Plan Review Notes
Plan Review Notes For Permit 00010655
Permit Number 00010655
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT WATER RISER DIAGRAM FOR REVIEW
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SHOW SQ.FT.OF BUILDING AND OCCUPANT
 LOAD PER SPC 407.
  
 SIZING OF VENT SYSTEM SHALL COMPLY W/SPC
 TABLE 920.2.
  
 MIN.SIZE OF DRAIN UNDERGROUND SHALL BE
 2" PER SPC SEC.714.4.
  
 UNDERGROUND SANITARY DRAINAGE SYSTEM
 SHALL BE SIZED PER SPC SEC.714.1,714.2.
  
 WATER CLOSET IN TODDLER'S AREA NOT
 PROPERLY VENTED.SPC SEC.901.2.
  
 A CLEANOUT IS REQD.IN THE BLDG.DRAIN PER
 SPC SEC.710.2.2.
  
 SHOW FIXTURE CLEARANCE OF HANDICAP WATER
 CLOSET FROM WALL AND LAVATORY.COMPLY W/
 FACBC FIGURE 28.
  
 PLANS SHOW A COOKING RANGE AND 3-COMP.
 SINK.IF FOOD PREPARATION/COOKING IS
 BEING DONE A GREASE TRAP WILL BE REQD.
 FOR THE SANITARY SYSTEM PER SPC SEC.
 1004.1 CONTACT ROD COMPO AT CITY OF WPB
 UTILITIES AT (561)835-7423.