Plan Review Details - Permit 99121043
Plan Review Stops For Permit 99121043 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-04-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-04-25 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-04-25 |
Time |
07:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-01-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-01-08 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-01-08 |
Time |
11:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-12-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
1999-12-28 |
Time |
08:00 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
1999-12-28 |
Time |
08:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
1999-12-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-12-27 |
Time |
10:19 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
1999-12-27 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2000-04-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2000-04-21 |
Time |
19:08 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2000-04-21 |
Time |
19:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SUBMITTAL FOR ITEMS ON PREVIOUS PROVISO | | DATED 1-21-00 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2000-02-22 |
Time |
09:11 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2000-02-22 |
Time |
09:11 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-SPECIFY CONNECTORS CAPABLE OF | | RESISTING THE UPLIFT LOADS CALCULATED | | ON THE ENGINEERED ROOF TRUSSES FOR THE | | FOLLOWING TRUSSES: H6, H7, H8. | | 2-REVISE ARCHITECT'S ROOF FRAMING PLAN | | TO MATCH ROOF FRAMING PLAN SHOWN BY | | THE TRUSS COMPANY. AND, SPECIFY THE | | REQUIRED CONNECTORS. SEE COMMENTS ON | | ROOF PLAN BY THE TRUSS COMPANY. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2000-01-21 |
Time |
16:17 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2000-01-21 |
Time |
16:17 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE "A0". PROVIDE ELEVATION | | CERTIFICATE. | | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOOR WITH SIDELITE ASSEMBLY. | | 3-STORM PANELS: | | -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS | | AND ANCHOR SPACING TO BE USED | | ACCORDING TO THE EDGE DISTANCE, DESIGN | | PRESSURES, PANEL SPAN AND BUILDING | | CONSTRUCTION. | | NOTE: THIS HOUSE IS BUILT WITH MASONRY | | NOT CONCRETE. THEREFORE, USE ANCHOR | | SPACING AS REQUIRED. | | 4-SEE COMMENTS ON PLANS AND UPDATE | | DRAWINGS AS REQUIRED. | | 5-RE-SUBMIT PRODUCT APPROVALS FOR DOORS | | AND WINDOWS (AND MULLIONS). |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2000-01-28 |
Time |
12:33 |
Rev Time |
0.15 |
Received By |
jgomez |
Date |
2000-01-28 |
Time |
12:32 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | APPROVED BY GRACE 12-23-99 |
|
|
|