Plan Review Details - Permit 99121451
Plan Review Stops For Permit 99121451
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-16 Cont ID  
Sent By dpalmer Date 2001-04-16 Time 21:11 Rev Time 0.00
Received By dpalmer Date 2001-04-16 Time 21:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-22 Cont ID  
Sent By dpalmer Date 2000-01-22 Time 14:37 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 NOTES ATTACHED TO PLANS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-16 Cont ID  
Sent By jleech Date 2001-04-16 Time 19:41 Rev Time 0.50
Received By jleech Date 2001-04-16 Time 19:41 Sent To  
Notes
2001-04-16 00:00:00PROVISO REVISE PLAND BEFORE ROUGH
 A/C INSPECTION ALL DUCT SIZES REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-22 Cont ID  
Sent By jleech Date 2000-01-22 Time 08:39 Rev Time 0.50
Received By jleech Date 2000-01-22 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-16 Cont ID  
Sent By kstevens Date 2001-04-16 Time 18:11 Rev Time 0.33
Received By kstevens Date 2001-04-16 Time 18:22 Sent To  
Notes
2001-04-16 00:00:00PLUMBING PLAN REVIEW:
 PRIVSO:
 SUBMIT SANITARY RISER DIAGRAM THAT
 REFLECTS FLOOR PLAN BEFORE INSPECTIONS.
 END OF COMMENTS.
 QUESTIONS CONTACT KEN STEVENS.
 (561) 659-8096 X'S 8389 OR 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 09:44 Rev Time 0.50
Received By tlarge Date 2000-01-04 Time 09:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-05-04 Cont ID  
Sent By rmcdouga Date 2001-05-04 Time 10:12 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-04-19 Cont ID  
Sent By rmcdouga Date 2001-04-19 Time 08:38 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-19 00:00:00DENIED
  
 1) TYPICAL EXTERIOR CEILING DETAIL ON
 SHEET A-2 IS INCORRECT; SEE 1997 SBC
 SEC.2504.2.2 WHICH REFERS TO ASTM C 1603
 AT LEAST 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD FRAMING MEMBER IS
 REQUIRED. PLEASE CORRECT.
  
 2) THE 2ND STORY LOFT WINDOW (RIGHT
 ELEVATION) EXCEEDS THE 20% OF OPENING
 AREA ALLOWED BY TABLE 600 OF 97 SBC.
 PLEASE CORRECT.
  
 3) THE BLOCK PRIVACY WALL IS SHOWN AT A
 HEIGHT OF 8' ON SHEETS A-2 & A-4. THE
 MAXIMUM HEIGHT ALLOWED IS 6'. PLEASE
 CORRECT. THIS WILL AFFECT TABLE 600.
  
 4) PROVIDE NEGATIVE AND POSITIVE DESIGN
 PRESSURES (PSF) FOR ALL EXTERIOR DOOR
 AND WINDOW OPENINGS.
  
 5) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO RECEIVING A C.O.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FLAT ROOF SYSTEM
  
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-20 Cont ID  
Sent By lsmith Date 2000-06-20 Time 14:48 Rev Time 0.50
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER TM 6/19/00

Review Stop Z ZONING
Rev No 2 Status P Date 2001-04-25 Cont ID  
Sent By sgraham Date 2001-04-13 Time 16:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-12-29 Time 15:31 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***