Plan Review Details - Permit 99121250
Plan Review Stops For Permit 99121250
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-10 Time 16:15 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ATTACHED TO THE PLANS.
 REVISED PLANS REVIEWED 3/13/00

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-10 Cont ID  
Sent By jleahy Date 2000-02-10 Time 13:59 Rev Time 1.45
Received By jleahy Date 2000-02-10 Time 13:58 Sent To  
Notes
2001-01-08 00:00:001- WORKING CLEARANCES AT SERVICES!!!!!!!
 110-16
  
 2- WATER HEATERS NEED A DISCONNECT IF
 NOT WITHIN SIGHT OF THE PANEL!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-19 Cont ID  
Sent By bstaples Date 2000-02-09 Time 13:39 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ON PLANS
 PASSED AS PER BILL STAPLES 04/19/2000

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-03 Cont ID  
Sent By jleech Date 2001-01-03 Time 12:22 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-09 Cont ID  
Sent By ndenmark Date 2000-03-09 Time 06:54 Rev Time 1.00
Received By ndenmark Date 2000-03-09 Time 06:54 Sent To  
Notes
2001-01-08 00:00:00PRIOR ISSUES CORRECTED BY REVISIONS SEE
 REVISIONS AND COMMENT SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-09 Cont ID  
Sent By ndenmark Date 2000-02-10 Time 08:04 Rev Time 0.33
Received By ndenmark Date 2000-02-10 Time 08:04 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISIONS3/9/00**********
  
 1) SHT A-31 DETAIL 3 DRYER VENT AND BAT
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) SHT AC-1 AREAS WITH 300CFM OR GREATER
 REQUIRES RETURN AIR FROM AREA
 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S
 ON CAPACITY TO PUSH LENGTH OF DUCT USED
 6) ANY DUCT PENETRATING RATED CEILING
 TO HAVE FIRE DAMPERS PER 1997 SMC 610.2
 7) CONDENSING UNIT SERVICE TO BE PER NE
 AND 1997 SMC 304.7.2 WHICHEVER IS GREAT
 ER. DISCONNECT TO BE WITHIN 6' OF THE
 SERVICE SIDE OF THE EQUIPMENT AND A 115
 GFIC OUTLET REQUIRED.
 8) SHT AC 5 OVERFLOW PROTECTION REQUIRE
 FOR AHU'S PER 1997 SMC 304.8.6
 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT
 ING 2ND FL CONC. FLOOR SLAB ABOVE GARAG
 PROVIDE DETAIL TO SHOW COMPLIANCE W/ SM
 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D
 FOR FIRE PROTECTION OF ASSEMBLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 12:51 Rev Time 1.25
Received By tlarge Date 2000-03-12 Time 12:43 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 PLUMBING-BUILDING 6D
  
 HORIZONTAL DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1.
  
 ENERGY CALCS NOTE EWH AS 65 GALS.AND
 WATER HEATER SCHEDULE ON SHT.P-7 NOTES
 30 GAL.CLARIFY.FLA.ENERGY CODE SEC.103.2
  
 SUBMIT COPIES OF PERMITS FROM DEPT.OF
 ENVIRONMENTAL PROTECTION (DEP) AND P.B.
 COUNTY HEALTH DEPT.FOR WATER AND SEWER
 MAINS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-02-09 Cont ID  
Sent By tlarge Date 2000-02-09 Time 15:16 Rev Time 1.50
Received By tlarge Date 2000-02-09 Time 15:16 Sent To  
Notes
2001-01-08 00:00:00SEE PERMIT 99121248 FOR PLBG.COMMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-09 Time 13:35 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED DENNIS CAMPBELL REPLAT REQUIRED
 APPROVED DENNIS CAMPBELL 3/08/00