Plan Review Stops For Permit 99120033 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-12-01 |
Time |
15:16 |
Rev Time |
0.30 |
Received By |
jleahy |
Date |
1999-12-01 |
Time |
15:12 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- SUBMIT LOAD CALCS. FOR UNITS | | 2- NEED BRANCH CIRCUIT NUMBERS FOR THE | | ELECTRICAL WORK SHOWN ON PLAN | | 3- NEED SERVICE OUTLET AT EACH LOCATION | | FOR ACS | | 4- SERVICE OUTLET IS TO BE GFI PROTECTED | | 5- PROVIDE THIS INFORMATION PRIOR TO | | ANY ELECTRICAL INSPECTIONS |
|
|
|