Plan Review Stops For Permit 99121239 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2000-05-08 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-08 |
Time |
14:32 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PERMIT ISSUED FOR FOUNDATIN TO GRADE. | | NO WORK IS TO BE PERFORMED ABOVE THIS | | POINT. NEW PLANS SHALL BE REQUIRED AND | | WILL BE RVIEWED FOR CODE COMPLIANCE. | | SEE CHECK LIST ATTACHED FOR COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-04-24 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-04-24 |
Time |
09:31 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FIRST REVIEW | | 1. EFIS, PROVIDE CODE COMPLIANCE | | INFORMATION SEE 1997 SBC CHAPTER 26 AND | | APPENDIX F FOR MINUMUM REQUIREMENTS. | | 2. OK REC. 4/28/00CERTIFICATION FOR | | WIND LOADS SEE 1997 SBC CHAPTER16. | | 3. SUBMIT PRODUCT INFORMATION FOR ALL | | GLAZING FOR WIND AND IMPACT PROTECTION, | | 4. EXIT FROM MEZZAINE SEE 1997 SECTION | | 1006.2.4 OPEANINGS ADJACENT TO EXIT. | | SEE ELEVATION ON SHEET 1.05. | | 5. FIRE RATING OF WALLS AND CELING AT | | INTERIOR LOADING DOCK SEE 1997 SBC | | SECTIONS 610 AND 704. | | 6. HANDRAILS SHALL COMPLY WITH FL. HCC | | FOR BULDING CONST. SEE FIG. 19 AND SHEET | | A7.1 SECTION 1. | | 7. HANDICAPPED RAMP NOT LOCATED AT | | BUILDING ENTRY PROVIDE PLAN TO LIMIT USE | | OF OUT DOOR SEATING AREA, OUT LINE | | ACCESSABLE ROUTE AND SINAGE TO BE USED. | | SEE FL. ACCESSABILITY CODE 4.1.3(7). | | 8. AWNINGS REQUIRE SEPERATE PERMITS. | | 9. COPY OF SOILS REPORT FOR THE SITE. | | 10. REVIEW IS FOR SHELL AND FOUNDATION | | ONLY ADDITIONAL PERMITS AND FEES WILL | | BE REQUIRED. | | 11. FLORIDA ENERGY SHEETS REQUIRED. | | 12. PAY IMPACT FEES. | | 13. NO INTERIOR FIRE SEPERATION OR | | LIFE SAFETY INCLUDED SEPERATE PERMIT | | REQUIRED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2000-05-08 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-08 |
Time |
14:58 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FOUNDATION TO GRADE NO ELECTRICAL WORK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-04-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-04-24 |
Time |
06:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-04-24 |
Time |
06:13 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE PROVIDE ALL DETAILS ON | | SLABBED ELECTRICAL CONDUITS. PLEASE | | INCLUDE ANY PENETRATION THROGH ANY | | SHELL STRUCTURES. | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 | | EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-04-24 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-04-24 |
Time |
10:41 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE PROVISO ISSUED BY M. CARSILLO | | 4/21/00 ATTACHED TO PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-04-25 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-04-24 |
Time |
15:38 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-04-24 |
Time |
15:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVIDE MECH INFO AT TIME OF BUILDOUT | | INSUFFICIENT INFORMATION INCLUDED FOR | | REVIEW AT THIS TIME | | PROVIDE DETAILS OF MECHANICAL INSTALLA- | | TION FOR REVIEW |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2000-05-08 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-08 |
Time |
14:58 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FOUNDATION TO GRADE NO PLUMBING PERMIT |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-04-26 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-04-26 |
Time |
17:21 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | SHELL ONLY | | (1) SHT A-1.03 SPC SEC.1107,1109 RAIN | | WATERDRAINS & SECONDARY DRAINS, | | PROVIDE SQUARE FOOTAGE FOR EACH DRAIN, | | PIPE SIZES WITH ISOMETRIC LAYOUT. | | (2) SHOW LOCATION OF WATER SUPPLY, | | SANITARY SEWER FOR FUTURE USE. | | PLUMBING DENIED ANY QUESTIONS | | PAUL SCHMITZ 561-659-8096 X 82323 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-04-26 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-04-26 |
Time |
10:02 |
Rev Time |
0.50 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVIEWED DENNIS CAMPBELL 4/26/00 |
|
|