Plan Review Stops For Permit 99121245 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-01 |
Time |
16:31 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES ATTACHED TO PLANS. WRS 2/1/00 | | REVISIONS REVIEWED 3/13/00 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-02-02 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-02-02 |
Time |
10:05 |
Rev Time |
2.00 |
Received By |
jleahy |
Date |
2000-02-02 |
Time |
09:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1-110-16 WORKING CLEARANCE AT METERS | | WILL BE 3' IN FRONT OF METER!!!!! | | | | 2-MAIN FOR PANEL "HD" WILL HAVE TO BE | | GROUPED WITH METERS AND OTHER MAINS | | SHOWN AT THIS LOCATION. | | | | 3-TYPE 2 TOWNHSE. WILL HAVE TO PUT A D | | DISCONNECT AT THE WATER HEATER | | | | 3-NOT SURE ON TYPE 1 CAN'T TELL IF | | THERE IS A WALL IN FROINT OF THE | | WATER HEATER. | | | | 4-NEED A RISER DIAGRAM SHOWING HOW | | PANEL HD IS TO BE FED ALONG WITH THE | | TOWNHSE. METER AND MAIN!!!!!!!!!!!! | | | | 5-SUBMIT THIS INFORMATION BEFORE 1ST | | ELECTRICAL INSPECTION (ROUGH) |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-01 |
Time |
17:23 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES ON PLANS M. CARSILLO |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-01-03 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-03 |
Time |
12:57 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-03-08 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-03-08 |
Time |
15:36 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-03-08 |
Time |
15:36 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ISSUES CORRECTED BY REVISIONSNCD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-01-04 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-01-04 |
Time |
11:16 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-01-04 |
Time |
11:16 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | | | | | | | | | | | | | | | CORRECTED BY REVISIONS3/8/00 NCD****** | | | | 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | BOTTOM OF ROOF STRUCTURE | | 2) SHT A-31 DETAIL 2 DRYER VENT TO BE | | MIN. 4" NOT 3", DRYER VENT TO RUN FULL | | LENGTH OUT OF BUILDING | | 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE | | CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX | | METAL DUCT NOT ALLOWED BY CODE | | 4) SHT AC-1 AREAS WITH 300CFM OR GREATER | | REQUIRES RETURN AIR FROM AREA | | 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S | | ON CAPACITY TO PUSH LENGTH OF DUCT USED | | 6) ANY DUCT PENETRATING RATED CEILING | | TO HAVE FIRE DAMPERS PER 1997 SMC 610.2 | | 7) CONDENSING UNIT SERVICE TO BE PER NEC | | AND 1997 SMC 304.7.2 WHICHEVER IS GREAT- | | ER. DISCONNECT TO BE WITHIN 6' OF THE | | SERVICE SIDE OF THE EQUIPMENT AND A 115V | | GFIC OUTLET REQUIRED. | | 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED | | FOR AHU'S PER 1997 SMC 304.8.6 | | | | 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT- | | ING 2ND FL CONC. FLOOR SLAB ABOVE GARAGE | | PROVIDE DETAIL TO SHOW COMPLIANCE W/ SMC | | 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D | | FOR FIRE PROTECTION OF ASSEMBLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-03-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-12 |
Time |
11:35 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
2000-03-12 |
Time |
11:26 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | PLUMBING-BUILDING 4D | | | | ENERGY CALCS.NOTE EWH AS 65 GALS.AND | | WATER HEATER SCHEDULE ON SHT.P7 NOTES 30 | | GAL.CLATIFY.FLA.ENERGY CODE SEC.103.2. | | | | HORIZONTAL DRY VENTS NOT PERMITTED PER | | SPC SEC.906.2.1 (SHT.P2-SEE 2ND.FLR.VENT | | | | SUBMIT COPIES OF PERMITS FROM DEPT.OF | | ENVIRONMENTAL PROTECTION(DEP) AND HEALTH | | DEPT.FOR WATER AND SEWER MAINS.COUNTY- | | WIDE AMENDMENTS TO SPC SEC.101.4.7. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
1999-01-26 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-01-26 |
Time |
15:51 |
Rev Time |
3.00 |
Received By |
tlarge |
Date |
1999-01-26 |
Time |
15:51 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REFER TO PERMIT #99121236 FOR GENERIC | | COMMENTS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-01 |
Time |
17:22 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED D. CAMPBELL | | APPROVED BY DENNIS CAMPBELL 3/8/00 |
|
|