Plan Review Details - Permit 99121678
Plan Review Stops For Permit 99121678
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By dpalmer Date 2000-02-01 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2000-02-01 Time 11:53 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND NEEDS TO BE ABLE TO HANDLE
 THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: SMOKE DETECTORS INSIDE AND OUT-
 -SIDE ALL SLEEPING ROOMS.
  
 3)NOTE: NEED TO HAVE CIRCUT FOR BATH(S)
 LISTED ON PANEL SCHEDULE AS PER 210-52D
 20 AMP AND #12 AWG.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEAS CALL 659-8096 EXT-
 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 10:08 Rev Time 0.35
Received By jleech Date 2000-01-22 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By tlarge Date 2000-01-13 Time 09:45 Rev Time 0.33
Received By tlarge Date 2000-01-13 Time 09:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-25 Cont ID  
Sent By fknapp Date 2000-02-25 Time 11:00 Rev Time 1.00
Received By fknapp Date 2000-02-25 Time 11:00 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-02-15 Cont ID  
Sent By fknapp Date 2000-02-15 Time 12:44 Rev Time 4.00
Received By fknapp Date 2000-02-15 Time 08:37 Sent To  
Notes
2001-01-08 00:00:00 
 ****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE SOIL TEST REPORT
  
 2)PROVIDE RAISE SEAL OF DESIGN
 PROFESSIONAL ON PRODUCT APPROVAL
 SUBMITTAL FORMS
  
 3)PROVIDE 32" CLEAR OPENING AT FRONT
 DOOR 1997 SBC 1012.1.1
  
 4)PROVIDE PRODUCT APPROVAL FOR FRONT
 DOOR ASSEMBLY BEING USED
  
 5)PROVIDE PICKETS IN GUARDRAILS THAT A
 4" SPHERE CANNOT PASS THRU 97 SBC 1015.3
  
 6)PROVIDE 1 HR FIRE RATING AT GLASS
 BLOCK OPENING ON 2ND FLOOR
  
 7)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-11 Cont ID  
Sent By gjoyce Date 2000-01-11 Time 09:22 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***