Plan Review Notes
Plan Review Notes For Permit 00010279
Permit Number 00010279
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. MAINS NEED TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.AS REQ`D
 BY ARTS;110-9/110-10 AND 215-5 OF THE
 NEC.
  
 2)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSDIE AND
 OUTSIDE ALL SLEEPING ROOMS.
  
 3)NOTE:PLEASE HAVE THE DEDICATED BATH(S)
 CIRCUT(S) LISTE ON PANEL SCHEDULE. MUST
 BE 20 AMP AND #12 AWG. THIS IS REQ`D BY
 ART;210-52D
  
 4)NOTE: NEED TO HAVE OUTLET MARKED ON
 WALL BY FRONT DOOR PER 210-52 OR 210-52H
  
 PLEASE NOTE A/C AND METER LOCATION AND
 CLEARANCES REQ`D BY 110-16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372