Plan Review Stops For Permit 99121447 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-11-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-02 |
Time |
06:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-02 |
Time |
06:38 |
Sent To |
|
|
Notes |
2001-11-02 00:00:00 | ******** NOTED ********** | | | | 1)NOTE: MISSING BLDG/FOOTER STEEL, | | MISSING MAIN SHOWN W/ METER? | | MISSING BATHS LISTED ON PANEL SCHEDULE. | | 210-11-C-3. | | | | ITEMS REDLINED ON PLANS . |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-03-20 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-03-20 |
Time |
11:02 |
Sent To |
|
|
Notes |
2001-03-20 00:00:00 | FOUND AIC RATINGS AND CALCS. REV WAS | | SUBMITTED BEFORE THIS DATE OF 3/20/01 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-03-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-03-21 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-03-21 |
Time |
16:11 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: STILL NEED TO SUBMIT ALL THE | | CORRECTIONS FROM THE FIRST SET OF NOTES. | | NEED TO SUBMIT THE AIC RATING OF MAIN. | | PER 110-9/215-5 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-22 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-22 |
Time |
07:34 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE:NEED TO INCLUDE BLDG.STEEL AS | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | AS REQ`D BY 250-81 | | | | 2)NOTE:NEED TO LIST ON PANEL SCEDULES | | THE DEDICATED BATH(S) CIRCUT(S) REQ`D | | BY 210-52D THEY MUST BE 20AMP #12 AWG. | | | | 3)NOTE: PLEASE DRAW ON PLANS BOTH DISC.S | | THAT ARE SHOWN ON RISER DIAGRAM. 215-5 | | | | 4)NOTE: AS NOTED BEFORE,, NEED TO SUBMIT | | THE AIC RATING OF ALL EQUIPMENT MAINS!!! | | MAINS MUST BE RATED FOR THE AVAILABLE | | FAULT CURRENT FIGURED FROM FAULT CURRENT | | CALCULATIONS. REQ`D BY 110-9/110-10 AND | | 215-5 OF THE NEC. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 | | EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2001-11-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-26 |
Time |
15:20 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-10-26 |
Time |
15:20 |
Sent To |
|
|
Notes |
2001-10-26 00:00:00 | | | MECHANICAL PLANS REVISION ALREADY | | SUBMITTED AND APPROVED PRIOR....NO MECH | | CHANGES WITH THIS SUBMITTAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-20 |
Time |
15:29 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-07-20 |
Time |
15:29 |
Sent To |
|
|
Notes |
2001-07-20 00:00:00 | REVISION MECH PERMIT 00010481. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-03-30 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVIEW OK BY CLYDE THIRBENNY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-01-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-01-28 |
Time |
07:56 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2000-01-28 |
Time |
07:56 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO A/C PLAN; | | A/C CONTRACTOR MUST PROVIDE A/C DRAWING | | WITH APPLICATION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2001-10-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-31 |
Time |
19:28 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-10-31 |
Time |
19:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2000-05-26 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-26 |
Time |
06:45 |
Rev Time |
0.30 |
Received By |
tlarge |
Date |
2000-05-26 |
Time |
06:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISED SANITARY RISER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-05-18 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-18 |
Time |
06:11 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-05-18 |
Time |
06:11 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | MAX.OF 4 FIXTURE UNITS PERMITTED ON 2" | | WET VENT PER SPC SEC.911.1. | | | | VENTING OF 2 WATER CLOSETS SHALL COMPLY | | W/COUNTYWIDE AMENDMENTS TO SPC SEC. | | 911.1.3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-03-21 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-21 |
Time |
05:56 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-03-21 |
Time |
05:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-01-25 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-25 |
Time |
06:38 |
Rev Time |
1.00 |
Received By |
tlarge |
Date |
2000-01-25 |
Time |
06:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SIZE THE PLUMBING RISER IN ITS ENTIRETY | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | 104.2.1. | | | | ALL FIXTURES DOWMSTREAM OF WATER CLOSETS | | SHALL BE INDIVIDUALLY VENTED PER SPC | | 913.2.AND SHOWERS SHALL BE TRAPPED. | | | | SHOW DIMENSIONS OF 2ND FLR.SHOWER.(LXW) | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | SEC.409.8.2.1. | | | | THE LOCATION OF PLUMBING FIXTURES ON THE | | PLUMBING RISER SHALL MATCH THE ARCH. | | FLOOR PLAN. COUNTYWIDE AMENDMENTS TO SPC | | SEC.104.2.1. | | | | MAIN VENT REQD.THRU ROOF.SPC SEC.904.3.1 | | | | BUILDING DRAIN SHALL COMPLY W/SPC SEC. | | 714.1 & TABLE 714.1(FOOTNOTE #3.) | | | | CLARIFY TERMINATION POINT OF KIT.DRAIN. | | (PLANS SHOW OPEN PIPE.) | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | PERMITTED ON HORIZONTAL WET VENTS PER | | COUNTYWIDE AMENDMENTS 911.1 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2001-10-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2001-10-26 |
Time |
08:46 |
Rev Time |
1.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-26 00:00:00 | ************BUILDING PROVISO************ | | REVISION | | 1) PROVIDE PRODUCT APPROVALS FOR ROLL UP | | SHUTTER PRIOR TO INSTALLATION. | | | | 2) PROVIDE INFORMATION ON EXTRA HEAVY | | CHANDELIER TO TRUSS ENGINEER TO VERIFY | | THAT TRUSS DESIGN IS ADEQUATE TO CARRY | | LOAD. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2000-03-06 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-03-06 |
Time |
16:46 |
Rev Time |
5.00 |
Received By |
fknapp |
Date |
2000-03-06 |
Time |
10:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | ****************PROVISO***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | METRO-DADE PRODUCT APPROVALS FOR ALL | | EXTERIOR DOORS AND GARAGE. | | | | 2)PROVIDE PRODUCT INFORMATION FOR | | FIREPLACE. | | | | PLEASE SUBMIT PRIOR TO INSTALLATION | | | | 3)PROVIDE SOIL REPORT PRIOR TO FIRST | | INSPECTION. | | | | 4)PROVIDE IMPACT PROTECTION INFORMATION | | WITH PERMIT APPLICATION. | | | | *****************NOTE******************* | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO., THE PERMIT PLANS STAMPED BY | | THEM AND THE RECIEPT ATTACHED TO THE | | PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-12-29 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-12-29 |
Time |
08:36 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|