Plan Review Stops For Permit 99121250 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-10 |
Time |
16:15 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES ATTACHED TO THE PLANS. | | REVISED PLANS REVIEWED 3/13/00 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-02-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-02-10 |
Time |
13:59 |
Rev Time |
1.45 |
Received By |
jleahy |
Date |
2000-02-10 |
Time |
13:58 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- WORKING CLEARANCES AT SERVICES!!!!!!! | | 110-16 | | | | 2- WATER HEATERS NEED A DISCONNECT IF | | NOT WITHIN SIGHT OF THE PANEL!! |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-04-19 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-09 |
Time |
13:39 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES ON PLANS | | PASSED AS PER BILL STAPLES 04/19/2000 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-01-03 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-03 |
Time |
12:22 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-03-09 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-03-09 |
Time |
06:54 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-03-09 |
Time |
06:54 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PRIOR ISSUES CORRECTED BY REVISIONS SEE | | REVISIONS AND COMMENT SHEETS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-03-09 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-02-10 |
Time |
08:04 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-02-10 |
Time |
08:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | CORRECTED BY REVISIONS3/9/00********** | | | | 1) SHT A-31 DETAIL 3 DRYER VENT AND BAT | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | BOTTOM OF ROOF STRUCTURE | | 2) SHT A-31 DETAIL 2 DRYER VENT TO BE | | MIN. 4" NOT 3", DRYER VENT TO RUN FULL | | LENGTH OUT OF BUILDING | | 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE | | CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX | | METAL DUCT NOT ALLOWED BY CODE | | 4) SHT AC-1 AREAS WITH 300CFM OR GREATER | | REQUIRES RETURN AIR FROM AREA | | 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S | | ON CAPACITY TO PUSH LENGTH OF DUCT USED | | 6) ANY DUCT PENETRATING RATED CEILING | | TO HAVE FIRE DAMPERS PER 1997 SMC 610.2 | | 7) CONDENSING UNIT SERVICE TO BE PER NE | | AND 1997 SMC 304.7.2 WHICHEVER IS GREAT | | ER. DISCONNECT TO BE WITHIN 6' OF THE | | SERVICE SIDE OF THE EQUIPMENT AND A 115 | | GFIC OUTLET REQUIRED. | | 8) SHT AC 5 OVERFLOW PROTECTION REQUIRE | | FOR AHU'S PER 1997 SMC 304.8.6 | | 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT | | ING 2ND FL CONC. FLOOR SLAB ABOVE GARAG | | PROVIDE DETAIL TO SHOW COMPLIANCE W/ SM | | 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D | | FOR FIRE PROTECTION OF ASSEMBLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-03-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-12 |
Time |
12:51 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
2000-03-12 |
Time |
12:43 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | PLUMBING-BUILDING 6D | | | | HORIZONTAL DRY VENTS NOT PERMITTED PER | | SPC SEC.906.2.1. | | | | ENERGY CALCS NOTE EWH AS 65 GALS.AND | | WATER HEATER SCHEDULE ON SHT.P-7 NOTES | | 30 GAL.CLARIFY.FLA.ENERGY CODE SEC.103.2 | | | | SUBMIT COPIES OF PERMITS FROM DEPT.OF | | ENVIRONMENTAL PROTECTION (DEP) AND P.B. | | COUNTY HEALTH DEPT.FOR WATER AND SEWER | | MAINS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-02-09 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-09 |
Time |
15:16 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-02-09 |
Time |
15:16 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE PERMIT 99121248 FOR PLBG.COMMENTS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-09 |
Time |
13:35 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED DENNIS CAMPBELL REPLAT REQUIRED | | APPROVED DENNIS CAMPBELL 3/08/00 |
|
|