Plan Review Notes
Plan Review Notes For Permit 00010371
Permit Number 00010371
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLANS NOT DESIGNED TO THE 1997 SBC.
 NOTES THROUGHOUT PLANS REFERENCE 94 EDI-
 TION.
  
 FILL OUT THE HEADING OF THE DESIGN COMPL
 IANCE FORM.PROVIDE ADDRESS.
  
  
 TYPICAL WALL SECTION REFERS TO THE
 INVALID SSTD 10-93.CANNOT MIX DESIGN
 CRETERIA WITH SBC 1606 & SSTD.
  
 PLAN #1, HURRICANE INSTALTION SCHEDULE
 SPECIFYS THATTHE GARAGE OVERHEAD DOOR
 WILL SERVE AS A MEANS OF EGRESS.NOTE
 THATALL EGRESS DOORS ARE REQUIRED TO
 BE SWING TYPE.CLARIFY
  
 PLANS ARE REQUIRED TO BE SPECIFIC.
 PROVIDE THE ADDRESS ON THE PLANS
  
  
  
 ROOF TILE PRODUCT APPROVAL, THE PALM
 BEACH COUNTY CHECK LIST IS INVALID SINCE
 THE TILES HAVE A METRO DADE APPROVAL AND
 MUST BE INSTALLED ACCORDING TO.
  
  
 ROOF TILE, SPECIFY THE METHOD OF ATTACH-
 MENT.IF NAIL ON SYSTEM IS TO BE USED
 THAN PROVIDE THE CALCULATIONS.SEE PAGE
 10 OF THE PRODUCT APPROVAL.
  
  
 NORANDEX PRODUCT APPROVAL IS REQUIRED TO
 HAVE THE DESIGNER OF RECORD RAISED SEAL.
  
 MANUAL J CALCULATIONS, PROVIDE UPDATED
 CALCULATIONS.NOTE THAT WHITE OUT
 CHANGES WILL NOT BE ACCEPTED.
  
 HURRICANE SHUTTERS, PROVIDE A INSTALLAT-
 ION SCHEDULE AND PLAN IDENTIFYING THE
 OPENINGS.
  
 FILL OUT THE HEADING INFORMATION
 COMPLETELY ON THE ENERGY FORM 600