Plan Review Details - Permit 99121650
Plan Review Stops For Permit 99121650
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-01-06 Cont ID  
Sent By dlauderm Date 2000-01-06 Time 13:16 Rev Time 0.00
Received By dlauderm Date 2000-01-06 Time 13:14 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
 PASSED WITH PROVISOS:
 1.A TEE MUST BE PLACED BETWEEN THE METER
 AND THE EXISTING DOMESTIC BACKFLOW
 PREVENTER.THEN AN APPROVED DOUBLE
 CHECK BACKFLOW PREVENTER ASSEMBLY (DCA)
 CAN BE PLACED ON THE END OF THE TEE TO
 SERVE THE SPRINKLERS, THEN THE FIRE
 DEPARTMENT CONNECTION (FDC) CAN BE
 INSTALLED AFTER THE DCA SO THE WATER
 WILL NOT CONTAMINATE THE CITY OR
 BUILDING DRINKING WATER AS WELL AS NOT
 HAVING THE WATER FOR THE SPRINKLER
 SYSTEM GOING THROUGH TWO BACKFLOW
 PREVENTERS.
 2.THE SPRINKLER FLOWS SUPPLIED CALL FOR
 24 GALLONS PER MINUTE(GPM) FOR FIRE
 FLOW.A MINIMUM OF A 1" METER IS
 REQUIRED FOR THESE FLOWS.

Review Stop FS  
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By rturnque Date 2000-01-05 Time 09:48 Rev Time 0.20
Received By rturnque Date 1999-12-30 Time 08:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-01-07 Cont ID  
Sent By ndenmark Date 2000-01-07 Time 13:17 Rev Time 0.50
Received By ndenmark Date 2000-01-07 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By ndenmark Date 2000-01-06 Time 14:52 Rev Time 1.00
Received By ndenmark Date 2000-01-06 Time 14:52 Sent To  
Notes
2001-01-08 00:00:00*******CORRECTED BY REVISION************
  
 1. EXISTING METER DOES NOT HAVE THE
 CAPACITY TO PROVIDE ENGINEER'S REQUIRE-
 MENT OF 24 GPM @ 42.8 PSI.
 A MINIMUM OF A 1" METER IS REQUIRED TO
 OBTAIN THESE FLOWS. (SEE ENGINEERING PG)
 2. CORRECT METER SHALL BE INSTALLED
 PRIOR TO FIRE SPRINKLER PERMIT BEING
 APPROVED.
 3. PROVIDE PLANS SHOWING COMPLIANCE WITH
 PROVISO 1 OF ENGINEERING REQUIREMENTS.
 PER NKM