Plan Review Details - Permit 99121241
Plan Review Stops For Permit 99121241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-17 Cont ID  
Sent By bstaples Date 2000-03-17 Time 09:11 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS REVIEWED 3/17/00 WRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-25 Cont ID  
Sent By bstaples Date 2000-01-25 Time 15:03 Rev Time 0.00
Received By bstaples Date 2000-01-26 Time 16:07 Sent To  
Notes
2001-01-08 00:00:001. SHEET A-1 NOTE #4 SHOWS TYPE VI CONST
 TYPE VI CONST. NOT ALLOWED IN FIRST FIRE
 DISTRICT SEE APPENDIX F, 1997 SBC.
 2. REVISE SHEET A-1 TO REFLECT OPEANINGS
 SIZE ALLOWED BASED ON TYPE OF
 CONSTRUCTION USED SEE TABLE 600, 1997SBC
 3.REVISE EXTERIOR WALL DESIGN FOR FIRE
 DISTRICT BASED ON FIRE DISTRICT AND
 TABLE 600, 1997 SBC.
 4. SHEET A-2- INDICATES A DUCT BANK
 UNDER THE BUILDING NO EASEMENT RELEASES
 ON FILE. NO STRUCTURAL DETAILS ON PLANS.
 5. SHEET A-20 CHANGE REFERENCE FROM PALM
 BEACH COUNTY TO THE CITY OF WEST PALM
 BEACH.
 6. SUBMIT TRUSS DRAWINGS FOR REVIEW.
 7. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR WINDOWS AND DOORS AS PER REQUIREMENT
 SHEET A-33.
 8. NOTE: CANOPIES, FENCES, GATES, SIGNS
 AND FOUNTIANS REQUIRE SEPERATE PERMITS.
 9. SHEET A-28 MAILBOXES UNDER STAIRS
 COMPLY WITH 1006.1.4, 1997 SBC
 10.SHEET A-29 SECTION A INDICATES WOOD
 FRAME ROOF SYSTEM ENERGY SHEET INDICATE
 CONCRETE ROOF WITH R10 INSULATION REVISE
 11. SHEET A-32 INDICATES IN NOTES THAT
 MISSLE IMPACT NOTES ARE ON SHEET A-27.
 A-27 DOES NOT CONTAIN THE INFORMATION
 PROPER REFERENCE IS A-33.
 12. SHEET A-32 DOOR SCHEDULE DOORS DO
 NOT MATCH ELEVATION SEE DOOR #7.
 13. SHEET A-33 CODE REFERENCE FOR MISSLE
 IMPACT AND WIND DESIGN IS NOT CORRECT
 INDICATES 1994 SBC SHOULD BE 1997 SBC.
 14. SHEET A-35 REFERENCES WRONG EDITION
 OF THE FAIR HOUSING ACT.
 15. SHEET S-9 SECTION 7 INDICATES A
 1 1/2" OFFSET, SHEET A-32 SECTION 5
 INDICATES 1/2" AND COMPLIES WITH FAIR
 HOUSING ACT DOORS.
 16. SHEET S-12 DOES NOT INDICATE CODE
 EDITION (1997) OR METHOUD OF COMPLIANCE
 1606 OR ASCE-7-95 FOR BUILDING DESIGN.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2001-03-07 Time 10:54 Sent To  
Notes
2001-03-07 00:00:00REV FOR E-2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-20 Cont ID  
Sent By jleahy Date 2000-01-20 Time 12:56 Rev Time 2.00
Received By jleahy Date 2000-01-20 Time 12:55 Sent To  
Notes
2001-01-08 00:00:001-SUBMIT AIC RATING FOR PANELS AND CIR
 BREAKERS BEFORE FINAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-25 Cont ID  
Sent By bstaples Date 2000-01-25 Time 07:34 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ATTACHED TO PLANS M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-28 Cont ID  
Sent By jleech Date 2000-12-28 Time 14:13 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-21 Cont ID  
Sent By ndenmark Date 2000-03-21 Time 07:11 Rev Time 0.50
Received By ndenmark Date 2000-03-21 Time 07:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-21 Cont ID  
Sent By ndenmark Date 2000-01-10 Time 13:31 Rev Time 1.00
Received By ndenmark Date 2000-01-10 Time 13:31 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISION 3/21/00***********
 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE.
 2) SHT A-31 DRYER VENT DUCT TO BE 4" NOT
 3".
 3) CONDENSATE DRAIN LINE SHALL NOT VENT
 INTO OCCUPIED SPACE. CARRY VENT THROUGH
 ROOF
 4) SHT AC-4 SHOWS DRYER VENT INTO SUB-
 DUCT. DRYER VENT TO RUN FULL LENGTH OUT
 OF BUILDING
 5) OVERFLOW PROTECTION REQUIRED FOR AHUS
 PER 1997 SMC 304.8.6

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-04-01 Cont ID  
Sent By tlarge Date 2000-04-01 Time 10:11 Rev Time 1.00
Received By tlarge Date 2000-04-01 Time 10:11 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO*************
 SHOWERS IN COVERED UNITS SHALL BE
 CHANGED TO BATHTUBS TO COMPLY W/FEDERAL
 FAIR HOUSING ACT 24 CFR 100.205.
 (SEE SIGNED AND SEALED LETTER FROM ARCH.
 FIRM ATTACHED TO PLANS.)
  
 WATER RISER FOR UNIT DOESN'T CORRELATE
 W/ARCH.FLOOR PLAN.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.
  
 A PERMIT IS REQD. FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION AND P.B.COUNTY
 HEALTH DEPT.SUBMIT COPIES OF APPROVALS
 .COUNTYWIDE AMENDMENTS TO SPC 101.4.7.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 10:43 Rev Time 1.25
Received By tlarge Date 2000-03-12 Time 10:43 Sent To  
Notes
2001-01-08 00:00:00****************PLUMBING****************
 BUILDING 3D
 WATER RISER FOR UNIT "D" DOESN'T MATCH
 THE ARCH. FLOOR PLAN.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 THE DEPT.OF ENVIRONMENTAL PROTECTION AND
 P.B.COUNTY HEALTH DEPT.SUBMIT COPIES OF
 APPROVALS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 ALL BATHROOMS IN THECOVERED DWELL-
 ING UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT 24 CFR 100.205 (C)(3)(IV)
 REQ.#7(2),PARAGRAPH (A) 0R (B).CLEAR
 FLOOR SPACE SHALL BE SHOWN ON THE PLANS
 AND DESIGNATE WHICH DESIGN SPECIFICATION
 ("A" OR "B")OF THE FAIR HOUSING ACT IS
 BEING USED.
 ***NOTE:IF YOU CHOOSE SPECIFICATION "A",
 IT APPLIES TOALL BATHROOMS AND CLEAR
 FLOOR SPACE IS REQD.AT THE SHOWER.IN
 SPECIFICATION "B" BATHROOMS,ONLY ONE
 BATHING FIXTURE SHALL BE PROVIDED W/THE
 REQD.CLEAR FLOOR SPACE.A 30"X 48" CLEAR
 FLOOR SPACE IS REQD.ADJACENT TO THE
 BATHTUB.AS DESIGNED THE SHOWERS AND
 BATHTUBS DO NOT COMPLY W/THE ACT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-26 Cont ID  
Sent By tlarge Date 2000-01-26 Time 14:01 Rev Time 4.75
Received By tlarge Date 2000-01-25 Time 20:28 Sent To  
Notes
2001-01-08 00:00:00CONDENSATE DRAINS SHLL BE VENTED TO THE
 ATMOSPHERE PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.804.3(5).
  
 WATER RISER FOR UNIT "D" DOESN'T MATCH
 THE ARCH.FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.A-35 NOTES THAT BATHROOMS WILL BE
 DESIGNED UNDER THE FEDERAL FAIR
 HOUSING ACT REQ.#7(2)(A).THIS
 SPECIFICATION APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS
 MUST BE USABLE.CLEAR FLOOR SPACE FOR
 FIXTURES AS ILLUSTRATED IN THE ACT SHALL
 BE PROVIDED.UNITS "C"AND "D" DO NOT
 COMPLY FOR THE BATHROOMS W/SHOWERS.
  
 A PERMIT FOR THE WATER MAIN IS REQD.FROM
 DEPT.OF ENVIRON.PROTECTION.SUBMIT COPY
 OF PERMIT FOR REVIEW.AN ADDITIONAL
 PERMIT MAY ALSO BEREQD.FROM P.B.COUNTY
 HEALTH DEPT.SUBMIT ALL REQD.APPROVALS
 SPC 1O1.4.7.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-07 Cont ID  
Sent By bstaples Date 2000-01-25 Time 07:43 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED DENNIS CAMPBELL 2/7/00


Account Summary | Usage Policy | Privacy Policy