Plan Review Details - Permit 99121888
Plan Review Stops For Permit 99121888 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-12 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-12 |
Time |
14:10 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | 1)NOTE: NEED TO CORRECT OVERCURRENT | | PROTECTION FOR PANEL'B'. | | YOU SHOW 2P40 WITH A 52 AMP LOAD?? | | ALSO SHOW #8 AWG. WIRE IS TO BE SIZED | | FROM 310-16 AND FROM THE 75C COLUMN. | | | | PLEASE CORRECT THE ABOVE AND SUBMIT | | PLANS FOR REVIEW AND APPROVAL BEFORE | | ROUGH INSPECTION IS CALLED IN. IF THERE | | ARE ANY QUESTIONS PLEASE CALL. 659-8096 | | EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-05-18 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-05-18 |
Time |
09:17 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-05-18 |
Time |
09:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-01-28 |
Time |
07:52 |
Rev Time |
0.35 |
Received By |
jleech |
Date |
2000-01-28 |
Time |
07:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-01-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-27 |
Time |
05:55 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-01-27 |
Time |
05:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2000-03-03 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-03-03 |
Time |
11:37 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
2000-03-03 |
Time |
08:23 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | ****************PROVISO***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE SOIL REPORT,SUBMIT PRIOR TO | | FIRST INSPECTION. | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVALS FOR STORM PANELS,SUBMIT PRIOR | | TO INSTALLATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-01-20 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-01-20 |
Time |
08:48 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|