2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR AVAILABLE FAULT CURRENT.AS REQ`D BY
 ARTS:110-9/110-10 AND 215-5 OF THE NEC.
  
 2)NOTE:PLEASE HAVE THE DEDICATED BATH(S)
 CIRCIUT(S) LISTED ON PANEL SCHEDLUE.
  
 AIC RATING MUST BE ON ALL PLANS! THIS
 HAS BEEN PREVIOUSLY REQUESTED. PLEASE
 HAVE ALL THE ABOVE INFORMATION SUBMITTED
 FOR REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372