLANS SPECIFY 94 EDITIO
  
 FILL OUT THE HEADING OF THE DESIGN COMPL
 IANCE FORM. PROVIDE ADDRESS.
  
  
 TYPICAL WALL SECTION REFERS TO THE
 INVALID SSTD 10-93. CANNOT MIX DESIGN
 CRITERIA,SBC 1606 & SSTD.
  
 PLAN #1, HURRICANE INSTALLTION SCHEDULE
 SPECIFYS THAT THE GARAGE OVERHEAD DOOR
 WILL SERVE AS A MEANS OF EGRESS. NOTE
 ALL EGRESS DOORS ARE REQUIRED TO BE
 SWING TYPE.CLARIFY
  
 PLANS ARE REQUIRED TO BE SPECIFIC.
 PROVIDE THE ADDRESS ON THE PLANS.
  
  
  
 ROOF TILE PRODUCT APPROVAL,THE PALM
 BEACH COUNTY CHECK LIST IS INVALID SINCE
 THE PROPOSED TILES HAVE METRO DADE
 APPROVAL.
  
  
 ROOF TILE,SPECIFY THE METHOD OF ATTACH
 MENT.IF NAIL ON SYSTEM IS TO BE USED
 PROVIDE ATTACHMENT CALCULATIONS, SEE
 PAGE 10 OF PRODUCT APPROVAL.
  
  
 OVERHEAD GARAGE DOOR, PROVIDE PRODUCT
 APPROVAL.
  
  
 NORANDEX PRODUCT APPROVAL IS REQUIRED TO
 HAVE THE DESIGNER OF RECORD RAISED
 SEAL.
  
  
 MANUAL J, PROVIDE UPDATED CALCULATIONS.
 NOTE THAT WHITE OUT CHANGES TO THE DATE
 WILL NOT BE ACCEPTED.
  
 HURRICANE SHUTTERS, PROVIDE A INSTALLATI
 PLAN IDENTIFYING THE OPENING LOCATIONS.
  
 FILL OUT THE HEADINGINFORMATION COMPLETE
 LY ON THE ENERGY FORM 600