Plan Review Details - Permit 99111338
Plan Review Stops For Permit 99111338
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-07 Cont ID  
Sent By dpalmer Date 2000-03-07 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By dpalmer Date 1999-12-09 Time 11:49 Rev Time 0.00
Received By dpalmer Date 1999-12-09 Time 11:49 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT MAINS/BRKRS. AIC ARTING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: NEED TO SUBMIT RISER DIAGRAM
 SHOWING DEDICATED 20 AMP CIRCUT REQ`D
 PER 210-52D.
  
 3)PLEASE INCLUDE COLD WATER PIPE AS PART
 OF GROUNDING ELECTRODE SYSTEM. PLEASE
 SHOW ON RISER DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By cthirben Date 1999-12-06 Time 16:37 Rev Time 1.00
Received By cthirben Date 1999-12-06 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By tlarge Date 1999-12-02 Time 18:57 Rev Time 0.33
Received By tlarge Date 1999-12-02 Time 18:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-17 Cont ID  
Sent By jcaloger Date 1999-12-17 Time 15:35 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By gjoyce Date 1999-12-01 Time 10:00 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved