Plan Review Details - Permit 99121765
Plan Review Stops For Permit 99121765
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By dpalmer Date 2000-01-31 Time 15:22 Rev Time 0.00
Received By dpalmer Date 1900-01-31 Time 08:54 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AS REQ`D BY 110-9/230-65
 AND 215-5 OF THE NEC.
  
 2)NOTE: NEED TO SHOW SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 AS REQ`D BY NFPA-72 2-2.1.1.1
  
 3)NOTE:PLEASE SHOW REQ`D DEDICATED
 CIRCUTS FOR BATH(S)20 AMP AND #12 AWG
 AS REQ`D BY 210-52D
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE AN
 QUESTIONS PLEASE CALL 659-8096EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 09:08 Rev Time 0.50
Received By jleech Date 2000-01-22 Time 09:08 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 REVISE A/C DRAWINGS BEFORE ROUGH A/C
 INSPECTION.
 1. A/H UNITS NOT CAPABLE OF PUSHING CFMS
 INDICATED, BOTH UNITS.
 2. RETURN AIR AH#2, RETURN AIR CANNOT
 BE IN BATHROOM. R/A SHOULD BE SPLIT
 TO BEDROOMS WHICH ARE OVER 300CFMS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By tlarge Date 2000-01-13 Time 08:20 Rev Time 0.50
Received By tlarge Date 2000-01-13 Time 08:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-25 Cont ID  
Sent By fknapp Date 2000-02-25 Time 10:34 Rev Time 1.00
Received By fknapp Date 2000-02-25 Time 10:34 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-14 Cont ID  
Sent By fknapp Date 2000-02-14 Time 13:41 Rev Time 4.00
Received By fknapp Date 2000-02-14 Time 09:02 Sent To  
Notes
2001-01-08 00:00:00 
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE SOIL TEST REPORT
  
 2)PROVIDE RAISE SEAL OF DESIGN
 PROFESSIONAL ON PRODUCT APPROVAL
 SUBMITTAL FORMS
  
 3)PROVIDE PRODUCT APPROVAL FOR FRONT
 DOOR ASSEMBLY BEING USED
  
 4)PROVIDE SIZE OF FRONT DOOR TO BE USED
 ON PLANS
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-11 Cont ID  
Sent By gjoyce Date 2000-01-11 Time 09:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***