Plan Review Details - Permit 99111215
Plan Review Stops For Permit 99111215
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-22 Cont ID  
Sent By lmartine Date 1999-12-22 Time 15:27 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 21:42 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 21:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-20 Cont ID  
Sent By dpalmer Date 1999-12-20 Time 14:12 Rev Time 0.00
Received By dpalmer Date 1999-12-20 Time 14:12 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE:E-1 SHOWS ELECTRICAL PANEL 'A'
 SHEET E-3 DOES NOT SHOW PANEL SCHEDULE
 FOR PANEL 'A'. PLEASE SUBMIT!!
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS OF
 MAINS.230-65/110-9/215-5
  
 3)NOTE:NEED TO HAVE RATED DISC. FROM
 GENERATOR ON THE INSIDE OF BLDG.INLINE/
 INFRONT OF ATS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By rturnque Date 1999-12-07 Time 09:12 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-06 Cont ID  
Sent By cthirben Date 2000-04-06 Time 07:19 Rev Time 1.00
Received By cthirben Date 2000-04-06 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-22 Cont ID  
Sent By ndenmark Date 1999-12-22 Time 07:05 Rev Time 0.25
Received By ndenmark Date 1999-12-22 Time 07:05 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved