Plan Review Details - Permit 99111320
Plan Review Stops For Permit 99111320
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-12-09 Cont ID  
Sent By dpalmer Date 1999-12-09 Time 05:56 Rev Time 0.00
Received By dpalmer Date 1999-12-09 Time 05:56 Sent To  
Notes
2001-01-08 00:00:00*************UNSAT*********************
  
 1)NOTE: NEED TO SUBMIT AIC RATING WITH
 ALL DRAWINGS. NEED TO AIC RATING FOR
 ALL EQUIPMENT MAINS/BKRS AS PER 110-9
 215-5. AIC RATING IS FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
 2)NOTE;EQUIPMENT GROUND REQ`D BETWEEN
 MAIN DISC. AND PANEL SIZE PER 250-95.
  
 3)NOTE:AS REQ`D BY 250-81/215-5 PLEASE
 SHOW BDLG.STEEL AS PART OF THR GROUNDING
 ELECTRODE SYSTEM.
  
 4)NOTE:AS REQ`D BY 215-5/210-52D PLEASE
 SHOW DEDICATED BATH(S) 20AMP CIRCUT ON
 PANEL SCHEDULE.
  
 5)NOTE:AS REQ`D PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW RES. DWELLINGS.
  
 6)NOTE: PLEASE DELETE ALL ITEMS THAT ARE
 NOT STAYING ON PANEL SCHEDULE. PLEASE
 CLEAN UP AND REDRAW. CLEAN UP ANY
 SHADED AREAS ON PLANS THAT ARE NOT MEANT
 TO BE THERE.
  
  
 PLEASE SUBMIT THE ABOVEINFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS; 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By cthirben Date 1999-12-09 Time 07:57 Rev Time 1.00
Received By cthirben Date 1999-12-09 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-05 Cont ID  
Sent By tlarge Date 2000-02-05 Time 07:41 Rev Time 0.33
Received By tlarge Date 2000-02-05 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-05 Cont ID  
Sent By tlarge Date 1999-12-02 Time 18:28 Rev Time 0.33
Received By tlarge Date 1999-12-02 Time 18:28 Sent To  
Notes
2001-01-08 00:00:00LOCATION OF FIXTURES ON SANITARY RISER
 DOESN'T MATCH ARCH.FLOOR PLAN.(MASTER
 BATH AND GUEST BATH.)COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1,104.2.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-02-16 Cont ID  
Sent By fknapp Date 2000-02-16 Time 13:32 Rev Time 3.00
Received By fknapp Date 2000-02-16 Time 13:32 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-12-30 Cont ID  
Sent By jcaloger Date 1999-12-30 Time 15:02 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE PLANS NEEDS TO HAVE PERSONAL
 SIGNATURE OVER THE RAISE SEAL OF THE
 ARCHITECT.
  
 THE GUEST SUITE WINDOWS ARE REQUIRED TO
 PROVIDE THE EGRESS REQUIREMENTS STATED
 IN SECTION 1005.4.4 SBC 1997. NOTE PGT
 WINDOW SIZE OF 24SH DOES NOT MEET THE
 CODE REQUIREMENT.
  
 THE US TRUSS LAYOUT PLAN ILLUSTRATES A
 2 STORY STRUCTURE AND THE ARCHITECT
 PALNS SPECIFY A ONE STORY STRUCTURE.
  
 THE FRONT DOOR IS REQUIRED TO PROVIDE A
 MINIUM 32" CLEAR OPENING WHEN ONE LEAF
 IS OPEN.
  
 PROVIDE PRODUCT APPROVAL FOR THE EXTERIO
 SWING DOORS.
  
 THE DESIGN COMPLIANCE FORM SPECIFYS THAT
 THE STRUCTURE WAS DESIGNED ACCORDING TO
 THE INVALID CODE EDITION, SBC 1994. NOTE
 THAT THE CURRENT CODE EDITION IS THE
 1997 SBC. ATTACHED IS A COPY OF THE
 UPDATED DESIGN COMPLIANCE FORM.
  
 CLARIFY THE HEIGHT AND WIDTH DEMINSION
 FOR THE F1 FOOTER.

Review Stop Z ZONING
Rev No 2 Status P Date 1999-12-23 Cont ID  
Sent By gjoyce Date 1999-12-23 Time 08:56 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 1999-12-01 Cont ID  
Sent By gjoyce Date 1999-12-01 Time 10:03 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:006' WALL CROSSING FPL EASEMENT; EASMENT R
 RELEASE REQUIRED