Plan Review Stops For Permit 99121236 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-01 |
Time |
09:21 |
Rev Time |
4.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE PLANS FOR NOTES WRS 2/1/00 | | REVISIONS REVIEWED 3/13/00 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-04-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-04-05 |
Time |
16:35 |
Rev Time |
2.30 |
Received By |
jleahy |
Date |
2000-04-05 |
Time |
16:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-01-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-01-14 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-01-14 |
Time |
12:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1 - SERVICE DOES NOT MEET CODE | | 2 - MAINS TO BE GROUPED230-72 | | 3 - ONE LATERAL TO THE BUILDING230-2 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-04-21 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-01-14 |
Time |
13:54 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES ON PLANS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2000-12-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-28 |
Time |
15:17 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | A/C REVISION |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-03-08 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-03-08 |
Time |
15:30 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-03-08 |
Time |
15:30 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PRIOR ISSUES CORRECTED BY REVISIONS | | SUBMITTED AND REVIEWED ON 3/8/00 NCD | | SEE REVISIONS AND COMMENTS SHEETS BY | | ROGER FRY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-02-01 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-02-01 |
Time |
10:20 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-02-01 |
Time |
10:20 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | | | | | CORRECTED BY REVISIONS3/8/00********* | | | | 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | BOTTOM OF ROOF STRUCTURE NOT REQUIRED | | 2) SHT A-31 DETAIL 2 DRYER VENT TO BE | | MIN. 4" NOT 3", DRYER VENT TO RUN FULL | | LENGTH OUT OF BUILDING | | 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE | | CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX | | METAL DUCT NOT ALLOWED BY CODE | | 4) SHT AC-1 AREAS WITH 300CFM OR GREATER | | REQUIRES RETURN AIR FROM AREA | | 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S | | ON CAPACITY TO PUSH LENGTH OF DUCT USED | | 6) ANY DUCT PENETRATING RATED CEILING | | TO HAVE FIRE DAMPERS PER 1997 SMC 610.2 | | 7) CONDENSING UNIT SERVICE TO BE PER NEC | | AND 1997 SMC 304.7.2 WHICHEVER IS GREAT- | | ER. DISCONNECT TO BE WITHIN 6' OF THE | | SERVICE SIDE OF THE EQUIPMENT AND A 115V | | GFIC OUTLET REQUIRED. | | 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED | | FOR AHU'S PER 1997 SMC 304.8.6 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2000-03-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-12 |
Time |
08:10 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-03-12 |
Time |
08:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | BUILDING 1D | | | | | | | | | | ENERGY CALCS. NOTE EWH AS 65 GALS.AND | | WATER HEATER SCHEDULE ON SHT.P-7 NOTES | | 30 GAL.CLARIFY.FLA.ENERGY CODE SEC. | | 103.2. | | | | HORIZONTAL DRY VENTS NOT PERMITTED PER | | SPC SEC.906.2.1.(SHT.P2-SEE 2ND.FLR.VENT | | | | SUBMIT COPY OF PERMITS FROM DEPT. OF | | ENVIRONMENTAL PROTECTION (DEP) AND | | HEALTH DEPT.FOR WATER AND SEWER MAINS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-03-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-01 |
Time |
11:51 |
Rev Time |
2.00 |
Received By |
tlarge |
Date |
2000-03-01 |
Time |
11:51 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT | | P-7 NOTES 30 GALS.CLARIFY.FEC SEC.103.2. | | | | PERMIT IS REQD.FROM DEPT.OF | | ENVIRONMENTAL PROTECTION (DEP)FOR THE | | SEWER MAINS AND THE WATER MAINS.A PERMIT | | MAY ALSO BE REQD.FROM DEPT.OF HEALTH | | FOR THE WATERE MAINS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-01-14 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-14 |
Time |
18:40 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
2000-01-14 |
Time |
18:40 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHT.P-2-CONDENSATE LINES ARE SHOWN AS 2" | | AND AS 1 1/4".CLARIFY. | | | | SHT.P-2-SUBMIT A SANITARY ISOMETRIC THAT | | IS LEGIBLE AND CLEARLY REFLECTS THE | | SCOPE OF THE INSTALLATION PER COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1.(SUBMIT | | ONE LAYOUT OF THE UNITS AND SEWER.DELETE | | ALTERNATES.) | | | | ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT | | P-1 NOTES 30 GAL.CLARIFY.FEC.SEC.103.2. | | (SEE SHT.7.) | | | | CONDENSATE DRAINS ON MULTIPLE STORY | | BUILDINGS SHALL BE VENTED WHERE 2 OR | | MORE UNITS ARE CONNECTED TO A COMMON | | RISER PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.804.3(5). | | | | SUBMIT CONDENSATE RISER FOR REVIEW PER | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | SUBMIT IRRIGATION PLANS IF APPLICABLE | | AND INDICATE WATER SUPPLY SOURCE FOR | | SYSTEM.A WATER USE PERMIT MAY BE REQD. | | FROM SFWMD PER F.S.373.219. | | | | CIVIL DRAWINGS SHALL BE SEALED PER F.S. | | 471.025,104.2.3. | | | | NOTE:SEPARATE PERMITS SHALL BE REQD.FOR | | THE POOL,FOUNTAIN AND CABANA. | | | | A PERMITIS REQUIRED FROM THE DEPT.OF | | ENVIRONMENTAL PROTECTION (DEP) FOR THE | | WATER AND SEWER MAINS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-03-13 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-02-01 |
Time |
09:22 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENNIS CAMPBELL DENIED REQUIRES RE PLAT | | APPROVED DENNIS CAMPBELL 3/08/00 |
|
|