Plan Review Details - Permit 99110890
Plan Review Stops For Permit 99110890
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-10 Cont ID  
Sent By lmartine Date 1999-11-23 Time 07:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-24 Cont ID  
Sent By lmartine Date 1999-11-24 Time 07:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-23 Cont ID  
Sent By rturnque Date 1999-11-23 Time 11:25 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-11-22 Cont ID  
Sent By ndenmark Date 1999-11-22 Time 07:42 Rev Time 0.00
Received By wlehnhar Date 2000-01-10 Time 14:31 Sent To  
Notes
2001-01-08 00:00:00NO AIR CONDITIONING INCLUDED FOR REVIEW
 PROVIDE A/C PLANS WITH MECHANICAL PERMIT
 APPLICATION
 MEDICAL GAS (DENTAL INCL) REQUIRES MECH
 PERMIT, PROVIDE COMPLETE PLANS WITH MECH
 PERMIT APPLICATION PRIOR TO STARTING
 INSTALLATION FOR APPROVAL (NFPA 99C 1993
 CODE FOR COMPLIANCE)

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-12-09 Time 16:07 Rev Time 0.50
Received By tlarge Date 1999-12-09 Time 16:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-11-19 Time 15:27 Rev Time 2.50
Received By tlarge Date 1999-11-19 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00SUBMIT MANUFACTURERS SHEET FOR DENTAL
 CHAIRS,VACUUM PUMP,AIR COMPRESSORS AND
 ALL OTHER MEDICAL EQUIPMENT. COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 CLEARLY SHOW DIMENSIONS OF NEW TOILET
 ROOM AND SHOW FIXTURE CLEARANCE OF H.C.
 WATER CLOSET AND SUBMIT DETAILS/HEIGHT
 DIMENSIONS OF ALL H.C.EQUIPMENT AND
 FIXTURES.COMPLY W/FACBC FOR NEW
 CONSTRUCTION 1997 ED.
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 AND SHALL BE H.C.ACCESSIBLEPER
 FACBC 4.1.3.(10)(A),4.15.
  
 SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC TABLE 407 FOR AMOUNT OF PLBG.FIXS.
  
 SUBMIT DATA FROM MANUFACTURER REGARDING
 PH OF EFFLUENT FROM AUTO-PROCESSOR.
 ACCEPTABLE RANGE IS 5.0-10.0. A
 NEUTRALIZING TANK SHALL BE INSTALLED IF
 THIS RANGE CANNOT BE MAINTAINED PER
 SPC SEC.801.4.SUBMIT MANUF.SHEETS FOR
 PROCESSOR AND DEVELOPER.
  
 SUBMIT COPY OF CONTRACT FOR PROPER
 DISPOSAL OF PROCESSING CHEMICALS AND
 SILVER FROM DEVELOPING TANK.SPC 301.3.
  
 ALL SUBMITTED SHOP DWGS./MANUF.SHEETS
 SHALL BE LEGIBLE FOR REVIEW PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SEC.
 104.2.1,104.2.2.
  
 SUBMIT SIGNED AND SEALED DRAWINGS FOR
 THE ENTIRE MEDICAL PIPING SYSTEM PER
 COUNTYWIDE AMENDMENTS TO STANDARD PLBG.
 CODE SEC.104.2.1.,104.2.3.COMPLY W/NFPA
 99.
  
 SIZE ALL THE VENTS ON THE SAN.RISER
 DIAGRAMS AND SUBMIT WATER RISER DIAGRAMS
 FOR ALL ALTERED PLBG PER COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE 104.2.1.,
 104.2.2.
  
 CLEARLY SHOW REQD.TURNING SPACE IN H.C.
 TOILET ROOM PER FACBC SEC.4.2.3.
  
  
 INDICATE PREVIOUS OCCUPANCY OF STRUCTURE
 IF THIS IS A CHANGE OF OCCUPANCY,THE
 BUILDING SHALL CONFORM TO THE INTENT OF
 THE TECHNICAL CODES AS REQD.BY THE
 BUILDING OFFICIAL PER SBC SEC.3401.2.2.1

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By gjoyce Date 1999-12-02 Time 09:58 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***