2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE:AS PER OUR CONVERSATION PLEASE
 CHECK FAULT CURRENT CALCULATIONS FOR
 AIC RATING. FPL CAN GIVE FALUT CURRENT
 AVAILABILITY.
  
 2)NOTE:PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO BLDG.STEEL ALSO AS S
 REQ`D BY 250-81 FO THE NEC.
  
 3)NOTE: BATH(S) CIRCUT DOES NOT NEED TO
 BE INCLUDED IN LOAD CALCULATION BUT
 NEEDS TO BE ON PANEL SCHEDULE.
  
 4)NOTE: RISER DIAGRAM SHOWS FEEDTO
 PANEL GOING OVERHEAD. IF THIS IS THE
 CASE THERE CANNOT BE OVER 8`OF CONDUCTOR
 INSIDE THE STRUCTURE AS PER ART;230-70A
 OF THE NEC. IF IT IS GOING TO BE IN-
 -STALLED IN SLAB THEN PLEASE SHOW.
  
 PLESE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS;
 CALL; 561-659-8096 EXT 8372