Plan Review Details - Permit 99121236
Plan Review Stops For Permit 99121236
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-01 Time 09:21 Rev Time 4.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PLANS FOR NOTES WRS 2/1/00
 REVISIONS REVIEWED 3/13/00

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-05 Cont ID  
Sent By jleahy Date 2000-04-05 Time 16:35 Rev Time 2.30
Received By jleahy Date 2000-04-05 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-01-14 Cont ID  
Sent By jleahy Date 2000-01-14 Time 12:08 Rev Time 0.00
Received By jleahy Date 2000-01-14 Time 12:09 Sent To  
Notes
2001-01-08 00:00:001 - SERVICE DOES NOT MEET CODE
 2 - MAINS TO BE GROUPED230-72
 3 - ONE LATERAL TO THE BUILDING230-2

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-21 Cont ID  
Sent By bstaples Date 2000-01-14 Time 13:54 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES ON PLANS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-28 Cont ID  
Sent By jleech Date 2000-12-28 Time 15:17 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2001-01-08 00:00:00A/C REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-08 Cont ID  
Sent By ndenmark Date 2000-03-08 Time 15:30 Rev Time 1.00
Received By ndenmark Date 2000-03-08 Time 15:30 Sent To  
Notes
2001-01-08 00:00:00PRIOR ISSUES CORRECTED BY REVISIONS
 SUBMITTED AND REVIEWED ON 3/8/00 NCD
 SEE REVISIONS AND COMMENTS SHEETS BY
 ROGER FRY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-02-01 Cont ID  
Sent By ndenmark Date 2000-02-01 Time 10:20 Rev Time 1.00
Received By ndenmark Date 2000-02-01 Time 10:20 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 CORRECTED BY REVISIONS3/8/00*********
  
 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH
 EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO
 BOTTOM OF ROOF STRUCTURE NOT REQUIRED
 2) SHT A-31 DETAIL 2 DRYER VENT TO BE
 MIN. 4" NOT 3", DRYER VENT TO RUN FULL
 LENGTH OUT OF BUILDING
 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE
 CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX
 METAL DUCT NOT ALLOWED BY CODE
 4) SHT AC-1 AREAS WITH 300CFM OR GREATER
 REQUIRES RETURN AIR FROM AREA
 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S
 ON CAPACITY TO PUSH LENGTH OF DUCT USED
 6) ANY DUCT PENETRATING RATED CEILING
 TO HAVE FIRE DAMPERS PER 1997 SMC 610.2
 7) CONDENSING UNIT SERVICE TO BE PER NEC
 AND 1997 SMC 304.7.2 WHICHEVER IS GREAT-
 ER. DISCONNECT TO BE WITHIN 6' OF THE
 SERVICE SIDE OF THE EQUIPMENT AND A 115V
 GFIC OUTLET REQUIRED.
 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED
 FOR AHU'S PER 1997 SMC 304.8.6

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 08:10 Rev Time 1.50
Received By tlarge Date 2000-03-12 Time 08:09 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 BUILDING 1D
  
  
  
  
 ENERGY CALCS. NOTE EWH AS 65 GALS.AND
 WATER HEATER SCHEDULE ON SHT.P-7 NOTES
 30 GAL.CLARIFY.FLA.ENERGY CODE SEC.
 103.2.
  
 HORIZONTAL DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1.(SHT.P2-SEE 2ND.FLR.VENT
  
 SUBMIT COPY OF PERMITS FROM DEPT. OF
 ENVIRONMENTAL PROTECTION (DEP) AND
 HEALTH DEPT.FOR WATER AND SEWER MAINS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-01 Time 11:51 Rev Time 2.00
Received By tlarge Date 2000-03-01 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT
 P-7 NOTES 30 GALS.CLARIFY.FEC SEC.103.2.
  
 PERMIT IS REQD.FROM DEPT.OF
 ENVIRONMENTAL PROTECTION (DEP)FOR THE
 SEWER MAINS AND THE WATER MAINS.A PERMIT
 MAY ALSO BE REQD.FROM DEPT.OF HEALTH
 FOR THE WATERE MAINS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-14 Cont ID  
Sent By tlarge Date 2000-01-14 Time 18:40 Rev Time 1.25
Received By tlarge Date 2000-01-14 Time 18:40 Sent To  
Notes
2001-01-08 00:00:00SHT.P-2-CONDENSATE LINES ARE SHOWN AS 2"
 AND AS 1 1/4".CLARIFY.
  
 SHT.P-2-SUBMIT A SANITARY ISOMETRIC THAT
 IS LEGIBLE AND CLEARLY REFLECTS THE
 SCOPE OF THE INSTALLATION PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.(SUBMIT
 ONE LAYOUT OF THE UNITS AND SEWER.DELETE
 ALTERNATES.)
  
 ENERGY CALCS.NOTE EWH AS 60 GALS.AND SHT
 P-1 NOTES 30 GAL.CLARIFY.FEC.SEC.103.2.
 (SEE SHT.7.)
  
 CONDENSATE DRAINS ON MULTIPLE STORY
 BUILDINGS SHALL BE VENTED WHERE 2 OR
 MORE UNITS ARE CONNECTED TO A COMMON
 RISER PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.804.3(5).
  
 SUBMIT CONDENSATE RISER FOR REVIEW PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT IRRIGATION PLANS IF APPLICABLE
 AND INDICATE WATER SUPPLY SOURCE FOR
 SYSTEM.A WATER USE PERMIT MAY BE REQD.
 FROM SFWMD PER F.S.373.219.
  
 CIVIL DRAWINGS SHALL BE SEALED PER F.S.
 471.025,104.2.3.
  
 NOTE:SEPARATE PERMITS SHALL BE REQD.FOR
 THE POOL,FOUNTAIN AND CABANA.
  
 A PERMITIS REQUIRED FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION (DEP) FOR THE
 WATER AND SEWER MAINS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By bstaples Date 2000-02-01 Time 09:22 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENNIS CAMPBELL DENIED REQUIRES RE PLAT
 APPROVED DENNIS CAMPBELL 3/08/00