Plan Review Details - Permit 99121621
Plan Review Stops For Permit 99121621
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2002-09-06 Cont ID  
Sent By hpiskura Date 2002-09-06 Time 14:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-09-06 00:00:00SHEETS A120 AND A122 ARCHITECT'S DATE
 8/28/02.
  
 THE DETAIL FOR THE WOODEN RAMP DOES NOT
 COMPLY WITH SBC 1013.2 AND SBC 1517.2
 OR FBC 1013.1 AND FBC 1511.2.1.PLEASE
 REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2002-07-16 Cont ID  
Sent By hpiskura Date 2002-07-16 Time 13:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-16 00:00:00REVISIONS SUBMITTED 6/24/02 SHEETS
 ADD-1 AND A801 TOGETHER WITH DORSKY
 HODGSON LETTER/ LAWRENCE LORDI.
  
 UL 419 AND UL 428 ARE RECOGNIZED
 ASSEMBLIES.UL 419 HAS FOUR POSSIBLE
 ASSEMBLIES FOR THE DESIRED TWO HOUR
 WALL CONSTRUCTION.WHICH IF ANY, WERE
 USED IN THE TWENTY ONE ENCLOSURES
 POSSIBILITIES SHOWN ON THIS SHEET?
 WHERE WAS THE UL 428 SHAFT WALL USED?
  
 RESPONSES #7 AND #8 IN THE DORSKY
 HODGSON LETTER DATED 6/18/02 SIGNED BY
 LAWRENCE LORDI.REGARDING THE CANOPY,
 THE HEIGHT ABOVE FINISH GRADE,
 (SIDEWALKS) WAS NOT SHOWN.
  
 I HAVE INCLUDED COPIES OF TWO PAGES FROM
 THE FAIR HOUSING ACT DESIGN MANUAL
 WHICH CLEARLY INDICATE A FOUR INCH HIGH
 "CURB" IS CONTRADICTORY TO THE ALLOWED
 FOUR INCH "DROP" CONTAINED IN THAT
 PUBLICATION.
  
 REVISONS #3 AND #4 ON SHEET A801 ARE
 APPROVED.
  
 SHEET ADD-1 IS BEING REJECTED, FOR THE
 ABOVE REASONS.
  
 THOSE WERE THE ONLY TWO PAGES IN THIS
 SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2002-07-16 Cont ID  
Sent By hpiskura Date 2002-07-16 Time 08:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-16 00:00:00THE REVISIONS DATED 6/24/02 "REMOVE
 AWNINGS" AND HAVING VARIOUS NUMBERED
 DELTAS IN THE TITLE BLOCK, DO NOT
 APPEAR ON THE PLANS IN AGREEMENT WITH
 THE RESPECTIVE NUMBERED DELTAS.
  
 ALSO, SEE NOTE ON SUBMITTAL FORM FROM
 DOWNTOWN PLANNER RE: LOGO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-07-05 Time 15:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-21 00:00:00METAL FRAMING SHOP DRAWINGS,
 CALCULATIONS BY THOMAS KELLEHER PE.
 THE CALCULATIONS CITE ASCE 7-93.THE
 1997 SBCCI INVOKED THE ASCE 7-95.
 PLEASE REVISE AS NECESSARY.
  
 PROVIDE A METAL FRAMING DETAIL FOR THE
 CANOPY THAT THE " TITAN ROOFING" PANELS
 WILL BE ATTACHED TO.
  
 THE FIRE PROTECTION SYSTEM FOR THE
 CANOPY IS A COLUMN DESIGN.HOW ARE THE
 HORIZONTAL STRUCTURAL MEMBERS PROTECTED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2002-05-14 Cont ID  
Sent By btrobaug Date 2002-05-20 Time 15:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-14 00:00:00REVISIONS SUBMITTED 5/7/02
 SHEET A801 DATED 5/2/02.SECTION
 6/A801WHAT IS THE 1 1/2" ACCENT PANEL
 MADE OF? HOW IS IT ATTACHED?
  
 WHERE IN THE STRUCTURAL DRAWINGS IS THE
 FRAMING DETAIL FOUND?
  
 SSK 19THE NEW 7'-4" HEIGHT DOES NOT
 COMPLY WITH THE 98" HEIGHT REQUIRED BY
 THE FACBC SEC 4.6.5.IF IT IS NOT ON
 THE SITE ACCESSIBLE ROUTE PROVIDE
 SIGNAGE AS APPLICABLE.
  
 SSK 26-28SPECIFY THE TYPE OF WELDS TO
 BE USED IN ACCORDANCE WITH GOOD
 ENGINEERING PRACTICE.IF THE
 CONNECTIONS ARE TO BE DELEGATED,
 PROVIDE THE APPROPRIATE INFORMATION ON
 THE DRAWING.SEE 61G15-31.009
  
 SSK 27 PLAN VIEW SHOWS THE FRONT OF THE
 CANOPY AS BEING STRAIGHT. THE
 ARCHITECTURAL PLANS DEPICT IT AS BEING
 CURVED.HOW IS THIS ACCOMPLISHED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-05-10 Cont ID  
Sent By hpiskura Date 2002-05-10 Time 10:29 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-10 00:00:00REVISIONS SUBMITTED 5/1/02
 SHEET A110 REVISIONS NUMBERED 1-8.THE
 PERMIT PLANS HAVE REV 1, SOME OF THE
 REVISONS ARE DATED TWO YEARS AGO, WHY
 ARE THEY JUST NOW BEING PROVIDED TO THE
 CITY FOR REVIEW?
  
 PROVIDE DETAILS FOR THE BUILT IN BAR
 SHOWN INCLUDING HC ACCESIBILITY
 REQUIREMENTS.
  
 THE PLANS HAVE REFERENCE SECTIONS TO
 A802.THE PERMIT PLANS DO NOT SHOW
 SECTION DETAILS NUMBERED THAT HIGH,
 THEYSTOP AT DETAIL 6, THESE PLANS SHOW
 17.
  
 SHEET A111.PROVIDE A CONSTRUCTION
 DETAIL FOR THE SUSPENDED CEILING.
 REVISIONS SHOWN 1-6, PERMIT PLANS 0.
  
 SHEET A120 REVISIONS 1-6, PERMIT PLAN 0.
 THE HANDRAILS FOR THE STAIRS FROM THE
 POOL DECK TO THE CLUBHOUSE DO NOT
 COMPLY WITH THE 30" REACH RANGE OF SBC
 1007.5.7.THE STAIRS AT THE FOUNTAIN
 AREA REQUIRE HANDRAILS ON BOTH SIDES
 AND THE RANGE OF REACH REQUIREMENTS OF
 SBC 1007.5.2ANDSBC 1007.5.7.
  
 SHEET A201 REV 1-8, PERMIT SET 1-4.
 PROVIDE STRUCTURAL DETAILS FOR THE
 CANOPY.THIS WAS REQUESTED ON MY
 CHECKLIST DATED 4/18/02 DENYING THOSE
 REVISIONS.
  
 WHAT PERMITTED PLAN DID THE THRESHOLD
 INSPECTOR USE TO INSPECT THIS
 STRUCTURAL WORK?
  
 SHEET A323 REVISIONS 1-3, PERMIT SET 1.
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 ADDED MASONRY VEHICLE BARRIER WALL
 INCLUDING CALCULATIONS DEMONSTRATING
 COMPLIANCE WITH THE LOADS PRESCRIBED IN
 SBC 1608.2.3.
  
 SHEET A404 REVISIONS 1-4, PERMIT SET 0.
 PROVIDE A DETAIL FOR CONSTRUCTION OF
 THEADDED VAULT.
  
 SHEET A406 REVISIONS 1-5, PERMIT SET 0.
 PROVIDE DETAILS FOR THE GALVANIZED
 SHUTTER.WHAT IS IT FOR?THE 4" HIGH
 CURBS AT THE PATIO SLIDING DOORS DO NOT
 COMPLY WITH THE FAIR HOUSING ACT.SEE
 PART 2, CHAPTER 4, PAGE 4.11 OF THE FHA
 DESIGN MANUAL.
  
 SHEET A421 REVISIONS 1-3, PERMIT SET 0.
 PROVIDE A DETAIL OF WHAT THE ADDED
 WALKWAY WILL BE MADE OF.
  
 SHEET A425 REVISIONS 1-3, PERMIT SET 0.
 SECTION DETAILS REFERENCED AS"XX/804"
 ARE ABSENT FROM THE PERMIT PLANS.
  
 SHEET E1.06, PROVIDE INFORMATION FOR THE
 METHOD OF OPENING PROTECTIVE FOR THE
 ADDED EXHAUST FAN.SEE SBC TABLE 600.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-03-26 Cont ID  
Sent By btrobaug Date 2002-04-18 Time 11:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-26 00:00:00REVISIONS SUBMITTED 2/28/02 HAVING
 VARIOUS DATES ON THE PLANS AND REVISION
 DELTAS 1 THROUGH 7.ARCH. PAGES
  
 SHEET A 101. PROVIDE STRUCTURAL DETAILS
 FOR THE ADDED LOUVERS PENETRATING THE
 EXTERIOR WALLS.SBC 104.2
  
 SHEET A 202. PROVIDE STRUCTURAL DETAILS
 FOR THE REVISED ENTRY.
  
 SHEET A 206.PROVIDE STRUCTURAL DETAILS
 FOR THE ADDED MECHANICAL EQUIPMENT
 ADDRESSING THE CONCENTRATED LOADINGS
 AND NEW PENETRATION/OPENINGS.
  
 SHEET A 303.STRUCTURAL INFORMATION FOR
 THE ADDED COOLING TOWER ENCLOSURE, AND
 THE CURB SHOWN IN SECTION 6/A303.
  
 A 310 PROVIDE STRUCTURAL DETAILS FOR THE
 SUSPENDED CEILING FRAMING INCLUDING
 CONNECTION TO THE SLAB ABOVE.
  
 A 320.STRUCTURAL DETAILS FOR THE NEW
 ARCH FRAMING.
  
 A 323 AND A 425.PROVIDE STRUCTURAL
 DETAILS FOR THE ADDED CANOPY.ALSO IT
 DOES NOT APPEAR TO COMPLY WITH SBC
 3204.3.
 REVISE AS NECESSARY.
  
 SHEET A 406 AND SEVERAL SUBSEQUENT PAGES
 INDICATE A 4" HIGH CURB AT THE PATIO
 SGD.THIS DOES NOT COMPLY WITH THE
 FAIR HOUSING MANUAL GUIDELINES PAGE
 4.11PLEASE REVISE AS NECESSARY.
  
 SHEET ADD 1.PROVIDE THE FIRE DESIGN
 NUMBERS FOR THE PRIMARY AIRSHAFT WALLS.
 SEE SBC 701.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status A Date 2001-03-20 Cont ID  
Sent By hpiskura Date 2001-03-20 Time 14:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-20 00:00:00THE FIRE RATED WINDOWS SHOWN ON THE
 NORTH ELEVATIION ARE REQUIRED TO BE A
 TESTED ASSEMBLY COMPLYING WITH NFPA 80

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-09-13 Cont ID  
Sent By hpiskura Date 2000-09-13 Time 14:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO SEE ARCH LETTER DATED 8/23/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-09 Cont ID  
Sent By hpiskura Date 2000-08-09 Time 12:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER WITH APPLCATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-04-24 Cont ID  
Sent By lmartine Date 2000-04-24 Time 11:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00FOUNDATION PERMIT ONLY,2ND REVIEW
 1]INSPECTION LETTER FROM MIGNOGNA IS OK
 PROVIDE SIGNED AND SEALED COPY.
 2]SUBMIT A CERTIFIED SOIL ANALYSIS
 REPORT-FOUNDATION REPORT.
 3]THRESHOLD INSPECTOR MUST BE SIGNED UP
 AND APPROVED BEFORE PERMIT CAN BE
 ISSUED.
 4]SURVEYS ARE NOT SIGNED AND SEALED.
 5]SUBMIT COPYS OF ALL RIGHT OF WAY
 PERMITS AND RELEASES REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-10 Cont ID  
Sent By lmartine Date 2000-03-10 Time 11:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:001]FOUNDATION PERMIT ONLY!
 SUBMIT THRESHOLD INSPECTION PLAN SIGNED
 AND SEALED BY A REGISTERED STRUCTUAL
 ENGINEER
 2]SUBMIT FOUNDATION INSPECTION REPORT
 3]THRESHOLD INSPECTOR IS REQUIRED,PLEASE
 CONTACT ASS. BUILDING OFFICIAL DON NEELY
 AT EXT.#8333 FOR APPROVED LIST
 4]SUBMIT SIGNED AND SEALED SURVEYS
 5]RIGHT OF WAY PERMITS AND RELEASES WILL
 BE REQUIRED,CONTACT ENGINEERING DEPART.
 AT 659-8040

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 17:37 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 17:27 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2002-07-31 Cont ID  
Sent By ndenmark Date 2002-08-05 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2002-07-31 Time 18:21 Sent To  
Notes
2002-07-31 00:00:00***** REV FOR 6 AND 7 ON E 1.14 ONLY.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2002-07-05 Cont ID  
Sent By btrobaug Date 2002-07-05 Time 15:55 Rev Time 0.00
Received By btrobaug Date 2002-07-05 Time 15:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2002-07-01 Cont ID  
Sent By dpalmer Date 2002-07-01 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2002-07-01 Time 14:41 Sent To  
Notes
2002-07-01 00:00:00LAYOUT FOR ELEC RM/FIRE PUMP RM. RISER
 OK.

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2002-07-01 Cont ID  
Sent By dpalmer Date 2002-07-01 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2002-07-01 Time 14:39 Sent To  
Notes
2002-07-01 00:00:00ELEC LT SPEC BKS.

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2002-06-17 Cont ID  
Sent By dpalmer Date 2002-06-17 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2002-06-17 Time 08:26 Sent To  
Notes
2002-06-17 00:00:00************ NOTE ************
  
 PLEASE NOTE AS PER FEILD INSPECTION AND
 CONVERSATION WITH GC.
 PLANS/ RISER DIAGRAM IS TO BE REVISED
 TO CORRELATE WITH JOBSITE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2002-05-30 Cont ID  
Sent By dpalmer Date 2002-05-30 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2002-05-30 Time 06:21 Sent To  
Notes
2002-05-30 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY REVISIONS SHOWN
 FOR SOME PANELS ON RISER DIAGRAM AND
 NOTES REF "SEE PANEL SCHEDULES". PLEASE
 NOTE NO PANEL SCHEDULES WERE SUBMITTED
 FOR THOSE MENTIONED. NOTE REF CHANGE TO
 FEEDERS TO APTS ALSO.?METER CENTERS ALSO
  
 2)NOTE: PLEASE NOTE THAT SINCE THIS
 REV WAS SUBMITTED, THE RISER DIAGRAM
 HAS CHANGED DUE TO FIELD EVALUATION OF
 MAIN DISC`S AND/OR GROUPING OF MAINS.
 PLEASE REVISE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2002-05-21 Cont ID  
Sent By dpalmer Date 2002-05-21 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2002-05-21 Time 08:15 Sent To  
Notes
2002-05-21 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE GROUPING OF MAINS
 PER 230-72 NOT MET.
  
 2)NOTE: PLEASE NOTE SHUNT TRIP(S)
 SHOWN AS A MAIN DISCONNECT FOR 6E.
 PLEASE SEE 230-76 AND 230-79
  
 3)NOTE: PLEASE NOTE ELECTRICAL ROOM(S)
 LAYOUTS DO NOT CORRELATE WITH HOW IT
 IS ACTUALLY INSATLLED IN THE FIELD.
  
 4)NOTE: PLEASE NOTE MAIN 1&2 "W" ON
 FIRST FLOOR AND NOT GROUPED WITH OTHERS
 ALSO DOES NOT MEET THE REQ`MENTS FOR
 FIRE DEPT.
  
 5)NOTE: PLEASE SUBMIT OCP FOR FIRE PUMPS
 AND ASSC EQUIPMENT. PLEASE SEE 695-4/
 695-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-05-20 Cont ID  
Sent By btrobaug Date 2002-04-18 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2002-04-18 Time 10:27 Sent To B
Notes
2002-04-18 00:00:00*******************UNSAT!***************
  
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 SEE SHEET"F1".
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-03-27 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2002-03-27 Time 15:10 Sent To FIRE
Notes
2002-03-27 00:00:00PLANS BEING RESTAMPED. OLD REV SHEETS
 FROM LAST YEAR.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2001-12-27 Cont ID  
Sent By dpalmer Date 2001-12-27 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2001-12-27 Time 11:57 Sent To  
Notes
2001-12-27 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT THERE WERE MANY
 SHEETS FOR FIXTURES THAT ARE CLEAR AND
 DO NOT SHOW ANY LISTINGS FOR FIXTURES
 PLEASE SEE THE FOLLOWING AS A LIST
 OF FIXTURES NOTED:
  
  
 STERNBERGTYPE C
 BEGHELLITYPE XG
 THOMAS RES TYPE AB
 THOMAS RES TYPE AE
 ACCOLADETYPE PORCH
 BOYD TYPE P1
 BALDINGERTYPE WI
 BOYD TYPE P3
 ILLUMNATION LTG TYPE P4
 SCHMITZ TYPE P5
 MINKA AIRE TYPE FAN
 RESOLTE MANIFESTO TYPE W4
 LUMEC "STREET LUMINAIRE"
 AMERON "STREET POLE" VES-4-3 T6MOD
  
  
 PLEASE SUBMIT THE ABOVE CLARIFICATION
 FOR ALL OF THE ABOVE FIXTURS BEING
 USED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-11-14 Cont ID  
Sent By dpalmer Date 2001-11-14 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2001-11-14 Time 08:12 Sent To  
Notes
2001-11-14 00:00:00REV TO E2.06 ROOM LAYOUT

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-01-04 Cont ID  
Sent By dpalmer Date 2001-01-04 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2001-01-04 Time 16:57 Sent To  
Notes
2001-01-08 00:00:00REVISION FOR FIRST LEVEL. POWER

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-15 Cont ID  
Sent By jleahy Date 2000-08-15 Time 10:29 Rev Time 0.00
Received By jleahy Date 2000-08-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-08-29 Cont ID  
Sent By jleahy Date 2000-04-11 Time 10:46 Rev Time 2.30
Received By jleahy Date 2000-04-11 Time 10:45 Sent To  
Notes
2001-01-08 00:00:00THIS PERMIT IS FOR A LIMITED AMOUNT OF
 CONDUITS TO BE INSTALLED UNDERGROUND!!!!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-20 Cont ID  
Sent By jleahy Date 2000-01-20 Time 13:28 Rev Time 0.00
Received By jleahy Date 2000-08-29 Time 07:53 Sent To  
Notes
2001-01-08 00:00:001- NO ELECTRIC SHOWN
 2- NO ELECTRIC SHOWN
 3- NO ELECTRIC SHOWN
 4- NO ELECTRIC SHOWN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 5- NO ELECTRIC SHOWN!!!!!!!!!!!!!!!!!!!!

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2002-07-15 Cont ID  
Sent By mamini Date 2002-07-15 Time 15:22 Rev Time 1.00
Received By mamini Date 2002-07-15 Time 15:21 Sent To  
Notes
2002-07-15 00:00:00PASSED:
 1. REVIEWED FOR SIGN LAYOUT IN PARKING
 GARAGE LEVELS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2002-01-11 Cont ID  
Sent By mamini Date 2002-01-11 Time 16:02 Rev Time 1.00
Received By mamini Date 2002-01-11 Time 16:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2001-11-05 Cont ID  
Sent By mamini Date 2001-11-05 Time 9:08 Rev Time 1.00
Received By mamini Date 2001-11-05 Time 9:07 Sent To  
Notes
2001-11-02 00:00:00PASSED:
 1. ADA RAMPS MUST HAVE TACTILE, SLIP
 RESISTANT SURFACE .
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2001-11-02 Cont ID  
Sent By mamini Date 2001-10-23 Time 09:35 Rev Time 1.00
Received By mamini Date 2001-10-23 Time 09:34 Sent To  
Notes
2001-10-23 00:00:00FAILED:
 1. ADA RAMPS MUST HAVE TACTILE, SLIP
 RESISTANT SURFACE.
 2. BASE AND SUBGRADE MUST BE COMPACTED
 TO 98% OF AASHTO T-180 PRIMED AND HAVING
 THE THICKNESS AS ORIGINAL PLANS.
 3. WORK WITHIN PUBLIC R.O.W WILL REQUIRE
 A SEPARATE PERMIT FROM CITY ENGINEER'S
 OFFICE / FDOT.
 4. IS THE EXISTING INLET AT CORNER OF
 NARCISSUS AND EVERNIA RELOCATED/RECONS-
 TRUCTED ??
 5. PROPOSED REVISION WOULD REDUCE THE
 WESTBOUND TRAVEL LANE ON EVERNIA ST.
 TO 8', PLEASE VERIFY.
 6. PLEASE REFER TO THE ORIGINAL APPROVED
 PLAN FOR OVERLAY REQUERMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-12-05 Cont ID  
Sent By mgonzale Date 2000-12-05 Time 15:21 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 SHOP DRAWINGS FOR WATER AND SEWER

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-06-13 Cont ID  
Sent By dlauderm Date 2000-06-13 Time 15:44 Rev Time 1.00
Received By dlauderm Date 2000-06-13 Time 15:40 Sent To  
Notes
2001-01-08 00:00:00PLANS APPROVED THRU OUR UTILITIES
 DEPARTMENT OFFICE AT 45TH ST.
 CONTRACTOR NEEDS TO SUBMIT THOSE PLANS
 WITH THE UTILITY DEPARTMENT APPROVAL
 STAMP ON IT TO B&Z.
 PER COMMISSION APPROVAL ON 6-12-00
 THE FOOTER EASEMENTS ARE APPROVED.
 THE FOOTERS IN THE CITY RIGHTS-OF-WAY
 MUST BE 5'DEEP.

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2002-08-20 Cont ID  
Sent By mcarsill Date 2002-08-20 Time 16:29 Rev Time 0.00
Received By mcarsill Date 2002-08-20 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status F Date 2002-07-18 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 17:37 Rev Time 0.00
Received By mcarsill Date 2002-07-18 Time 12:09 Sent To  
Notes
2002-07-18 00:00:001) PLEASE SUBMIT A COMPREHENSIVE
 NARRATIVE FOR THE SMOKE CONTROL SYSTEM
 PLANNED FOR USE. THE ORIGINAL DESIGN
 INDICATED PRESSURIZING TWO FLOORS ABOVE
 AND TWO FLOORS BELOW WITH THE FLOOR
 OF INCIDENT BETWEEN THESE. DURING
 TESTING WITH CITY MECHANICAL DIVISION
 PERSONNEL, PROBLEMS WERE IDENTIFIED
 AND THUS THE ORGINAL DESIGN HAS SINCE
 BEEN CHANGES. THE NARRATIVE IS
 REQUIRED FROM THE ENGINEER OF RECORD
 TO PROVIDE SUPPORTIVE DOCUMENTATION
 FOR THE DESIGN CHANGE.
  
 2) IS IS UNDERSTOOD BY THIS OFFICE THAT
 A TEMPROARY SHROUD HAS BEEN INSTALLED
 ON THE FAN. THIS TEMPORARY DEVICE IS
 TO BE REMOVED AS IT NOT PART OF THE
 ORIGINAL LISTING FOR THE FAN DEVICE.
  
 3) THE ACCEPTANCE TESTING CRITERIA
 NOTED ON THE PLANS ARE TO BE FOLLOWED.
  
 4) THE OWNER, ENGINEER, AND CONTRACTOR
 MUST ACCEPT THE LIABILTIY FOR
 THE PRESCRIBED SYSTEM DURING TESTING
 SINCE THE DESIGN INTENT HAS CHANGED
 SIGNIFICANTLY. THE ENGINEER OF RECORD
 SHALL BE CONSULTED DURING THE ENTIRE
 TESTING PROCESS.
  
 5) THE FUNCTIONAL APPROVAL BY CITY
 OFFICIALS WILL ONLY OCCUR AFTER
 MUTUALLY AGREED UPON TESTING METHODS
 AND RESULTS ARE DISCUSSSED.
  
 6) ALL APPLICABLE BUILDING, FIRE , AND
 MECHANICAL CODES ARE TO BE MET FOR
 THE SYSTEM WITHIN THE BUILDING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2002-06-20 Cont ID  
Sent By mcarsill Date 2002-06-20 Time 10:17 Rev Time 0.00
Received By mcarsill Date 2002-06-20 Time 10:17 Sent To  
Notes
2002-06-20 00:00:00THIS REVIEW WAS PERFORMED ON THE FLAME
 SPREAD SPECIFICATION BOOK THAT WAS
 SUBMITTED TO CONSTRUCTION SERVICES
 DEPARTMENT ON JUNE 18, 2002.
  
 1) IT APPEARS THAT THE WALLCOVERINGS
 LOCATED WITHIN THE BOOK APPEAR TO MEET
 THE REQUIREMENTS FOR CLASS A MATERIALS
 PER THE NATIONAL FIRE PROTECTION
 ASSOCIATION. THESE MATERIALS WILL BE
 APPROVED BY THE BUREAU OF FIRE
 PREVENTION. PLEASE HAVE COPIES AVAILABLE
 REGARDING THE FLAMESPREAD RATINGS
 OF THESE MATERIALS SHOULD YOU BE ASKED
 TO PROVIDE DOCUMENTATION.
  
 2) THE ITEMS SUBMITTED WITHIN THE BOOK
 DETAILING THE FURNISHINGS HAVE BEEN
 REVIEWED. SINCE SOME FURNISHINGS ARE
 INCIDENTAL TO VARIOUS ROOM USES, THIS
 OFFICE WILL ACCEPT THE DOCUMENTATION
 AS PRESENTED. TYPICALLY, FLAME SPREAD
 RATINGS FOR FURNISHINGS ARE NOT
 SUBJECTED TO SAME REVIEW AS THE
 INTERIOR FINISH AS THE WALLS, CEILINGS
 OR COLUMNS UNLESS THE AUTHORITY HAVING
 JURISDICTIONS MANDATES IT. IT WAS NOTED
 THAT SOME TESTING HAD OCCURED TO THE
 MATERIAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2002-05-23 Cont ID  
Sent By mcarsill Date 2002-05-23 Time 11:12 Rev Time 0.00
Received By mcarsill Date 2002-05-23 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2002-04-12 Cont ID  
Sent By mcarsill Date 2002-04-12 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2002-04-12 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status N Date 2002-01-10 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2002-01-10 Time 16:12 Sent To  
Notes
2002-01-10 00:00:001) STEPS NEAR POOL ARE TO BE SLIP
 RESISTANT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 12:27 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 12:27 Sent To  
Notes
2001-11-21 00:00:00THIS PLAN REVIEW STOP IS FOR THE
 PRODUCT APPROVAL DATA THAT WAS SUBMITTED
 FOR THE HOOD EXHAUST DUCT SCRUBBER UNIT
 PROPOSED FOR ONE OF THE RETAIL SPACES.
 PLEASE BE ADVISED THAT IF THIS UNIT IS
 ACCEPTABLE TO CITY OFFICIALS, A SEPARATE
 FIRE SUPPRESSION SYSTEM WILL BE REQUIRED
 PER NFPA 96. ALSO NO DOWNGRADES OF THE
 EXHAUST DUCT BEYOND THE SCRUBBER UNIT
 WILL BE PERMITTED. ALSO APPROVAL IS
 DIFFICULT TO GIVE AT THIS TIME BECAUSE
 PLANS HAVE NOT BEEN RECEIVED OR REVIEWED
 FOR THE TENANT SPACE HOOD,DUCT,AND
 EXTINGUISHING SYSTEM WHICH WOULD WORK
 IN CONJUNCTION WITH THE PROPSED
 SCRUBBER UNIT. THE EXHAUST DUCT
 TERMINATIONS MUST COMPLY WITH THE
 REQUIREMENTS OF NFPA 96 AS WELL AS THE
 REST OF THE INSTALLATION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 14:53 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2000-12-28 Cont ID  
Sent By mcarsill Date 2000-12-28 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2000-12-28 Time 10:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-08-22 Cont ID  
Sent By mcarsill Date 2000-08-22 Time 14:29 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00ON AUGUST 22, 2000, WRITER AND CHIEF
 MECHANICAL INSPECTOR NANCY DENMARK MET
 WITH STRAND AND SUFFOLK CONSTRUCTION
 REPRESENATIVES. THE FOLLOWING ITEMS WERE
 DISCUSSED:
 1) TESTING PROCEDURES ARE TO BE
 SUBMITTED FOR THE SMOKE CONTROL SYSTEM.
 2) INFORMATION IS TO BE SUBMITTED ON
 WHAT THE SMOKE CONTROL PANEL IS TO
 LOOK LIKE AND THE TYPE CONTROLS WILL
 BE ON THE PANEL.
 3) MINIMUM TESTING EQUIPMENT FOR
 SMOKE CONTROL SYSTEM IS TO BE NOTED
 ON PLANS. A LETTER IS TO BE SUBMITTED
 ON AUGUST 23, 2000, REGARDING THESE
 ISSUES. APPROVED PROVISO

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 13:16 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) MORE INFORMATION REQUIRED FOR THE
 FIREFIGHTERS SMOKE CONTROL STATION. THE
 PLANS DO NOT INDICATE WHAT WILL BE
 FEATURED ON THE PANEL. PLEASE REFER TO
 NFPA 92A, SECTION 3-4.3.4 REGARDING
 MINIMUM REQUIREMENTS.
 2) NO TESTING EQUIPMENT NOTED ON
 DRAWINGS. PLEASE SEE NFPA 92A, SECTION
 4-3.2. THIS EQUIPMENT SHALL BE NOTED
 ON THE PLANS TO ASSIST IN TESTING THESE
 LIFE SAFETY SYSTEMS.
 3) TYPE AND DURATION OF SMOKE BOMBS
 TO BE USED NOT IDENTIFIED. NO CRITERIA
 NOTED ON WHAT IS EXPECTED DURING TESTING
 WITH SMOKE BOMBS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-04-19 Cont ID  
Sent By rturnque Date 2000-04-19 Time 10:46 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001. PROVIDE DOOR SCHEDULE
 2. FIRE ALARM SYSTEM SHALL BE CLASS "A"
 OR ADDRESSABLE.
 3. PROVIDE ADDITIONAL STANDPIPE.
 4. ALL EXIT DOORS SHALL SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 5. PROVIDE 2 1/2"TO 1 1/2" REDUCERS ON
 ALL STANDPIPES.
 6.ALL APT. DOORS SHALL BE 20 MIN., SELF
 CLOSING, FIRE DOORS.
 7. ALL INTERIOR STAIRWELL DOORS SHALL
 BE CLASS B RATED, SELF CLOSING, FIRE
 DOORS.
 8. PROVIDE FIRE SPRINKLER DRAWINGS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By rturnque Date 2000-01-07 Time 10:12 Rev Time 0.50
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2002-08-05 Cont ID  
Sent By ndenmark Date 2002-08-05 Time 12:59 Rev Time 0.33
Received By ndenmark Date 2002-08-05 Time 12:59 Sent To E
Notes
2002-08-05 00:00:00ADDITION OF MOTORIZED DAMPER TO 2
 SMALLER STAIR WELLS FOR STAIR
 PRESSURIZATION.

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2002-07-29 Cont ID  
Sent By ndenmark Date 2002-07-29 Time 07:50 Rev Time 0.50
Received By ndenmark Date 2002-07-29 Time 07:50 Sent To  
Notes
2002-07-29 00:00:00NARRATIVE FOR CHANGES TO BUILDING
 SEQUENCE AND PLANS REFLECTING CHANGES

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2002-07-18 Cont ID  
Sent By ndenmark Date 2002-07-18 Time 12:28 Rev Time 0.50
Received By ndenmark Date 2002-07-18 Time 12:28 Sent To  
Notes
2002-07-18 00:00:00DENIED AS SUBMITTED
  
 SEE FIRE PLAN REVIEW FOR FULL DETAILS
 TEST AND BALANCE REPORT TO REFLECT CFM
 ON ENGINEERS DRAWING.
 PROVIDE INFORMATION AS REQUESTED BY FIRE

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2002-03-06 Cont ID  
Sent By pkrauss Date 2002-03-06 Time 15:25 Rev Time 5.00
Received By pkrauss Date 2002-03-05 Time 16:05 Sent To  
Notes
2002-03-06 00:00:00 
 MECHANICAL PERMIT 00120524
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR DRYERS BEING INSTALLED IN
 UNITS THAT THE IN-LINE FAN HAS BEEN
 DELETED.EXHASUT DUCT EXCEEDS 25 FT
 MAXIMUM AS PER 1997 SMC 509.3.
  
 REVISIONS APPROVED WITH THE EXCEPTION
 OF"PROPOSED KITCHEN HOOD".TERMINATION
 FOR GREASE DUCT SHALL COMPLY WITH NFPA
 96 AND 1997 SMC CHAPTER 5.TERMINATION
 OF EXHAUST SHALL BE LOCATED 10 FT FROM
 ANY ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW, DOOR OR
 AIR INTAKE.ADDITIONAL PLANS & PERMITS
 REQUIRED FOR HOOD (GREASE DUCT & MAKEUP
 AIR), FIRE SUPRESSION, AND WALKIN
 COOLERS/FREEZERS.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA
 WITH PLANS & PERMIT APPLICATION.PLEASE
 NOTE, THERE SHALL BE NO DOWNGRADING
 OTHER PARTS OF THE EXHAUST SYSTEM DUE
 TO THE INSTALLATION OF THE "ECOLO AIR"
 SYSTEM AS PER NFPA 96 6-3.FIRE
 SUPRESSION SYSTEM REQUIRED AS PER NFPA
 96 6-3.1.
  
 PLEASE NOTE 1 SET OF REVISIONS SUBMITTED
 MECHANICAL SHEETS M104, M106, & M108,
 ARE DIFFERENT.REVISION 4 IS DATED JUL
 20, 2001 AND PLAN SHEETS DIFFER.THE
 OTHER SET OF PLANS SUBMITTED THE
 AFOREMENTIONED PLAN SHEETS ARE DATED
 JUL 20, 2001 AND ALSO INDICATE LATEST
 REVISON TO BE #4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status N Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 07:54 Rev Time 0.10
Received By pkrauss Date 2002-01-05 Time 07:50 Sent To  
Notes
2002-01-05 00:00:00MECH PERMIT 00120524
 NO MECHANICAL REVISIOS.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2001-07-16 Cont ID  
Sent By pkrauss Date 2001-07-16 Time 13:18 Rev Time 0.40
Received By pkrauss Date 2001-07-16 Time 13:16 Sent To  
Notes
2001-07-16 00:00:00SUBMITTAL DATA FOR HEAT PUMPS, BATHROOM
 EXHAUST FANS AND POOL EXHAUST FAN.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 09:06 Rev Time 0.30
Received By pkrauss Date 2001-05-08 Time 09:06 Sent To  
Notes
2001-05-08 00:00:00REVIEW DONE UNDER MECH PERMIT 00120524
 SUBMITTAL OF FAN MOTOR FOR COOLING TWR.
 CHANGED FROM 15 HP TO 25 HP.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2001-05-07 Cont ID  
Sent By pkrauss Date 2001-05-07 Time 14:44 Rev Time 0.30
Received By pkrauss Date 2001-05-07 Time 14:44 Sent To  
Notes
2001-05-07 00:00:00*******************DENIED***************
  
 IN RESPONSE TO YOUR LETTER DATED 4/26/01
 (A/C CLOSET), THIS WILL BE AN ACCESS
 CODE ISSUE.1997 SMC 304.2, SUFFICIENT
 CLEARANCE FOR MAINTENANCE/REPLACEMENT
 AS WELL AS ACCESSIBILITY TO VENT
 CONNECTIONS.
  
  
 IF YOU HAVE ANY QUESTION PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 09:06 Rev Time 3.00
Received By pkrauss Date 2001-04-06 Time 09:06 Sent To  
Notes
2001-04-06 00:00:00APPROVED UNDER MECH PERMIT #00120524.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-01-09 Cont ID  
Sent By ndenmark Date 2001-01-09 Time 09:37 Rev Time 0.50
Received By ndenmark Date 2001-01-09 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2000-08-25 Cont ID  
Sent By ndenmark Date 2000-08-22 Time 14:18 Rev Time 2.00
Received By ndenmark Date 2000-08-22 Time 14:18 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 1.PROVIDE INFORMATION ON TEST ACCEPTANCE
 PROCEDURES FOR SMOKE CONTROL SYSTEMS
 2.EXHAUST DUCT SYSTEM FOR KITCHEN GREASE
 HOOD HAS NOT BEEN APPROVED AND SHALL BE
 APPROVED PRIOR TO ANY SYSTEM INSTALLATIO
 DUE TO ACCESS CONSIDERATIONS OF SHAFT AN
 TERMINATION OF EXHAUST FAN.
 3. NOTE: FIRE FLOOR SHALL NOT BE PRESSUR
 IZED PER REDLINE ON MECH DRAWING AND
 ELECTRIC SEQUENCE OF OPERATION
  
 REFER TO PERMIT NUMBER 00041269 FOR
 ADDITIONAL PLAN REVIEW COMMENTS FOR THIS
 ADDRESS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2000-08-25 Cont ID  
Sent By ndenmark Date 2000-05-01 Time 08:19 Rev Time 0.33
Received By ndenmark Date 2000-05-01 Time 08:19 Sent To  
Notes
2001-01-08 00:00:00MECHANICAL APPROVED FOR FOUNDATION ONLY
 NO MECHANICAL WORK TO BE DONE WITH THIS
 PERMIT PRIOR COMMENTS FOR BUILDING STILL
 APPLY TO BUILDING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-04-20 Cont ID  
Sent By cthirben Date 2000-04-20 Time 09:59 Rev Time 1.00
Received By cthirben Date 2000-04-20 Time 09:54 Sent To  
Notes
2001-01-08 00:00:00****************NOTES*******************
 INSUFFICIENT MECHANICAL INFOMATION TO
 REVIEW.AS PER REVIEW DONE ON 01.05.00
 BY NANCY.
 LETTER ATTACHED TO PLANS FROM PROJECT
 ARCHITECT ON THE MECH. COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-05 Cont ID  
Sent By ndenmark Date 2000-01-05 Time 13:09 Rev Time 1.00
Received By ndenmark Date 2000-01-05 Time 13:08 Sent To  
Notes
2001-01-08 00:00:00***********NOT ENOUGH INFORMATION******
  
 INSUFFICIENT MECHANICAL INFORMATION TO
 REVIEW:
 PROVIDE DETAILS AT TIME OF SUBMITION FOR
 BUILDING REVIEW. INCLUDE:
 EQUIPMENT TYPES AND LOCATION
 REFRIGERANT TYPE AND QUANTITY PER 1997
 SMC CHAPTER 11
 DUCT LAYOUT, SIZES AND SPECIFICATIONS
 FAN SHUT DOWN PER 1997 SMC 406,NFPA90A,
 AND 1997 SBC 412.2
 SMOKE CONTROL PER 1997 SBC 412.5
 STAIRWELL PRESSURIZATION PER 1997 SMC
 408 AND NFPA 92A
 INCLUDE SEQUENCE OF OPERATION FOR SMOKE
 CONTROL AND FAN SHUT DOWN SYSTEMS
 SHAFT ENCLOSURE DETAILS FOR EXHAUST DUCT
 FOR HOOD AND MAKE UP AIR LOCATION FOR
 HOOD
 OUTSIDE AIR CALCULATIONS AND AIR BALANCE
 SCHEDULE PER ASHRAE 62-89 AND SMC 501.2
  
  
 NOTE:SMC=STANDARD MECHANICAL CODE
 SBC=STANDARD BUILDING CODE
 NFPA=NATIONAL FIRE PROTECTION ASSOCIA-
 TION

Review Stop P PLUMBING
Rev No 13 Status P Date 2002-08-10 Cont ID  
Sent By kstevens Date 2002-08-10 Time 15:09 Rev Time 0.00
Received By kstevens Date 2002-08-10 Time 15:09 Sent To  
Notes
2002-08-10 00:00:00REVISION OK W/PROVISO - UNDERCOUNTER
 W/HEATER - SHALL BE READILY ACCESSIBLE.

Review Stop P PLUMBING
Rev No 12 Status P Date 2002-07-03 Cont ID  
Sent By pschmitz Date 2002-07-03 Time 10:13 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-03 00:00:00PLUMBING PLAN REVIEW, FOUNTAIN,PES.

Review Stop P PLUMBING
Rev No 11 Status F Date 2002-06-03 Cont ID  
Sent By kstevens Date 2002-06-03 Time 10:31 Rev Time 0.00
Received By kstevens Date 2002-06-03 Time 10:31 Sent To  
Notes
2002-06-03 00:00:00DENIED
 REFERENCE: SPC-94- FACBC-97
  
 1) SHT A110 SHOW DETAIL FOR WATER HEATER
 SHOW HOW IT WILL BE READILY ACCESSIBLE.
 SHOW PIPING FOR T/P RELIEF LINE AND FOR
 PAN DRAIN.
 2) SHT A110 DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY HDCP FIXT-
 URE. SEC 4.22.2
 3) SHT P126 PLEASE SUBMIT FACTORY INFO.
 FOR MISTING MACHINE. SHOW LISTING FOR
 PRODUCT APPROVAL.
 4) SK-P-1/SK-P-2 RISER DIAGRAMS, HUB
 DRAINS NOT APPROVED. FLOOR SINK REQUIRED
 FOR ALL INDIRECT WASTE. SEC 804.5
 5) SHT A110 PLEASE PROVIDE CHANGE IN
 SANT RISER DIAGRAM FOR NEW SINK IN CLUB
 ROOM
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 10 Status F Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-13 Time 13:43 Rev Time 0.00
Received By kstevens Date 2002-05-13 Time 13:43 Sent To  
Notes
2002-05-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PLEASE NOTE THAT ALL PLANS DRAWN BY
 AN ENGINEER SHALL BE SIGNED, SEALED, AND
 DATED BY THE ENGINEER OF RECORD.
 61G15-23.002
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 9 Status P Date 2002-03-18 Cont ID  
Sent By kstevens Date 2002-03-18 Time 14:44 Rev Time 1.50
Received By kstevens Date 2002-03-18 Time 14:44 Sent To  
Notes
2002-03-18 00:00:00REVISION OK - IRRIGATION FOR PLANTERS
 WITH BACKFLOW IN POOL EQUIP. ROOM.

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-01-14 Cont ID  
Sent By kstevens Date 2002-01-14 Time 11:42 Rev Time 0.50
Received By kstevens Date 2002-01-14 Time 11:42 Sent To  
Notes
2002-01-14 00:00:00SUBMITTAL FOR PUMP STATION APPROVED.

Review Stop P PLUMBING
Rev No 7 Status P Date 2001-10-01 Cont ID  
Sent By kstevens Date 2001-10-01 Time 17:26 Rev Time 0.50
Received By kstevens Date 2001-10-01 Time 17:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-03-27 Cont ID  
Sent By jleech Date 2001-03-27 Time 17:35 Rev Time 0.50
Received By jleech Date 2001-03-27 Time 17:35 Sent To  
Notes
2001-03-27 00:00:00PRODUCT APPROVAL BALL VALVES.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 15:58 Rev Time 0.75
Received By jleech Date 2001-01-02 Time 15:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-12-20 Cont ID  
Sent By jleech Date 2000-12-20 Time 07:27 Rev Time 1.00
Received By jleech Date 2000-12-20 Time 07:26 Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL MANUFACTURES CUT SHEETS

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-24 Time 11:25 Rev Time 6.00
Received By pschmitz Date 2000-08-24 Time 11:25 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 1)SHT.A-601-BACKING FOR GRAB BARS FOR
 THE TUB ALONG THE LONG WALL SHALL COMPLY
 W/THE FHA REQ.#6,FIG.4.THE PLANS SHOW 8"
 MAX.TO THE BOTTOM OF THE BACKING AND THE
 FHA REQ.IS 6".
  
 2)SHT.A-453-UNIT D9-THE WATER CLOSET
 INFRINGES ON THE CLEAR FLOOR SPACE IN
 THE M.B.TOILET ROOM.COMPLY W/FHA 24 CFR
 100.205(C)(3)(IV).
  
 3)SHTS.A-120,A204,A414 SHOW 1 TOILET
 ROOM IN THE POOL CLUBHOUSE AND SHT.A110
 SHOWS 2 TOILET ROOMS.PLEASE REVISE SO
 ALL APPLICABLE SHEETS CORRELATE.
  
 4)SHT.A-601-A MIN. OF 29"IS REQD.UNDER
 LAV.FROMM FINISH FLOOR TO BOTTOM OF
 APRON,NOT 27".COMPLU W/FACBC SEC.4.19.
  
 5)A DRINKING FOUNTAIN IS REQD.INSIDE THE
 CLUBHOUSE PER TABLE 407.DRINKING
 FOUNTAIN IS REQD.IN THE CLUBHOUSE PER
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BEND-
 ING OR STOOPING.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-30 Cont ID  
Sent By tlarge Date 2000-04-30 Time 13:20 Rev Time 1.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 PERMIT IS FOR FOUNDATION ONLY.
 PLANS SHALL BE APPROVED BY CITY OF WPB
 ENGINEERING DEPT.FOR STORM & WATER.
  
 PREVIOUS PLUMBING COMMENTS HAVE NOT BEEN
 ADDRESSED.NO PLUMBING SHALL BE INSTALLED
 UNDER THIS PERMIT.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-30 Cont ID  
Sent By tlarge Date 2000-01-29 Time 06:33 Rev Time 3.00
Received By tlarge Date 2000-01-31 Time 06:32 Sent To  
Notes
2001-01-08 00:00:00SHT.A001-APPLICABLE CODES-THE 1994 EDIT.
 OF THE STANDARD PLBG.CODE W/PALM BEACH
 COUNTY AMENDMENTS IS THE ADOPTED
 STANDARD.REVISE NOTE.
  
 THE MAXIMUM CAPACITY OF GREASE INTER-
 CEPTOR SHALL BE 1250 GALS.PER STATE OF
 FLA.HEALTH DEPT.REQS.CHAPT.64E-6.013(5).
  
 SIZE AND CAPACITY OF INTERCEPTORS SHALL
 BE APPROVED BY CITY OF WPB REGIONAL
 WASTEWATER TREATMENT PLANT.CONTACT
 RODNEY COMPO AT (561)835-7423.
  
 SUBMIT DETAIL OF OIL/SAND INTERCEPTOR.
 SPC1004.2.
  
 SHTS.P1.01,1.02,SHOWS 6" INLET TO OIL/
 SAND INTERCEPTOR AND 4" OUTLET.SPC 709.1
  
 SUBMIT ISOMETRIC DRAWINGS FOR ENTIRE
 SCOPE OF WORK TO BE DONE AT THIS TIME.
 SIZE ALL LINES AND INDICATE SLOPE OF
 PIPE.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SUBMIT ISOMETRIC FOR STORM DRAINAGE
 SYSTEM.SHOW SQUARE FOOT AREA DRAINED BY
 EACH ROOF DRAIN AND SUPPLY CALCULATIONS
 FOR SECONDARY DRAINAGE FOR ROOF.COMPLY
 W/SBC SEC.1517.6.4.1-1517.6.4.3.
 SPC 1108.1,1108.2.,APPENDIX "A",TABLE
 A101.2.INDICATE SLOPE OF PIPE.
  
 INDICATE WATER SOURCE FOR IRRIGATION
 SYSTEM.IF FROM A NON-POTABLE SOURCE A
 WATER USE PERMIT FROM SFWMD MAY BE REQD.
 PER F.S.373.219.
  
 NOTE:PLUMBING PLAN REVIEW IS FOR SHELL
 ONLY.DOES NOT INCLUDE REVIEW FOR LIVING
 UNITS,COMMON AREAS,OR REQS.FOR HANDICAP
 ACCESSIBILITY.
  
 THIS IS FOUNDATION ONLY PERMIT.NO
 PLUMBING WORK OF ANY NATURE IS PERMITTED
 3/8/00.TLARGE.

Review Stop Z ZONING
Rev No 4 Status F Date 2002-07-11 Cont ID  
Sent By sgraham Date 2002-07-11 Time 14:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-07-11 00:00:00SEPARATE PERMIT REQUIRED FOR LOGO, THE
 LOGO SHALL BE NO GREATER THAN 40 SQ.
 SEE ARTICLE IV, SEC 33-47(F)(3)

Review Stop Z ZONING
Rev No 3 Status N Date 2002-06-20 Cont ID  
Sent By lmartine Date 2002-06-20 Time 10:02 Rev Time 1.00
Received By lmartine Date 2002-06-20 Time 09:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2002-01-10 Cont ID  
Sent By rbrown Date 2002-01-10 Time 15:37 Rev Time 0.25
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-31 Cont ID  
Sent By gjoyce Date 2000-08-31 Time 09:01 Rev Time 0.25
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00WITH PROVISO