Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By dpalmer Date 2000-01-07 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2000-01-07 Time 16:29 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:AS PER 215-5 IF THERE ARE GOING
 TO BE TWO DISCONNECTS? THEN YOU NEED
 TO HAVE THEM BOTH DRAWN ON PLANS.
  
 2)NOTE:AS PER ART;210-52D/215-5 PLEASE
 HAVE DEDICATED BATH(S) CIRCUT(S) SHOWN
 ON PANEL SCHED. NEEDS TO BE 20AMP #12
 AWG.
  
 3)NOTE:AS PER 250-81/215-5 NEED TO SHOW
 BLDG.STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 4)NOTE;NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANELS AS PER THE FOLLOW
 -ING NEC ARTS:110-9/230-65/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 5)NOTE: AS NOTED BEFORE!! AS PER ART:
 373-8 PANELS/DISCONNECTS ETC ARE NOT TO
 BE USED AS RACEWAYS!!!!!!!!!!!!! THERE
 MUST BE AN ADDITIONAL CONDUIT FROM METER
 GOING TO SECOND DISC.!!!!!
 EACH COONDUIT MUST ONLY CONTAIN ONE SET
 OF CONDUCTORS.
  
 ****************************************
 ALL THE ABOVE INFORMATION NEEDS TO BE
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE THE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN!!!!! IF THERE
 ARE ANY QUESTIONS,,,CALL 659-8096 EXT.
 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-21 Cont ID  
Sent By cthirben Date 1999-12-21 Time 15:30 Rev Time 1.00
Received By cthirben Date 1999-12-21 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-17 Cont ID  
Sent By tlarge Date 2000-10-17 Time 16:32 Rev Time 0.30
Received By tlarge Date 2000-10-17 Time 16:32 Sent To  
Notes
2001-01-08 00:00:00AS BUILT PLBG.RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 09:17 Rev Time 0.75
Received By tlarge Date 1999-12-20 Time 09:17 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 GAS DRAWING COMPLYING W/NFPA 54 AND STD.
 GAS CODE SHALL BE SUBMITTED FOR REVIEW
 PRIOR TO ISSUANCE OF GAS PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-10 Cont ID  
Sent By fknapp Date 2000-01-10 Time 13:37 Rev Time 4.00
Received By fknapp Date 2000-01-10 Time 09:46 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR ALL EXTERIOR SWING DOORS.
  
 2)PROVIDE ENGINEERING FOR ALL BUTT GLASS
 OPENINGS.
  
 3)PROVIDE SPECIFIC WINDOW AND DOOR BUCK
 CONNECTION DETAILS FOR WINDLOAD SBC 1606
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-10 Cont ID  
Sent By gjoyce Date 1999-12-10 Time 15:01 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved