Plan Review Notes For Permit 00010485 |
Permit Number |
00010485 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: NEED TO SUBMIT A NEW REVISED | | RISER DIAGRAM?? YOU SHOW TWO PANELS BUT | | ON RISER ONLY SHOWS ONE. ALSO LOAD | | EXCEEDS THE 200 AMP RATING OF RISER | | EQUIPMENT. | | | | 2)NOTE: MISSING OUTLET PER 210-52 | | | | 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS OF NEW | | DWELLINGS. REQ`D BY 1993/1996 NFPA-72 | | 2-2.1.1.1. | | | | 4)NOTE; AS REQ`D BY ARTS;210-52/215-5 | | NEED TO HAVE DEDICATED BATH(S) CIRCUT(S) | | LISTED ON PANEL SCHEDULE AS 20 AMP | | # 12 AWG. | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REIVEW AND APPROVAL.IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 EXT; | | 8372 |
|