Plan Review Notes For Permit 00010763 |
Permit Number |
00010763 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** PROVISO **************** | | | | 1)NOTE:AS PER OUR CONVERSATION PLEASE | | CHECK FAULT CURRENT CALCULATIONS FOR | | AIC RATING. FPL CAN GIVE FALUT CURRENT | | AVAILABILITY. | | | | 2)NOTE:PLEASE SHOW GROUNDING ELECTRODE | | CONDUCTOR GOING TO BLDG.STEEL ALSO AS S | | REQ`D BY 250-81 FO THE NEC. | | | | 3)NOTE: BATH(S) CIRCUT DOES NOT NEED TO | | BE INCLUDED IN LOAD CALCULATION BUT | | NEEDS TO BE ON PANEL SCHEDULE. | | | | 4)NOTE: RISER DIAGRAM SHOWS FEEDTO | | PANEL GOING OVERHEAD. IF THIS IS THE | | CASE THERE CANNOT BE OVER 8`OF CONDUCTOR | | INSIDE THE STRUCTURE AS PER ART;230-70A | | OF THE NEC. IF IT IS GOING TO BE IN- | | -STALLED IN SLAB THEN PLEASE SHOW. | | | | PLESE HAVE ALL THE ABOVE INFORMATION | | SUBMITTED FOR REVIEW AND APPROVAL BEFORE | | FIRST ROUGH ELECTRICAL INSPECTION IS | | CALLED IN. IF THERE ARE ANY QUESTIONS; | | CALL; 561-659-8096 EXT 8372 |
|