Plan Review Details - Permit 99121447
Plan Review Stops For Permit 99121447
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-02 Cont ID  
Sent By dpalmer Date 2001-11-02 Time 06:38 Rev Time 0.00
Received By dpalmer Date 2001-11-02 Time 06:38 Sent To  
Notes
2001-11-02 00:00:00******** NOTED **********
  
 1)NOTE: MISSING BLDG/FOOTER STEEL,
 MISSING MAIN SHOWN W/ METER?
 MISSING BATHS LISTED ON PANEL SCHEDULE.
 210-11-C-3.
  
 ITEMS REDLINED ON PLANS .

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-20 Cont ID  
Sent By dpalmer Date 2001-03-20 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2001-03-20 Time 11:02 Sent To  
Notes
2001-03-20 00:00:00FOUND AIC RATINGS AND CALCS. REV WAS
 SUBMITTED BEFORE THIS DATE OF 3/20/01

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-23 Cont ID  
Sent By dpalmer Date 2000-03-21 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2000-03-21 Time 16:11 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ****************
  
 1)NOTE: STILL NEED TO SUBMIT ALL THE
 CORRECTIONS FROM THE FIRST SET OF NOTES.
 NEED TO SUBMIT THE AIC RATING OF MAIN.
 PER 110-9/215-5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-22 Cont ID  
Sent By dpalmer Date 2000-02-22 Time 07:35 Rev Time 0.00
Received By dpalmer Date 2000-02-22 Time 07:34 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE:NEED TO INCLUDE BLDG.STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 AS REQ`D BY 250-81
  
 2)NOTE:NEED TO LIST ON PANEL SCEDULES
 THE DEDICATED BATH(S) CIRCUT(S) REQ`D
 BY 210-52D THEY MUST BE 20AMP #12 AWG.
  
 3)NOTE: PLEASE DRAW ON PLANS BOTH DISC.S
 THAT ARE SHOWN ON RISER DIAGRAM. 215-5
  
 4)NOTE: AS NOTED BEFORE,, NEED TO SUBMIT
 THE AIC RATING OF ALL EQUIPMENT MAINS!!!
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQ`D BY 110-9/110-10 AND
 215-5 OF THE NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-11-07 Cont ID  
Sent By pkrauss Date 2001-10-26 Time 15:20 Rev Time 0.45
Received By pkrauss Date 2001-10-26 Time 15:20 Sent To  
Notes
2001-10-26 00:00:00 
 MECHANICAL PLANS REVISION ALREADY
 SUBMITTED AND APPROVED PRIOR....NO MECH
 CHANGES WITH THIS SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-07-20 Cont ID  
Sent By pkrauss Date 2001-07-20 Time 15:29 Rev Time 0.30
Received By pkrauss Date 2001-07-20 Time 15:29 Sent To  
Notes
2001-07-20 00:00:00REVISION MECH PERMIT 00010481.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-30 Cont ID  
Sent By fknapp Date 2000-03-30 Time 08:52 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEW OK BY CLYDE THIRBENNY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-28 Cont ID  
Sent By jleech Date 2000-01-28 Time 07:56 Rev Time 0.25
Received By jleech Date 2000-01-28 Time 07:56 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN;
 A/C CONTRACTOR MUST PROVIDE A/C DRAWING
 WITH APPLICATION.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-10-31 Cont ID  
Sent By kstevens Date 2001-10-31 Time 19:28 Rev Time 0.50
Received By kstevens Date 2001-10-31 Time 19:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 06:45 Rev Time 0.30
Received By tlarge Date 2000-05-26 Time 06:45 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-05-18 Cont ID  
Sent By tlarge Date 2000-05-18 Time 06:11 Rev Time 0.33
Received By tlarge Date 2000-05-18 Time 06:11 Sent To  
Notes
2001-01-08 00:00:00MAX.OF 4 FIXTURE UNITS PERMITTED ON 2"
 WET VENT PER SPC SEC.911.1.
  
 VENTING OF 2 WATER CLOSETS SHALL COMPLY
 W/COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.3.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-21 Cont ID  
Sent By tlarge Date 2000-03-21 Time 05:56 Rev Time 0.50
Received By tlarge Date 2000-03-21 Time 05:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-25 Cont ID  
Sent By tlarge Date 2000-01-25 Time 06:38 Rev Time 1.00
Received By tlarge Date 2000-01-25 Time 06:38 Sent To  
Notes
2001-01-08 00:00:00SIZE THE PLUMBING RISER IN ITS ENTIRETY
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 ALL FIXTURES DOWMSTREAM OF WATER CLOSETS
 SHALL BE INDIVIDUALLY VENTED PER SPC
 913.2.AND SHOWERS SHALL BE TRAPPED.
  
 SHOW DIMENSIONS OF 2ND FLR.SHOWER.(LXW)
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.409.8.2.1.
  
 THE LOCATION OF PLUMBING FIXTURES ON THE
 PLUMBING RISER SHALL MATCH THE ARCH.
 FLOOR PLAN. COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 MAIN VENT REQD.THRU ROOF.SPC SEC.904.3.1
  
 BUILDING DRAIN SHALL COMPLY W/SPC SEC.
 714.1 & TABLE 714.1(FOOTNOTE #3.)
  
 CLARIFY TERMINATION POINT OF KIT.DRAIN.
 (PLANS SHOW OPEN PIPE.)
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON HORIZONTAL WET VENTS PER
 COUNTYWIDE AMENDMENTS 911.1

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-10-26 Cont ID  
Sent By rmcdouga Date 2001-10-26 Time 08:46 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-26 00:00:00************BUILDING PROVISO************
 REVISION
 1) PROVIDE PRODUCT APPROVALS FOR ROLL UP
 SHUTTER PRIOR TO INSTALLATION.
  
 2) PROVIDE INFORMATION ON EXTRA HEAVY
 CHANDELIER TO TRUSS ENGINEER TO VERIFY
 THAT TRUSS DESIGN IS ADEQUATE TO CARRY
 LOAD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-03-06 Cont ID  
Sent By fknapp Date 2000-03-06 Time 16:46 Rev Time 5.00
Received By fknapp Date 2000-03-06 Time 10:01 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR ALL
 EXTERIOR DOORS AND GARAGE.
  
 2)PROVIDE PRODUCT INFORMATION FOR
 FIREPLACE.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION
  
 3)PROVIDE SOIL REPORT PRIOR TO FIRST
 INSPECTION.
  
 4)PROVIDE IMPACT PROTECTION INFORMATION
 WITH PERMIT APPLICATION.
  
 *****************NOTE*******************
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-12-29 Time 08:36 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***