Plan Review Details - Permit 99121248
Plan Review Stops For Permit 99121248
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By lsmith Date 2000-09-14 Time 08:38 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00REV#3 5/1/00 S-3

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-08 Time 09:08 Rev Time 5.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE CHECK LIST ATTACHED TO PLANS
 REVISIONS REVIEWED 3/13/00

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-31 Cont ID  
Sent By jleahy Date 2000-03-31 Time 15:32 Rev Time 2.00
Received By jleahy Date 2000-03-31 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-07 Cont ID  
Sent By jleahy Date 2000-01-07 Time 15:02 Rev Time 0.00
Received By jleahy Date 2000-02-10 Time 13:56 Sent To  
Notes
2001-01-08 00:00:00E-1 SERVICE FOR "HE" IS MOUNTED ONUNIT
 TOWN HOUSE,MAINS TO BE GROUPED
  
 E-1 MORE THAN ONE SERVICE ON A BUILDING
  
 E-1 OUTLET OUTSIDE ON CABANA NOT SHOWN
 WITH GFCI PROTECTION
  
 E-1 PARKING GARAGE IS SHOWN WITH 2 ADD-
 TIONAL SERVICES.MAINS NOT GROUPED!
  
 E-1 110-16 FOR SERVICE EQUIPMENT
 WORKING SPACE IN FRONT OF ALL SERVIC
 EQUIPMENT!!!!!!!!!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-01 Cont ID  
Sent By bstaples Date 2000-02-04 Time 16:15 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ON PLANS M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-28 Cont ID  
Sent By jleech Date 2000-12-28 Time 16:21 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2001-01-08 00:00:00A/C REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-09 Cont ID  
Sent By ndenmark Date 2000-03-09 Time 06:52 Rev Time 1.00
Received By ndenmark Date 2000-03-09 Time 06:52 Sent To  
Notes
2001-01-08 00:00:00PRIOR ISSUES CORRECTED BY REVISIONS SEE
 REVISIONS AND COMMENT SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-09 Cont ID  
Sent By ndenmark Date 1999-12-28 Time 08:40 Rev Time 1.00
Received By ndenmark Date 1999-12-28 Time 08:40 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISIONS3/9/00*****
  
 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) SHT AC-1 AREAS WITH 300CFM OR GREATER
 REQUIRES RETURN AIR FROM AREA
 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S
 ON CAPACITY TO PUSH LENGTH OF DUCT USED
 6) ANY DUCT PENETRATING RATED CEILING
 TO HAVE FIRE DAMPERS PER 1997 SMC 610.2
 7) CONDENSING UNIT SERVICE TO BE PER NEC
 AND 1997 SMC 304.7.2 WHICHEVER IS GREAT-
 ER. DISCONNECT TO BE WITHIN 6' OF THE
 SERVICE SIDE OF THE EQUIPMENT AND A 115V
 GFIC OUTLET REQUIRED.
 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED
 FOR AHU'S PER 1997 SMC 304.8.6
 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT-
 ING 2ND FL CONC. FLOOR SLAB ABOVE GARAGE
 PROVIDE DETAIL TO SHOW COMPLIANCE W/ SMC
 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D
 FOR FIRE PROTECTION OF ASSEMBLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 12:30 Rev Time 1.25
Received By tlarge Date 2000-03-12 Time 12:15 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 PLUMBING-BUILDING 5D
  
 HORIZONTAL DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1.
  
 ENERGY CALCS.NOTE EWH AS 65 GALS.AND
 WATER HEATER SCHEDULE ON SHT.P-7 NOTES
 30 GAL.CLARIFY.FLA.ENERGY CODE SEC.103.2
  
 SUBMIT COPIES OF PERMITS FROM DEPT. OF
 ENVIRONMENTAL PROTECTION (DEP) AND P.B.
 COUNTY HEALTH DEPT.FOR WATER AND SEWER
 MAINS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-11 Cont ID  
Sent By tlarge Date 2000-01-11 Time 11:22 Rev Time 7.75
Received By tlarge Date 2000-01-10 Time 16:39 Sent To  
Notes
2001-01-08 00:00:00SHT.P-1-THE WATER SERVICE TO THE CABANA
 DOESN'T APPEAR TO BE PROTECTED AGAINST
 BACKFLOW.COMPLY W/SPC SEC.606.1.
  
 DRINKING FOUNTAIN AT CABANA SHALL
 COMPLY W/FACBC SEC.4.1.3(10)(A).
  
 SHT.P-1.-SHOW DIMENSIONS OF TOILET ROOMS
 COMPLY W/FACBC SEC.4.16.2.AND FIG.28.
  
 SUBMIT NUMBER OF PERSONS THAT WILL BE
 UTILIZING THE CABANA AT ANY ONE TIME.
 COMPLY W/TABLE 407 OF SPC.
  
 SHT.P-2-CONDENSATE LINES ARE SHOWN AS
 2" AND 1 1/4" CLARIFY.
  
 SHT.P-2-SUBMIT A SANITARY ISOMETRIC THAT
 IS LEGIBLE AND CLEARLY REFLECTS THE
 SCOPE OF THE INSTALLATION PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT
 P-1 NOTES 30 GAL.CLARIFY.FEC SEC.103.2.
 (SEE SHT.P-7)
  
 CONDENSATE DRAINS ON MULTIPLE STORY
 BUILDINGS SHALL BE VENTED WHERE 2 OR
 MORE UNITS ARE CONNECTED TO COMMON RISER
 PER COUNTYWIDE AMENDMENTS SEC.5.
  
 SUBMIT CONDENSATE RISER FOR REVIEW PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT IRRIGATION PLANS IF APPLICABLE &
 INDICATE WATER SUPPLY SOURCE FOR SYSTEM.
 A WATER USE PERMIT FROM SFWMD MAY BE
 REQD.PER F.S.373.219,373.62.
  
 CIVIL DRAWINGS SHALL BE SIGNED AND
 SEALED PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.3.,F.S.471.025.
  
 NOTE:A SEPARATE PERMIT SHALL BE REQD.FOR
 THE POOL,FOUNTAIN,CABANA .

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-04 Time 16:14 Rev Time 0.10
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED DENNIS CAMPBELL RE-PLAT REQUIRED
 APPROVED 3/13/00 DENNIS CAMPBELL