Plan Review Details - Permit 99121652
Plan Review Stops For Permit 99121652
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-11 Cont ID  
Sent By dpalmer Date 2000-02-11 Time 13:17 Rev Time 0.00
Received By dpalmer Date 2000-02-11 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-31 Cont ID  
Sent By dpalmer Date 2000-01-31 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2000-01-31 Time 14:17 Sent To  
Notes
2001-01-08 00:00:00*************UNSAT********************
  
 1)NOTE:NEED TO SUBMTI AIC RATING OF ALL
 EQUIPMENT MAINS. 110-9/230-65
  
 2)NOTE: NEED TO COMPLY WIHT REQ`MENTS
 OF SMOKE DETECTORS INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. AS PER 1993/1996
 NFPA-72 2-2.1.1.1
  
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE SHOW.
  
 4)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUT
 ON PANEL SCHDULE. AS PER 210-52D
  
 5)NOTE:PLEASE INCLUDE BLDG.STEEL ON
 RISER DIAGRAM AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.250-81/215-5
  
 6)NOTE:AS PER 110-16 A/C DISC.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 65908096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 09:50 Rev Time 0.50
Received By jleech Date 2000-01-22 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By tlarge Date 2000-01-13 Time 07:05 Rev Time 0.50
Received By tlarge Date 2000-01-13 Time 07:05 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO***************
 SANITARY RISER DOESN'T MATCH FLOOR PLAN.
 SUBMIT NEW RISER DIAGRAM PRIOR TO RGH.
 PLBG.INSP.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-02-11 Cont ID  
Sent By jcaloger Date 2000-02-11 Time 12:47 Rev Time 0.30
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-11 Cont ID  
Sent By gjoyce Date 2000-01-11 Time 09:40 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved