Plan Review Details - Permit 99120039
Plan Review Stops For Permit 99120039 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-01-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-01-07 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-01-07 |
Time |
16:29 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************PROVISO******************** | | | | 1)NOTE:AS PER 215-5 IF THERE ARE GOING | | TO BE TWO DISCONNECTS? THEN YOU NEED | | TO HAVE THEM BOTH DRAWN ON PLANS. | | | | 2)NOTE:AS PER ART;210-52D/215-5 PLEASE | | HAVE DEDICATED BATH(S) CIRCUT(S) SHOWN | | ON PANEL SCHED. NEEDS TO BE 20AMP #12 | | AWG. | | | | 3)NOTE:AS PER 250-81/215-5 NEED TO SHOW | | BLDG.STEEL AS PART OF THE GROUNDING | | ELECTRODE SYSTEM. | | | | 4)NOTE;NEED TO SUBMIT AIC RATING OF | | EQUIPMENT MAINS/PANELS AS PER THE FOLLOW | | -ING NEC ARTS:110-9/230-65/215-5 | | AIC RATING IS FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | | | 5)NOTE: AS NOTED BEFORE!! AS PER ART: | | 373-8 PANELS/DISCONNECTS ETC ARE NOT TO | | BE USED AS RACEWAYS!!!!!!!!!!!!! THERE | | MUST BE AN ADDITIONAL CONDUIT FROM METER | | GOING TO SECOND DISC.!!!!! | | EACH COONDUIT MUST ONLY CONTAIN ONE SET | | OF CONDUCTORS. | | | | **************************************** | | ALL THE ABOVE INFORMATION NEEDS TO BE | | SUBMITTED FOR REVIEW AND APPROVAL | | BEFORE THE FIRST ROUGH ELECTRICAL | | INSPECTION IS CALLED IN!!!!! IF THERE | | ARE ANY QUESTIONS,,,CALL 659-8096 EXT. | | 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-12-21 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
1999-12-21 |
Time |
15:30 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
1999-12-21 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-10-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-17 |
Time |
16:32 |
Rev Time |
0.30 |
Received By |
tlarge |
Date |
2000-10-17 |
Time |
16:32 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | AS BUILT PLBG.RISER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
1999-12-20 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-12-20 |
Time |
09:17 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
1999-12-20 |
Time |
09:17 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************PROVISO****************** | | GAS DRAWING COMPLYING W/NFPA 54 AND STD. | | GAS CODE SHALL BE SUBMITTED FOR REVIEW | | PRIOR TO ISSUANCE OF GAS PERMIT. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2000-01-10 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-01-10 |
Time |
13:37 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
2000-01-10 |
Time |
09:46 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | *****************PROVISO**************** | | | | SBC 104.2.2 | | | | 1)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVALS FOR ALL EXTERIOR SWING DOORS. | | | | 2)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | OPENINGS. | | | | 3)PROVIDE SPECIFIC WINDOW AND DOOR BUCK | | CONNECTION DETAILS FOR WINDLOAD SBC 1606 | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO., THE PERMIT PLANS STAMPED BY | | THEM AND THE RECIEPT ATTACHED TO THE | | PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-12-10 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-12-10 |
Time |
15:01 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|