Plan Review Notes
Plan Review Notes For Permit 00010485
Permit Number 00010485
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT A NEW REVISED
 RISER DIAGRAM?? YOU SHOW TWO PANELS BUT
 ON RISER ONLY SHOWS ONE. ALSO LOAD
 EXCEEDS THE 200 AMP RATING OF RISER
 EQUIPMENT.
  
 2)NOTE: MISSING OUTLET PER 210-52
  
 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OF NEW
 DWELLINGS. REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1.
  
 4)NOTE; AS REQ`D BY ARTS;210-52/215-5
 NEED TO HAVE DEDICATED BATH(S) CIRCUT(S)
 LISTED ON PANEL SCHEDULE AS 20 AMP
 # 12 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REIVEW AND APPROVAL.IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT;
 8372