2001-01-08 00:00:00 | SUBMIT MANUFACTURERS SHEET FOR DENTAL |
| CHAIRS,VACUUM PUMP,AIR COMPRESSORS AND |
| ALL OTHER MEDICAL EQUIPMENT. COUNTYWIDE |
| AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1. |
| |
| CLEARLY SHOW DIMENSIONS OF NEW TOILET |
| ROOM AND SHOW FIXTURE CLEARANCE OF H.C. |
| WATER CLOSET AND SUBMIT DETAILS/HEIGHT |
| DIMENSIONS OF ALL H.C.EQUIPMENT AND |
| FIXTURES.COMPLY W/FACBC FOR NEW |
| CONSTRUCTION 1997 ED. |
| |
| A DRINKING FOUNTAIN IS REQD.PER TABLE |
| 407 AND SHALL BE H.C.ACCESSIBLEPER |
| FACBC 4.1.3.(10)(A),4.15. |
| |
| SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/ |
| SPC TABLE 407 FOR AMOUNT OF PLBG.FIXS. |
| |
| SUBMIT DATA FROM MANUFACTURER REGARDING |
| PH OF EFFLUENT FROM AUTO-PROCESSOR. |
| ACCEPTABLE RANGE IS 5.0-10.0. A |
| NEUTRALIZING TANK SHALL BE INSTALLED IF |
| THIS RANGE CANNOT BE MAINTAINED PER |
| SPC SEC.801.4.SUBMIT MANUF.SHEETS FOR |
| PROCESSOR AND DEVELOPER. |
| |
| SUBMIT COPY OF CONTRACT FOR PROPER |
| DISPOSAL OF PROCESSING CHEMICALS AND |
| SILVER FROM DEVELOPING TANK.SPC 301.3. |
| |
| ALL SUBMITTED SHOP DWGS./MANUF.SHEETS |
| SHALL BE LEGIBLE FOR REVIEW PER COUNTY- |
| WIDE AMENDMENTS TO STD.PLBG.CODE SEC. |
| 104.2.1,104.2.2. |
| |
| SUBMIT SIGNED AND SEALED DRAWINGS FOR |
| THE ENTIRE MEDICAL PIPING SYSTEM PER |
| COUNTYWIDE AMENDMENTS TO STANDARD PLBG. |
| CODE SEC.104.2.1.,104.2.3.COMPLY W/NFPA |
| 99. |
| |
| SIZE ALL THE VENTS ON THE SAN.RISER |
| DIAGRAMS AND SUBMIT WATER RISER DIAGRAMS |
| FOR ALL ALTERED PLBG PER COUNTYWIDE |
| AMENDMENTS TO STD.PLBG.CODE 104.2.1., |
| 104.2.2. |
| |
| CLEARLY SHOW REQD.TURNING SPACE IN H.C. |
| TOILET ROOM PER FACBC SEC.4.2.3. |
| |
| |
| INDICATE PREVIOUS OCCUPANCY OF STRUCTURE |
| IF THIS IS A CHANGE OF OCCUPANCY,THE |
| BUILDING SHALL CONFORM TO THE INTENT OF |
| THE TECHNICAL CODES AS REQD.BY THE |
| BUILDING OFFICIAL PER SBC SEC.3401.2.2.1 |