Plan Review Stops For Permit 99121621 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
F |
Date |
2002-09-06 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-09-06 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-09-06 00:00:00 | SHEETS A120 AND A122 ARCHITECT'S DATE | | 8/28/02. | | | | THE DETAIL FOR THE WOODEN RAMP DOES NOT | | COMPLY WITH SBC 1013.2 AND SBC 1517.2 | | OR FBC 1013.1 AND FBC 1511.2.1.PLEASE | | REVISE AS NECESSARY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
F |
Date |
2002-07-16 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-07-16 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-16 00:00:00 | REVISIONS SUBMITTED 6/24/02 SHEETS | | ADD-1 AND A801 TOGETHER WITH DORSKY | | HODGSON LETTER/ LAWRENCE LORDI. | | | | UL 419 AND UL 428 ARE RECOGNIZED | | ASSEMBLIES.UL 419 HAS FOUR POSSIBLE | | ASSEMBLIES FOR THE DESIRED TWO HOUR | | WALL CONSTRUCTION.WHICH IF ANY, WERE | | USED IN THE TWENTY ONE ENCLOSURES | | POSSIBILITIES SHOWN ON THIS SHEET? | | WHERE WAS THE UL 428 SHAFT WALL USED? | | | | RESPONSES #7 AND #8 IN THE DORSKY | | HODGSON LETTER DATED 6/18/02 SIGNED BY | | LAWRENCE LORDI.REGARDING THE CANOPY, | | THE HEIGHT ABOVE FINISH GRADE, | | (SIDEWALKS) WAS NOT SHOWN. | | | | I HAVE INCLUDED COPIES OF TWO PAGES FROM | | THE FAIR HOUSING ACT DESIGN MANUAL | | WHICH CLEARLY INDICATE A FOUR INCH HIGH | | "CURB" IS CONTRADICTORY TO THE ALLOWED | | FOUR INCH "DROP" CONTAINED IN THAT | | PUBLICATION. | | | | REVISONS #3 AND #4 ON SHEET A801 ARE | | APPROVED. | | | | SHEET ADD-1 IS BEING REJECTED, FOR THE | | ABOVE REASONS. | | | | THOSE WERE THE ONLY TWO PAGES IN THIS | | SUBMITTAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
F |
Date |
2002-07-16 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-07-16 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-16 00:00:00 | THE REVISIONS DATED 6/24/02 "REMOVE | | AWNINGS" AND HAVING VARIOUS NUMBERED | | DELTAS IN THE TITLE BLOCK, DO NOT | | APPEAR ON THE PLANS IN AGREEMENT WITH | | THE RESPECTIVE NUMBERED DELTAS. | | | | ALSO, SEE NOTE ON SUBMITTAL FORM FROM | | DOWNTOWN PLANNER RE: LOGO. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-07-05 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-21 00:00:00 | METAL FRAMING SHOP DRAWINGS, | | CALCULATIONS BY THOMAS KELLEHER PE. | | THE CALCULATIONS CITE ASCE 7-93.THE | | 1997 SBCCI INVOKED THE ASCE 7-95. | | PLEASE REVISE AS NECESSARY. | | | | PROVIDE A METAL FRAMING DETAIL FOR THE | | CANOPY THAT THE " TITAN ROOFING" PANELS | | WILL BE ATTACHED TO. | | | | THE FIRE PROTECTION SYSTEM FOR THE | | CANOPY IS A COLUMN DESIGN.HOW ARE THE | | HORIZONTAL STRUCTURAL MEMBERS PROTECTED? |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
F |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-20 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-14 00:00:00 | REVISIONS SUBMITTED 5/7/02 | | SHEET A801 DATED 5/2/02.SECTION | | 6/A801WHAT IS THE 1 1/2" ACCENT PANEL | | MADE OF? HOW IS IT ATTACHED? | | | | WHERE IN THE STRUCTURAL DRAWINGS IS THE | | FRAMING DETAIL FOUND? | | | | SSK 19THE NEW 7'-4" HEIGHT DOES NOT | | COMPLY WITH THE 98" HEIGHT REQUIRED BY | | THE FACBC SEC 4.6.5.IF IT IS NOT ON | | THE SITE ACCESSIBLE ROUTE PROVIDE | | SIGNAGE AS APPLICABLE. | | | | SSK 26-28SPECIFY THE TYPE OF WELDS TO | | BE USED IN ACCORDANCE WITH GOOD | | ENGINEERING PRACTICE.IF THE | | CONNECTIONS ARE TO BE DELEGATED, | | PROVIDE THE APPROPRIATE INFORMATION ON | | THE DRAWING.SEE 61G15-31.009 | | | | SSK 27 PLAN VIEW SHOWS THE FRONT OF THE | | CANOPY AS BEING STRAIGHT. THE | | ARCHITECTURAL PLANS DEPICT IT AS BEING | | CURVED.HOW IS THIS ACCOMPLISHED? |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
F |
Date |
2002-05-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-05-10 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-10 00:00:00 | REVISIONS SUBMITTED 5/1/02 | | SHEET A110 REVISIONS NUMBERED 1-8.THE | | PERMIT PLANS HAVE REV 1, SOME OF THE | | REVISONS ARE DATED TWO YEARS AGO, WHY | | ARE THEY JUST NOW BEING PROVIDED TO THE | | CITY FOR REVIEW? | | | | PROVIDE DETAILS FOR THE BUILT IN BAR | | SHOWN INCLUDING HC ACCESIBILITY | | REQUIREMENTS. | | | | THE PLANS HAVE REFERENCE SECTIONS TO | | A802.THE PERMIT PLANS DO NOT SHOW | | SECTION DETAILS NUMBERED THAT HIGH, | | THEYSTOP AT DETAIL 6, THESE PLANS SHOW | | 17. | | | | SHEET A111.PROVIDE A CONSTRUCTION | | DETAIL FOR THE SUSPENDED CEILING. | | REVISIONS SHOWN 1-6, PERMIT PLANS 0. | | | | SHEET A120 REVISIONS 1-6, PERMIT PLAN 0. | | THE HANDRAILS FOR THE STAIRS FROM THE | | POOL DECK TO THE CLUBHOUSE DO NOT | | COMPLY WITH THE 30" REACH RANGE OF SBC | | 1007.5.7.THE STAIRS AT THE FOUNTAIN | | AREA REQUIRE HANDRAILS ON BOTH SIDES | | AND THE RANGE OF REACH REQUIREMENTS OF | | SBC 1007.5.2ANDSBC 1007.5.7. | | | | SHEET A201 REV 1-8, PERMIT SET 1-4. | | PROVIDE STRUCTURAL DETAILS FOR THE | | CANOPY.THIS WAS REQUESTED ON MY | | CHECKLIST DATED 4/18/02 DENYING THOSE | | REVISIONS. | | | | WHAT PERMITTED PLAN DID THE THRESHOLD | | INSPECTOR USE TO INSPECT THIS | | STRUCTURAL WORK? | | | | SHEET A323 REVISIONS 1-3, PERMIT SET 1. | | PROVIDE A CONSTRUCTION DETAIL FOR THE | | ADDED MASONRY VEHICLE BARRIER WALL | | INCLUDING CALCULATIONS DEMONSTRATING | | COMPLIANCE WITH THE LOADS PRESCRIBED IN | | SBC 1608.2.3. | | | | SHEET A404 REVISIONS 1-4, PERMIT SET 0. | | PROVIDE A DETAIL FOR CONSTRUCTION OF | | THEADDED VAULT. | | | | SHEET A406 REVISIONS 1-5, PERMIT SET 0. | | PROVIDE DETAILS FOR THE GALVANIZED | | SHUTTER.WHAT IS IT FOR?THE 4" HIGH | | CURBS AT THE PATIO SLIDING DOORS DO NOT | | COMPLY WITH THE FAIR HOUSING ACT.SEE | | PART 2, CHAPTER 4, PAGE 4.11 OF THE FHA | | DESIGN MANUAL. | | | | SHEET A421 REVISIONS 1-3, PERMIT SET 0. | | PROVIDE A DETAIL OF WHAT THE ADDED | | WALKWAY WILL BE MADE OF. | | | | SHEET A425 REVISIONS 1-3, PERMIT SET 0. | | SECTION DETAILS REFERENCED AS"XX/804" | | ARE ABSENT FROM THE PERMIT PLANS. | | | | SHEET E1.06, PROVIDE INFORMATION FOR THE | | METHOD OF OPENING PROTECTIVE FOR THE | | ADDED EXHAUST FAN.SEE SBC TABLE 600. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-18 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-26 00:00:00 | REVISIONS SUBMITTED 2/28/02 HAVING | | VARIOUS DATES ON THE PLANS AND REVISION | | DELTAS 1 THROUGH 7.ARCH. PAGES | | | | SHEET A 101. PROVIDE STRUCTURAL DETAILS | | FOR THE ADDED LOUVERS PENETRATING THE | | EXTERIOR WALLS.SBC 104.2 | | | | SHEET A 202. PROVIDE STRUCTURAL DETAILS | | FOR THE REVISED ENTRY. | | | | SHEET A 206.PROVIDE STRUCTURAL DETAILS | | FOR THE ADDED MECHANICAL EQUIPMENT | | ADDRESSING THE CONCENTRATED LOADINGS | | AND NEW PENETRATION/OPENINGS. | | | | SHEET A 303.STRUCTURAL INFORMATION FOR | | THE ADDED COOLING TOWER ENCLOSURE, AND | | THE CURB SHOWN IN SECTION 6/A303. | | | | A 310 PROVIDE STRUCTURAL DETAILS FOR THE | | SUSPENDED CEILING FRAMING INCLUDING | | CONNECTION TO THE SLAB ABOVE. | | | | A 320.STRUCTURAL DETAILS FOR THE NEW | | ARCH FRAMING. | | | | A 323 AND A 425.PROVIDE STRUCTURAL | | DETAILS FOR THE ADDED CANOPY.ALSO IT | | DOES NOT APPEAR TO COMPLY WITH SBC | | 3204.3. | | REVISE AS NECESSARY. | | | | SHEET A 406 AND SEVERAL SUBSEQUENT PAGES | | INDICATE A 4" HIGH CURB AT THE PATIO | | SGD.THIS DOES NOT COMPLY WITH THE | | FAIR HOUSING MANUAL GUIDELINES PAGE | | 4.11PLEASE REVISE AS NECESSARY. | | | | SHEET ADD 1.PROVIDE THE FIRE DESIGN | | NUMBERS FOR THE PRIMARY AIRSHAFT WALLS. | | SEE SBC 701.5. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
A |
Date |
2001-03-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-03-20 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-03-20 00:00:00 | THE FIRE RATED WINDOWS SHOWN ON THE | | NORTH ELEVATIION ARE REQUIRED TO BE A | | TESTED ASSEMBLY COMPLYING WITH NFPA 80 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-09-13 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO SEE ARCH LETTER DATED 8/23/00 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2000-08-09 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-08-09 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LETTER WITH APPLCATION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-04-24 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-04-24 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FOUNDATION PERMIT ONLY,2ND REVIEW | | 1]INSPECTION LETTER FROM MIGNOGNA IS OK | | PROVIDE SIGNED AND SEALED COPY. | | 2]SUBMIT A CERTIFIED SOIL ANALYSIS | | REPORT-FOUNDATION REPORT. | | 3]THRESHOLD INSPECTOR MUST BE SIGNED UP | | AND APPROVED BEFORE PERMIT CAN BE | | ISSUED. | | 4]SURVEYS ARE NOT SIGNED AND SEALED. | | 5]SUBMIT COPYS OF ALL RIGHT OF WAY | | PERMITS AND RELEASES REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-03-10 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-03-10 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1]FOUNDATION PERMIT ONLY! | | SUBMIT THRESHOLD INSPECTION PLAN SIGNED | | AND SEALED BY A REGISTERED STRUCTUAL | | ENGINEER | | 2]SUBMIT FOUNDATION INSPECTION REPORT | | 3]THRESHOLD INSPECTOR IS REQUIRED,PLEASE | | CONTACT ASS. BUILDING OFFICIAL DON NEELY | | AT EXT.#8333 FOR APPROVED LIST | | 4]SUBMIT SIGNED AND SEALED SURVEYS | | 5]RIGHT OF WAY PERMITS AND RELEASES WILL | | BE REQUIRED,CONTACT ENGINEERING DEPART. | | AT 659-8040 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
16 |
Status |
P |
Date |
2002-08-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-06 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-06 |
Time |
17:27 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
15 |
Status |
P |
Date |
2002-07-31 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-08-05 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-31 |
Time |
18:21 |
Sent To |
|
|
Notes |
2002-07-31 00:00:00 | ***** REV FOR 6 AND 7 ON E 1.14 ONLY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
14 |
Status |
P |
Date |
2002-07-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-07-05 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-07-05 |
Time |
15:43 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
13 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-07-01 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-01 |
Time |
14:41 |
Sent To |
|
|
Notes |
2002-07-01 00:00:00 | LAYOUT FOR ELEC RM/FIRE PUMP RM. RISER | | OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
12 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-07-01 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-01 |
Time |
14:39 |
Sent To |
|
|
Notes |
2002-07-01 00:00:00 | ELEC LT SPEC BKS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
11 |
Status |
F |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-17 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-17 |
Time |
08:26 |
Sent To |
|
|
Notes |
2002-06-17 00:00:00 | ************ NOTE ************ | | | | PLEASE NOTE AS PER FEILD INSPECTION AND | | CONVERSATION WITH GC. | | PLANS/ RISER DIAGRAM IS TO BE REVISED | | TO CORRELATE WITH JOBSITE. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
10 |
Status |
F |
Date |
2002-05-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-30 |
Time |
06:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-30 |
Time |
06:21 |
Sent To |
|
|
Notes |
2002-05-30 00:00:00 | ************** UNSAT ************* | | | | 1)NOTE: PLEASE CLARIFY REVISIONS SHOWN | | FOR SOME PANELS ON RISER DIAGRAM AND | | NOTES REF "SEE PANEL SCHEDULES". PLEASE | | NOTE NO PANEL SCHEDULES WERE SUBMITTED | | FOR THOSE MENTIONED. NOTE REF CHANGE TO | | FEEDERS TO APTS ALSO.?METER CENTERS ALSO | | | | 2)NOTE: PLEASE NOTE THAT SINCE THIS | | REV WAS SUBMITTED, THE RISER DIAGRAM | | HAS CHANGED DUE TO FIELD EVALUATION OF | | MAIN DISC`S AND/OR GROUPING OF MAINS. | | PLEASE REVISE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-21 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-21 |
Time |
08:15 |
Sent To |
|
|
Notes |
2002-05-21 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE GROUPING OF MAINS | | PER 230-72 NOT MET. | | | | 2)NOTE: PLEASE NOTE SHUNT TRIP(S) | | SHOWN AS A MAIN DISCONNECT FOR 6E. | | PLEASE SEE 230-76 AND 230-79 | | | | 3)NOTE: PLEASE NOTE ELECTRICAL ROOM(S) | | LAYOUTS DO NOT CORRELATE WITH HOW IT | | IS ACTUALLY INSATLLED IN THE FIELD. | | | | 4)NOTE: PLEASE NOTE MAIN 1&2 "W" ON | | FIRST FLOOR AND NOT GROUPED WITH OTHERS | | ALSO DOES NOT MEET THE REQ`MENTS FOR | | FIRE DEPT. | | | | 5)NOTE: PLEASE SUBMIT OCP FOR FIRE PUMPS | | AND ASSC EQUIPMENT. PLEASE SEE 695-4/ | | 695-5. | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-18 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-18 |
Time |
10:27 |
Sent To |
B |
|
Notes |
2002-04-18 00:00:00 | *******************UNSAT!*************** | | | | NOTE: PLEASE NOTE THAT ALL PLANS | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | ING A TITLE BLOCK, MUST BE SIGNED, | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | RECORD. PER FS/FAC 481.221 & 471.025 | | SEE SHEET"F1". | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-27 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-27 |
Time |
15:10 |
Sent To |
FIRE |
|
Notes |
2002-03-27 00:00:00 | PLANS BEING RESTAMPED. OLD REV SHEETS | | FROM LAST YEAR. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-27 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-27 |
Time |
11:57 |
Sent To |
|
|
Notes |
2001-12-27 00:00:00 | ****************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE THAT THERE WERE MANY | | SHEETS FOR FIXTURES THAT ARE CLEAR AND | | DO NOT SHOW ANY LISTINGS FOR FIXTURES | | PLEASE SEE THE FOLLOWING AS A LIST | | OF FIXTURES NOTED: | | | | | | STERNBERGTYPE C | | BEGHELLITYPE XG | | THOMAS RES TYPE AB | | THOMAS RES TYPE AE | | ACCOLADETYPE PORCH | | BOYD TYPE P1 | | BALDINGERTYPE WI | | BOYD TYPE P3 | | ILLUMNATION LTG TYPE P4 | | SCHMITZ TYPE P5 | | MINKA AIRE TYPE FAN | | RESOLTE MANIFESTO TYPE W4 | | LUMEC "STREET LUMINAIRE" | | AMERON "STREET POLE" VES-4-3 T6MOD | | | | | | PLEASE SUBMIT THE ABOVE CLARIFICATION | | FOR ALL OF THE ABOVE FIXTURS BEING | | USED. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-14 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-14 |
Time |
08:12 |
Sent To |
|
|
Notes |
2001-11-14 00:00:00 | REV TO E2.06 ROOM LAYOUT |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-01-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-04 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-04 |
Time |
16:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISION FOR FIRST LEVEL. POWER |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-08-15 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-08-15 |
Time |
10:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2000-08-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-04-11 |
Time |
10:46 |
Rev Time |
2.30 |
Received By |
jleahy |
Date |
2000-04-11 |
Time |
10:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | THIS PERMIT IS FOR A LIMITED AMOUNT OF | | CONDUITS TO BE INSTALLED UNDERGROUND!!!! |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-01-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-01-20 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-08-29 |
Time |
07:53 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- NO ELECTRIC SHOWN | | 2- NO ELECTRIC SHOWN | | 3- NO ELECTRIC SHOWN | | 4- NO ELECTRIC SHOWN | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 5- NO ELECTRIC SHOWN!!!!!!!!!!!!!!!!!!!! |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
6 |
Status |
P |
Date |
2002-07-15 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-07-15 |
Time |
15:22 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-07-15 |
Time |
15:21 |
Sent To |
|
|
Notes |
2002-07-15 00:00:00 | PASSED: | | 1. REVIEWED FOR SIGN LAYOUT IN PARKING | | GARAGE LEVELS. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
5 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-01-11 |
Time |
16:02 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-01-11 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-11-05 |
Time |
9:08 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2001-11-05 |
Time |
9:07 |
Sent To |
|
|
Notes |
2001-11-02 00:00:00 | PASSED: | | 1. ADA RAMPS MUST HAVE TACTILE, SLIP | | RESISTANT SURFACE . | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
F |
Date |
2001-11-02 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-10-23 |
Time |
09:35 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2001-10-23 |
Time |
09:34 |
Sent To |
|
|
Notes |
2001-10-23 00:00:00 | FAILED: | | 1. ADA RAMPS MUST HAVE TACTILE, SLIP | | RESISTANT SURFACE. | | 2. BASE AND SUBGRADE MUST BE COMPACTED | | TO 98% OF AASHTO T-180 PRIMED AND HAVING | | THE THICKNESS AS ORIGINAL PLANS. | | 3. WORK WITHIN PUBLIC R.O.W WILL REQUIRE | | A SEPARATE PERMIT FROM CITY ENGINEER'S | | OFFICE / FDOT. | | 4. IS THE EXISTING INLET AT CORNER OF | | NARCISSUS AND EVERNIA RELOCATED/RECONS- | | TRUCTED ?? | | 5. PROPOSED REVISION WOULD REDUCE THE | | WESTBOUND TRAVEL LANE ON EVERNIA ST. | | TO 8', PLEASE VERIFY. | | 6. PLEASE REFER TO THE ORIGINAL APPROVED | | PLAN FOR OVERLAY REQUERMENTS. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-12-05 |
Time |
15:21 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED | | SHOP DRAWINGS FOR WATER AND SEWER |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2000-06-13 |
|
|
Cont ID |
|
Sent By |
dlauderm |
Date |
2000-06-13 |
Time |
15:44 |
Rev Time |
1.00 |
Received By |
dlauderm |
Date |
2000-06-13 |
Time |
15:40 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLANS APPROVED THRU OUR UTILITIES | | DEPARTMENT OFFICE AT 45TH ST. | | CONTRACTOR NEEDS TO SUBMIT THOSE PLANS | | WITH THE UTILITY DEPARTMENT APPROVAL | | STAMP ON IT TO B&Z. | | PER COMMISSION APPROVAL ON 6-12-00 | | THE FOOTER EASEMENTS ARE APPROVED. | | THE FOOTERS IN THE CITY RIGHTS-OF-WAY | | MUST BE 5'DEEP. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
14 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-08-20 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-20 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
13 |
Status |
F |
Date |
2002-07-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-06 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-07-18 |
Time |
12:09 |
Sent To |
|
|
Notes |
2002-07-18 00:00:00 | 1) PLEASE SUBMIT A COMPREHENSIVE | | NARRATIVE FOR THE SMOKE CONTROL SYSTEM | | PLANNED FOR USE. THE ORIGINAL DESIGN | | INDICATED PRESSURIZING TWO FLOORS ABOVE | | AND TWO FLOORS BELOW WITH THE FLOOR | | OF INCIDENT BETWEEN THESE. DURING | | TESTING WITH CITY MECHANICAL DIVISION | | PERSONNEL, PROBLEMS WERE IDENTIFIED | | AND THUS THE ORGINAL DESIGN HAS SINCE | | BEEN CHANGES. THE NARRATIVE IS | | REQUIRED FROM THE ENGINEER OF RECORD | | TO PROVIDE SUPPORTIVE DOCUMENTATION | | FOR THE DESIGN CHANGE. | | | | 2) IS IS UNDERSTOOD BY THIS OFFICE THAT | | A TEMPROARY SHROUD HAS BEEN INSTALLED | | ON THE FAN. THIS TEMPORARY DEVICE IS | | TO BE REMOVED AS IT NOT PART OF THE | | ORIGINAL LISTING FOR THE FAN DEVICE. | | | | 3) THE ACCEPTANCE TESTING CRITERIA | | NOTED ON THE PLANS ARE TO BE FOLLOWED. | | | | 4) THE OWNER, ENGINEER, AND CONTRACTOR | | MUST ACCEPT THE LIABILTIY FOR | | THE PRESCRIBED SYSTEM DURING TESTING | | SINCE THE DESIGN INTENT HAS CHANGED | | SIGNIFICANTLY. THE ENGINEER OF RECORD | | SHALL BE CONSULTED DURING THE ENTIRE | | TESTING PROCESS. | | | | 5) THE FUNCTIONAL APPROVAL BY CITY | | OFFICIALS WILL ONLY OCCUR AFTER | | MUTUALLY AGREED UPON TESTING METHODS | | AND RESULTS ARE DISCUSSSED. | | | | 6) ALL APPLICABLE BUILDING, FIRE , AND | | MECHANICAL CODES ARE TO BE MET FOR | | THE SYSTEM WITHIN THE BUILDING. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
12 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-20 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-20 |
Time |
10:17 |
Sent To |
|
|
Notes |
2002-06-20 00:00:00 | THIS REVIEW WAS PERFORMED ON THE FLAME | | SPREAD SPECIFICATION BOOK THAT WAS | | SUBMITTED TO CONSTRUCTION SERVICES | | DEPARTMENT ON JUNE 18, 2002. | | | | 1) IT APPEARS THAT THE WALLCOVERINGS | | LOCATED WITHIN THE BOOK APPEAR TO MEET | | THE REQUIREMENTS FOR CLASS A MATERIALS | | PER THE NATIONAL FIRE PROTECTION | | ASSOCIATION. THESE MATERIALS WILL BE | | APPROVED BY THE BUREAU OF FIRE | | PREVENTION. PLEASE HAVE COPIES AVAILABLE | | REGARDING THE FLAMESPREAD RATINGS | | OF THESE MATERIALS SHOULD YOU BE ASKED | | TO PROVIDE DOCUMENTATION. | | | | 2) THE ITEMS SUBMITTED WITHIN THE BOOK | | DETAILING THE FURNISHINGS HAVE BEEN | | REVIEWED. SINCE SOME FURNISHINGS ARE | | INCIDENTAL TO VARIOUS ROOM USES, THIS | | OFFICE WILL ACCEPT THE DOCUMENTATION | | AS PRESENTED. TYPICALLY, FLAME SPREAD | | RATINGS FOR FURNISHINGS ARE NOT | | SUBJECTED TO SAME REVIEW AS THE | | INTERIOR FINISH AS THE WALLS, CEILINGS | | OR COLUMNS UNLESS THE AUTHORITY HAVING | | JURISDICTIONS MANDATES IT. IT WAS NOTED | | THAT SOME TESTING HAD OCCURED TO THE | | MATERIAL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
11 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-19 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-19 |
Time |
14:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
10 |
Status |
P |
Date |
2002-05-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-23 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-23 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
9 |
Status |
P |
Date |
2002-04-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-12 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-12 |
Time |
13:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
8 |
Status |
N |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-27 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-10 |
Time |
16:12 |
Sent To |
|
|
Notes |
2002-01-10 00:00:00 | 1) STEPS NEAR POOL ARE TO BE SLIP | | RESISTANT. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-11-21 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-11-21 |
Time |
12:27 |
Sent To |
|
|
Notes |
2001-11-21 00:00:00 | THIS PLAN REVIEW STOP IS FOR THE | | PRODUCT APPROVAL DATA THAT WAS SUBMITTED | | FOR THE HOOD EXHAUST DUCT SCRUBBER UNIT | | PROPOSED FOR ONE OF THE RETAIL SPACES. | | PLEASE BE ADVISED THAT IF THIS UNIT IS | | ACCEPTABLE TO CITY OFFICIALS, A SEPARATE | | FIRE SUPPRESSION SYSTEM WILL BE REQUIRED | | PER NFPA 96. ALSO NO DOWNGRADES OF THE | | EXHAUST DUCT BEYOND THE SCRUBBER UNIT | | WILL BE PERMITTED. ALSO APPROVAL IS | | DIFFICULT TO GIVE AT THIS TIME BECAUSE | | PLANS HAVE NOT BEEN RECEIVED OR REVIEWED | | FOR THE TENANT SPACE HOOD,DUCT,AND | | EXTINGUISHING SYSTEM WHICH WOULD WORK | | IN CONJUNCTION WITH THE PROPSED | | SCRUBBER UNIT. THE EXHAUST DUCT | | TERMINATIONS MUST COMPLY WITH THE | | REQUIREMENTS OF NFPA 96 AS WELL AS THE | | REST OF THE INSTALLATION. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-11-14 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-11-14 |
Time |
14:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2000-12-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-12-28 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-12-28 |
Time |
10:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-22 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ON AUGUST 22, 2000, WRITER AND CHIEF | | MECHANICAL INSPECTOR NANCY DENMARK MET | | WITH STRAND AND SUFFOLK CONSTRUCTION | | REPRESENATIVES. THE FOLLOWING ITEMS WERE | | DISCUSSED: | | 1) TESTING PROCEDURES ARE TO BE | | SUBMITTED FOR THE SMOKE CONTROL SYSTEM. | | 2) INFORMATION IS TO BE SUBMITTED ON | | WHAT THE SMOKE CONTROL PANEL IS TO | | LOOK LIKE AND THE TYPE CONTROLS WILL | | BE ON THE PANEL. | | 3) MINIMUM TESTING EQUIPMENT FOR | | SMOKE CONTROL SYSTEM IS TO BE NOTED | | ON PLANS. A LETTER IS TO BE SUBMITTED | | ON AUGUST 23, 2000, REGARDING THESE | | ISSUES. APPROVED PROVISO |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2000-08-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-09 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) MORE INFORMATION REQUIRED FOR THE | | FIREFIGHTERS SMOKE CONTROL STATION. THE | | PLANS DO NOT INDICATE WHAT WILL BE | | FEATURED ON THE PANEL. PLEASE REFER TO | | NFPA 92A, SECTION 3-4.3.4 REGARDING | | MINIMUM REQUIREMENTS. | | 2) NO TESTING EQUIPMENT NOTED ON | | DRAWINGS. PLEASE SEE NFPA 92A, SECTION | | 4-3.2. THIS EQUIPMENT SHALL BE NOTED | | ON THE PLANS TO ASSIST IN TESTING THESE | | LIFE SAFETY SYSTEMS. | | 3) TYPE AND DURATION OF SMOKE BOMBS | | TO BE USED NOT IDENTIFIED. NO CRITERIA | | NOTED ON WHAT IS EXPECTED DURING TESTING | | WITH SMOKE BOMBS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-04-19 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
2000-04-19 |
Time |
10:46 |
Rev Time |
1.00 |
Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. PROVIDE DOOR SCHEDULE | | 2. FIRE ALARM SYSTEM SHALL BE CLASS "A" | | OR ADDRESSABLE. | | 3. PROVIDE ADDITIONAL STANDPIPE. | | 4. ALL EXIT DOORS SHALL SWING IN THE | | DIRECTION OF EXIT TRAVEL. | | 5. PROVIDE 2 1/2"TO 1 1/2" REDUCERS ON | | ALL STANDPIPES. | | 6.ALL APT. DOORS SHALL BE 20 MIN., SELF | | CLOSING, FIRE DOORS. | | 7. ALL INTERIOR STAIRWELL DOORS SHALL | | BE CLASS B RATED, SELF CLOSING, FIRE | | DOORS. | | 8. PROVIDE FIRE SPRINKLER DRAWINGS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-01-07 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
2000-01-07 |
Time |
10:12 |
Rev Time |
0.50 |
Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
14 |
Status |
P |
Date |
2002-08-05 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-08-05 |
Time |
12:59 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2002-08-05 |
Time |
12:59 |
Sent To |
E |
|
Notes |
2002-08-05 00:00:00 | ADDITION OF MOTORIZED DAMPER TO 2 | | SMALLER STAIR WELLS FOR STAIR | | PRESSURIZATION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
13 |
Status |
P |
Date |
2002-07-29 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-07-29 |
Time |
07:50 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2002-07-29 |
Time |
07:50 |
Sent To |
|
|
Notes |
2002-07-29 00:00:00 | NARRATIVE FOR CHANGES TO BUILDING | | SEQUENCE AND PLANS REFLECTING CHANGES |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
12 |
Status |
F |
Date |
2002-07-18 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-07-18 |
Time |
12:28 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2002-07-18 |
Time |
12:28 |
Sent To |
|
|
Notes |
2002-07-18 00:00:00 | DENIED AS SUBMITTED | | | | SEE FIRE PLAN REVIEW FOR FULL DETAILS | | TEST AND BALANCE REPORT TO REFLECT CFM | | ON ENGINEERS DRAWING. | | PROVIDE INFORMATION AS REQUESTED BY FIRE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
11 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-06 |
Time |
15:25 |
Rev Time |
5.00 |
Received By |
pkrauss |
Date |
2002-03-05 |
Time |
16:05 |
Sent To |
|
|
Notes |
2002-03-06 00:00:00 | | | MECHANICAL PERMIT 00120524 | | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | DATA FOR DRYERS BEING INSTALLED IN | | UNITS THAT THE IN-LINE FAN HAS BEEN | | DELETED.EXHASUT DUCT EXCEEDS 25 FT | | MAXIMUM AS PER 1997 SMC 509.3. | | | | REVISIONS APPROVED WITH THE EXCEPTION | | OF"PROPOSED KITCHEN HOOD".TERMINATION | | FOR GREASE DUCT SHALL COMPLY WITH NFPA | | 96 AND 1997 SMC CHAPTER 5.TERMINATION | | OF EXHAUST SHALL BE LOCATED 10 FT FROM | | ANY ADJACENT BUILDING, PARKING AREA, | | ADJACENT PROPERTY LINE, WINDOW, DOOR OR | | AIR INTAKE.ADDITIONAL PLANS & PERMITS | | REQUIRED FOR HOOD (GREASE DUCT & MAKEUP | | AIR), FIRE SUPRESSION, AND WALKIN | | COOLERS/FREEZERS. | | | | PROVIDE MANUFACTURER SUBMITTAL DATA | | WITH PLANS & PERMIT APPLICATION.PLEASE | | NOTE, THERE SHALL BE NO DOWNGRADING | | OTHER PARTS OF THE EXHAUST SYSTEM DUE | | TO THE INSTALLATION OF THE "ECOLO AIR" | | SYSTEM AS PER NFPA 96 6-3.FIRE | | SUPRESSION SYSTEM REQUIRED AS PER NFPA | | 96 6-3.1. | | | | PLEASE NOTE 1 SET OF REVISIONS SUBMITTED | | MECHANICAL SHEETS M104, M106, & M108, | | ARE DIFFERENT.REVISION 4 IS DATED JUL | | 20, 2001 AND PLAN SHEETS DIFFER.THE | | OTHER SET OF PLANS SUBMITTED THE | | AFOREMENTIONED PLAN SHEETS ARE DATED | | JUL 20, 2001 AND ALSO INDICATE LATEST | | REVISON TO BE #4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
10 |
Status |
N |
Date |
2002-01-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-05 |
Time |
07:54 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2002-01-05 |
Time |
07:50 |
Sent To |
|
|
Notes |
2002-01-05 00:00:00 | MECH PERMIT 00120524 | | NO MECHANICAL REVISIOS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
9 |
Status |
P |
Date |
2001-07-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-16 |
Time |
13:18 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-07-16 |
Time |
13:16 |
Sent To |
|
|
Notes |
2001-07-16 00:00:00 | SUBMITTAL DATA FOR HEAT PUMPS, BATHROOM | | EXHAUST FANS AND POOL EXHAUST FAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
8 |
Status |
P |
Date |
2001-05-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-05-08 |
Time |
09:06 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-05-08 |
Time |
09:06 |
Sent To |
|
|
Notes |
2001-05-08 00:00:00 | REVIEW DONE UNDER MECH PERMIT 00120524 | | SUBMITTAL OF FAN MOTOR FOR COOLING TWR. | | CHANGED FROM 15 HP TO 25 HP. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-05-07 |
Time |
14:44 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-05-07 |
Time |
14:44 |
Sent To |
|
|
Notes |
2001-05-07 00:00:00 | *******************DENIED*************** | | | | IN RESPONSE TO YOUR LETTER DATED 4/26/01 | | (A/C CLOSET), THIS WILL BE AN ACCESS | | CODE ISSUE.1997 SMC 304.2, SUFFICIENT | | CLEARANCE FOR MAINTENANCE/REPLACEMENT | | AS WELL AS ACCESSIBILITY TO VENT | | CONNECTIONS. | | | | | | IF YOU HAVE ANY QUESTION PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-06 |
Time |
09:06 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-04-06 |
Time |
09:06 |
Sent To |
|
|
Notes |
2001-04-06 00:00:00 | APPROVED UNDER MECH PERMIT #00120524. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2001-01-09 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
09:37 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2001-01-09 |
Time |
09:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
N |
Date |
2000-08-25 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-08-22 |
Time |
14:18 |
Rev Time |
2.00 |
Received By |
ndenmark |
Date |
2000-08-22 |
Time |
14:18 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | | | 1.PROVIDE INFORMATION ON TEST ACCEPTANCE | | PROCEDURES FOR SMOKE CONTROL SYSTEMS | | 2.EXHAUST DUCT SYSTEM FOR KITCHEN GREASE | | HOOD HAS NOT BEEN APPROVED AND SHALL BE | | APPROVED PRIOR TO ANY SYSTEM INSTALLATIO | | DUE TO ACCESS CONSIDERATIONS OF SHAFT AN | | TERMINATION OF EXHAUST FAN. | | 3. NOTE: FIRE FLOOR SHALL NOT BE PRESSUR | | IZED PER REDLINE ON MECH DRAWING AND | | ELECTRIC SEQUENCE OF OPERATION | | | | REFER TO PERMIT NUMBER 00041269 FOR | | ADDITIONAL PLAN REVIEW COMMENTS FOR THIS | | ADDRESS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2000-08-25 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-05-01 |
Time |
08:19 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-05-01 |
Time |
08:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | MECHANICAL APPROVED FOR FOUNDATION ONLY | | NO MECHANICAL WORK TO BE DONE WITH THIS | | PERMIT PRIOR COMMENTS FOR BUILDING STILL | | APPLY TO BUILDING |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2000-04-20 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-04-20 |
Time |
09:59 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-04-20 |
Time |
09:54 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************NOTES******************* | | INSUFFICIENT MECHANICAL INFOMATION TO | | REVIEW.AS PER REVIEW DONE ON 01.05.00 | | BY NANCY. | | LETTER ATTACHED TO PLANS FROM PROJECT | | ARCHITECT ON THE MECH. COMMENTS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-01-05 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-01-05 |
Time |
13:09 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-01-05 |
Time |
13:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***********NOT ENOUGH INFORMATION****** | | | | INSUFFICIENT MECHANICAL INFORMATION TO | | REVIEW: | | PROVIDE DETAILS AT TIME OF SUBMITION FOR | | BUILDING REVIEW. INCLUDE: | | EQUIPMENT TYPES AND LOCATION | | REFRIGERANT TYPE AND QUANTITY PER 1997 | | SMC CHAPTER 11 | | DUCT LAYOUT, SIZES AND SPECIFICATIONS | | FAN SHUT DOWN PER 1997 SMC 406,NFPA90A, | | AND 1997 SBC 412.2 | | SMOKE CONTROL PER 1997 SBC 412.5 | | STAIRWELL PRESSURIZATION PER 1997 SMC | | 408 AND NFPA 92A | | INCLUDE SEQUENCE OF OPERATION FOR SMOKE | | CONTROL AND FAN SHUT DOWN SYSTEMS | | SHAFT ENCLOSURE DETAILS FOR EXHAUST DUCT | | FOR HOOD AND MAKE UP AIR LOCATION FOR | | HOOD | | OUTSIDE AIR CALCULATIONS AND AIR BALANCE | | SCHEDULE PER ASHRAE 62-89 AND SMC 501.2 | | | | | | NOTE:SMC=STANDARD MECHANICAL CODE | | SBC=STANDARD BUILDING CODE | | NFPA=NATIONAL FIRE PROTECTION ASSOCIA- | | TION |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
13 |
Status |
P |
Date |
2002-08-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-10 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-10 |
Time |
15:09 |
Sent To |
|
|
Notes |
2002-08-10 00:00:00 | REVISION OK W/PROVISO - UNDERCOUNTER | | W/HEATER - SHALL BE READILY ACCESSIBLE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
12 |
Status |
P |
Date |
2002-07-03 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-07-03 |
Time |
10:13 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-03 00:00:00 | PLUMBING PLAN REVIEW, FOUNTAIN,PES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
11 |
Status |
F |
Date |
2002-06-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-03 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-03 |
Time |
10:31 |
Sent To |
|
|
Notes |
2002-06-03 00:00:00 | DENIED | | REFERENCE: SPC-94- FACBC-97 | | | | 1) SHT A110 SHOW DETAIL FOR WATER HEATER | | SHOW HOW IT WILL BE READILY ACCESSIBLE. | | SHOW PIPING FOR T/P RELIEF LINE AND FOR | | PAN DRAIN. | | 2) SHT A110 DOOR SHALL NOT SWING INTO | | THE CLEAR FLOOR SPACE OF ANY HDCP FIXT- | | URE. SEC 4.22.2 | | 3) SHT P126 PLEASE SUBMIT FACTORY INFO. | | FOR MISTING MACHINE. SHOW LISTING FOR | | PRODUCT APPROVAL. | | 4) SK-P-1/SK-P-2 RISER DIAGRAMS, HUB | | DRAINS NOT APPROVED. FLOOR SINK REQUIRED | | FOR ALL INDIRECT WASTE. SEC 804.5 | | 5) SHT A110 PLEASE PROVIDE CHANGE IN | | SANT RISER DIAGRAM FOR NEW SINK IN CLUB | | ROOM | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-13 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-13 |
Time |
13:43 |
Sent To |
|
|
Notes |
2002-05-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) PLEASE NOTE THAT ALL PLANS DRAWN BY | | AN ENGINEER SHALL BE SIGNED, SEALED, AND | | DATED BY THE ENGINEER OF RECORD. | | 61G15-23.002 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-18 |
Time |
14:44 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2002-03-18 |
Time |
14:44 |
Sent To |
|
|
Notes |
2002-03-18 00:00:00 | REVISION OK - IRRIGATION FOR PLANTERS | | WITH BACKFLOW IN POOL EQUIP. ROOM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-14 |
Time |
11:42 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-01-14 |
Time |
11:42 |
Sent To |
|
|
Notes |
2002-01-14 00:00:00 | SUBMITTAL FOR PUMP STATION APPROVED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-01 |
Time |
17:26 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-10-01 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-03-27 |
Time |
17:35 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-03-27 |
Time |
17:35 |
Sent To |
|
|
Notes |
2001-03-27 00:00:00 | PRODUCT APPROVAL BALL VALVES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2001-01-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-02 |
Time |
15:58 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2001-01-02 |
Time |
15:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-20 |
Time |
07:27 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2000-12-20 |
Time |
07:26 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PRODUCT APPROVAL MANUFACTURES CUT SHEETS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2000-08-25 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-24 |
Time |
11:25 |
Rev Time |
6.00 |
Received By |
pschmitz |
Date |
2000-08-24 |
Time |
11:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ******************PROVISO*************** | | 1)SHT.A-601-BACKING FOR GRAB BARS FOR | | THE TUB ALONG THE LONG WALL SHALL COMPLY | | W/THE FHA REQ.#6,FIG.4.THE PLANS SHOW 8" | | MAX.TO THE BOTTOM OF THE BACKING AND THE | | FHA REQ.IS 6". | | | | 2)SHT.A-453-UNIT D9-THE WATER CLOSET | | INFRINGES ON THE CLEAR FLOOR SPACE IN | | THE M.B.TOILET ROOM.COMPLY W/FHA 24 CFR | | 100.205(C)(3)(IV). | | | | 3)SHTS.A-120,A204,A414 SHOW 1 TOILET | | ROOM IN THE POOL CLUBHOUSE AND SHT.A110 | | SHOWS 2 TOILET ROOMS.PLEASE REVISE SO | | ALL APPLICABLE SHEETS CORRELATE. | | | | 4)SHT.A-601-A MIN. OF 29"IS REQD.UNDER | | LAV.FROMM FINISH FLOOR TO BOTTOM OF | | APRON,NOT 27".COMPLU W/FACBC SEC.4.19. | | | | 5)A DRINKING FOUNTAIN IS REQD.INSIDE THE | | CLUBHOUSE PER TABLE 407.DRINKING | | FOUNTAIN IS REQD.IN THE CLUBHOUSE PER | | TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | MADE FOR PEOPLE WHO HAVE TROUBLE BEND- | | ING OR STOOPING. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-04-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-04-30 |
Time |
13:20 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | PERMIT IS FOR FOUNDATION ONLY. | | PLANS SHALL BE APPROVED BY CITY OF WPB | | ENGINEERING DEPT.FOR STORM & WATER. | | | | PREVIOUS PLUMBING COMMENTS HAVE NOT BEEN | | ADDRESSED.NO PLUMBING SHALL BE INSTALLED | | UNDER THIS PERMIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2000-01-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-29 |
Time |
06:33 |
Rev Time |
3.00 |
Received By |
tlarge |
Date |
2000-01-31 |
Time |
06:32 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHT.A001-APPLICABLE CODES-THE 1994 EDIT. | | OF THE STANDARD PLBG.CODE W/PALM BEACH | | COUNTY AMENDMENTS IS THE ADOPTED | | STANDARD.REVISE NOTE. | | | | THE MAXIMUM CAPACITY OF GREASE INTER- | | CEPTOR SHALL BE 1250 GALS.PER STATE OF | | FLA.HEALTH DEPT.REQS.CHAPT.64E-6.013(5). | | | | SIZE AND CAPACITY OF INTERCEPTORS SHALL | | BE APPROVED BY CITY OF WPB REGIONAL | | WASTEWATER TREATMENT PLANT.CONTACT | | RODNEY COMPO AT (561)835-7423. | | | | SUBMIT DETAIL OF OIL/SAND INTERCEPTOR. | | SPC1004.2. | | | | SHTS.P1.01,1.02,SHOWS 6" INLET TO OIL/ | | SAND INTERCEPTOR AND 4" OUTLET.SPC 709.1 | | | | SUBMIT ISOMETRIC DRAWINGS FOR ENTIRE | | SCOPE OF WORK TO BE DONE AT THIS TIME. | | SIZE ALL LINES AND INDICATE SLOPE OF | | PIPE.COUNTYWIDE AMENDMENTS TO SPC SEC. | | 104.2.1. | | | | SUBMIT ISOMETRIC FOR STORM DRAINAGE | | SYSTEM.SHOW SQUARE FOOT AREA DRAINED BY | | EACH ROOF DRAIN AND SUPPLY CALCULATIONS | | FOR SECONDARY DRAINAGE FOR ROOF.COMPLY | | W/SBC SEC.1517.6.4.1-1517.6.4.3. | | SPC 1108.1,1108.2.,APPENDIX "A",TABLE | | A101.2.INDICATE SLOPE OF PIPE. | | | | INDICATE WATER SOURCE FOR IRRIGATION | | SYSTEM.IF FROM A NON-POTABLE SOURCE A | | WATER USE PERMIT FROM SFWMD MAY BE REQD. | | PER F.S.373.219. | | | | NOTE:PLUMBING PLAN REVIEW IS FOR SHELL | | ONLY.DOES NOT INCLUDE REVIEW FOR LIVING | | UNITS,COMMON AREAS,OR REQS.FOR HANDICAP | | ACCESSIBILITY. | | | | THIS IS FOUNDATION ONLY PERMIT.NO | | PLUMBING WORK OF ANY NATURE IS PERMITTED | | 3/8/00.TLARGE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2002-07-11 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-07-11 |
Time |
14:26 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-11 00:00:00 | SEPARATE PERMIT REQUIRED FOR LOGO, THE | | LOGO SHALL BE NO GREATER THAN 40 SQ. | | SEE ARTICLE IV, SEC 33-47(F)(3) |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
N |
Date |
2002-06-20 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-06-20 |
Time |
10:02 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
2002-06-20 |
Time |
09:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-01-10 |
Time |
15:37 |
Rev Time |
0.25 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-08-31 |
Time |
09:01 |
Rev Time |
0.25 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | WITH PROVISO |
|
|