Plan Review Details - Permit 99121245
Plan Review Stops For Permit 99121245
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-01 Time 16:31 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ATTACHED TO PLANS. WRS 2/1/00
 REVISIONS REVIEWED 3/13/00

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-02 Cont ID  
Sent By jleahy Date 2000-02-02 Time 10:05 Rev Time 2.00
Received By jleahy Date 2000-02-02 Time 09:57 Sent To  
Notes
2001-01-08 00:00:001-110-16 WORKING CLEARANCE AT METERS
 WILL BE 3' IN FRONT OF METER!!!!!
  
 2-MAIN FOR PANEL "HD" WILL HAVE TO BE
 GROUPED WITH METERS AND OTHER MAINS
 SHOWN AT THIS LOCATION.
  
 3-TYPE 2 TOWNHSE. WILL HAVE TO PUT A D
 DISCONNECT AT THE WATER HEATER
  
 3-NOT SURE ON TYPE 1 CAN'T TELL IF
 THERE IS A WALL IN FROINT OF THE
 WATER HEATER.
  
 4-NEED A RISER DIAGRAM SHOWING HOW
 PANEL HD IS TO BE FED ALONG WITH THE
 TOWNHSE. METER AND MAIN!!!!!!!!!!!!
  
 5-SUBMIT THIS INFORMATION BEFORE 1ST
 ELECTRICAL INSPECTION (ROUGH)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-25 Cont ID  
Sent By bstaples Date 2000-02-01 Time 17:23 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ON PLANS M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-03 Cont ID  
Sent By jleech Date 2001-01-03 Time 12:57 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-08 Cont ID  
Sent By ndenmark Date 2000-03-08 Time 15:36 Rev Time 1.00
Received By ndenmark Date 2000-03-08 Time 15:36 Sent To  
Notes
2001-01-08 00:00:00ISSUES CORRECTED BY REVISIONSNCD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-04 Cont ID  
Sent By ndenmark Date 2000-01-04 Time 11:16 Rev Time 0.50
Received By ndenmark Date 2000-01-04 Time 11:16 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
  
  
  
  
 CORRECTED BY REVISIONS3/8/00 NCD******
  
 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) SHT AC-1 AREAS WITH 300CFM OR GREATER
 REQUIRES RETURN AIR FROM AREA
 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S
 ON CAPACITY TO PUSH LENGTH OF DUCT USED
 6) ANY DUCT PENETRATING RATED CEILING
 TO HAVE FIRE DAMPERS PER 1997 SMC 610.2
 7) CONDENSING UNIT SERVICE TO BE PER NEC
 AND 1997 SMC 304.7.2 WHICHEVER IS GREAT-
 ER. DISCONNECT TO BE WITHIN 6' OF THE
 SERVICE SIDE OF THE EQUIPMENT AND A 115V
 GFIC OUTLET REQUIRED.
 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED
 FOR AHU'S PER 1997 SMC 304.8.6
  
 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT-
 ING 2ND FL CONC. FLOOR SLAB ABOVE GARAGE
 PROVIDE DETAIL TO SHOW COMPLIANCE W/ SMC
 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D
 FOR FIRE PROTECTION OF ASSEMBLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 11:35 Rev Time 1.25
Received By tlarge Date 2000-03-12 Time 11:26 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 PLUMBING-BUILDING 4D
  
 ENERGY CALCS.NOTE EWH AS 65 GALS.AND
 WATER HEATER SCHEDULE ON SHT.P7 NOTES 30
 GAL.CLATIFY.FLA.ENERGY CODE SEC.103.2.
  
 HORIZONTAL DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1 (SHT.P2-SEE 2ND.FLR.VENT
  
 SUBMIT COPIES OF PERMITS FROM DEPT.OF
 ENVIRONMENTAL PROTECTION(DEP) AND HEALTH
 DEPT.FOR WATER AND SEWER MAINS.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-01-26 Cont ID  
Sent By tlarge Date 1999-01-26 Time 15:51 Rev Time 3.00
Received By tlarge Date 1999-01-26 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00REFER TO PERMIT #99121236 FOR GENERIC
 COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-01 Time 17:22 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED D. CAMPBELL
 APPROVED BY DENNIS CAMPBELL 3/8/00