Plan Review Details - Permit 99111358
Plan Review Stops For Permit 99111358
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-02-01 Cont ID  
Sent By lmartine Date 2000-01-10 Time 12:04 Rev Time 0.00
Received By lmartine Date 2000-01-25 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-22 Cont ID  
Sent By dpalmer Date 2000-05-22 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2000-05-22 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 21:25 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 21:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-23 Cont ID  
Sent By dpalmer Date 1999-12-23 Time 06:22 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE: PLEASE SHOW HOW THE CONTINUOUS
 LIGHTING LOAD WAS FIGURED INTO THE
 LOAD CALCULATION. NEEDS TO BE FIGURED AT
 125%
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By dlauderm Date 1999-12-27 Time 09:32 Rev Time 0.25
Received By dlauderm Date 1999-12-27 Time 09:31 Sent To  
Notes
2001-01-08 00:00:00ALL INSIDE, NO REVIEW NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-03-07 Cont ID  
Sent By rturnque Date 2000-03-07 Time 11:36 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-03 Cont ID  
Sent By rturnque Date 1999-12-03 Time 14:07 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-31 Cont ID  
Sent By cthirben Date 2000-03-31 Time 14:47 Rev Time 0.50
Received By cthirben Date 2000-03-31 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By ndenmark Date 1999-12-16 Time 13:41 Rev Time 0.50
Received By ndenmark Date 1999-12-16 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 VENTILATION FOR CLEANING AREA TO BE PER
 1997 SMC 512. PROVIDE MEANS FOR REMOTE
 CONTROL AND SHALL OPERATE AUTOMATICALLY
 WHEN EQUIPMENT IS IN USE

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-05-11 Cont ID  
Sent By tlarge Date 2000-05-11 Time 09:46 Rev Time 0.50
Received By tlarge Date 2000-05-11 Time 09:45 Sent To  
Notes
2001-01-08 00:00:00SANITARY AND WATER REVISIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-06 Cont ID  
Sent By tlarge Date 2000-05-06 Time 05:59 Rev Time 1.50
Received By tlarge Date 2000-05-06 Time 05:59 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 A CLEANOUT IS REQD.ON THE INLET TO
 INTERCEPTOR PER SPC SEC.710.4.
  
 FLOOR DRAIN IN LAUNDRY AREA SHALL BE A
 MIN.OF 3" PER SPC SEC.4.9.4.5
  
 PLANS DON'T CORRELATE.ONE SET SHOWS F.D.
 IN LAUNDRY AREA, ONE DOES NOT.CLARIFY
  
 SUBMIT ADDITIONAL INFORMATION FROM
 MANUF.FOR TRAFFIC BEARING LINT TRAP.
 SUBMITTED INFORMATION IS VAGUE AS TO
 TRANSFERRAL OF IMPOSED LOADS ON TANK.
 SPC SEC.303.5.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-03-01 Cont ID  
Sent By tlarge Date 2000-03-01 Time 14:45 Rev Time 1.00
Received By tlarge Date 2000-03-01 Time 14:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-03-01 Cont ID  
Sent By tlarge Date 2000-02-02 Time 05:34 Rev Time 0.00
Received By tlarge Date 2000-02-02 Time 05:34 Sent To  
Notes
2001-01-08 00:00:00SHOW LOCATION OF GAS METER ON PLANS.
 LOCATION SHALL COMPLY W/SGC SEC.303.&
 NFPA 54
  
 SUBMIT UPDATED PRODUCT APPROVAL SHEETS
 FOR LINT TRAP.(APPROVAL EXPIRED 11/21/99
  
 SUBMIT MANUF.SHEETS FOR H20 UNIT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT
 PER SGC SEC.402.1.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-01 Cont ID  
Sent By tlarge Date 1999-12-04 Time 08:34 Rev Time 0.00
Received By tlarge Date 2000-01-25 Time 09:11 Sent To  
Notes
2001-01-08 00:00:00 
 SUBMIT UPDATED PRODUCT APPROVAL SHEETS
 FOR LINT TRAP.(APPROVAL EXPIRED 11/21/99
  
 SUBMIT MANUF.SHEETS FOR H2O UNIT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIP.SGC
 SEC.402.1
  
 FLOOR DRAIN IN BOILER EXCEEDS DISTANCE
 FROM VENT PER SPC 908.1.
  
 GALV.PIPE NOT PERMITTED U/G FOR WATER
 PIPE PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.6.11.3.DELETE NOTE#12 ON P-3.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOW LOCATION OF GAS METER.METER SHALL
 BE PROTECTED FROM DAMAGE.SGC 303.
  
 H.C.DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A)-PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.