Plan Review Details - Permit 99121759
Plan Review Stops For Permit 99121759
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By jleech Date 2000-01-18 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2000-01-18 Time 15:17 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1. 4 TON UNIT IS NOT CAPABLE OF
 PROVIDING 2040 CFM. AS SHOWN ON
 DRAWING. REVISE DRAWINGS.
 2. ELECTRIC EXHAUST FAN IS REQUIRED
 IN MASTER SUITE TOILET ROOM.
 3APPROV:99121739 JW