Plan Review Details - Permit 99110858
Plan Review Stops For Permit 99110858
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-06-05 Cont ID  
Sent By bstaples Date 2000-05-09 Time 08:32 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00OWES FEES, TWO REVISIONS $500.00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-27 Cont ID  
Sent By jwitmer Date 1999-12-22 Time 07:51 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SHEET PD-A3.01 EAST ELEVATION
 SECTION A5.01(A) NOT ABLE TO LOCATE?
 2. OWES FEES
 OK.CODE COMPLIANCE CERTIFICATION FLORIDA
 STATUTES CHAPTER 553.79(7)(D).OK 1/27/00
 REVISION 1/27/00
 1. EASEMENT UNDER BUILDING NOT APPROVED
 EASMENT RELEASE NOT ON FILE.OK 2/9/00
 2. DOORS ADDED TO ELEVATIONS SOUTH AND
 WEST LACK INFORMATION OK 4/26/00.
 DOORS ARE REQUIRED TO BE RATED BASED
 ON RATING OF EXTERIOR WALLS.
 OK.1/27/00FROM ANTONIO CANTILLO NOT
 SEALED AND ONLY ONE COPY RECEIVED.
 4. PLANS NOT CORRECTED AS REQUIRED TO
 ALLOW FOR ISSUANCE OF PERMIT.
 5. DENIED ZONING DENNIS CAMPBELL OK 2/9

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-27 Cont ID  
Sent By jleahy Date 2000-04-27 Time 11:38 Rev Time 2.00
Received By jleahy Date 2000-04-27 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-19 Cont ID  
Sent By jleahy Date 2000-01-19 Time 11:59 Rev Time 2.00
Received By jleahy Date 2000-01-19 Time 11:03 Sent To  
Notes
2001-01-08 00:00:001-PAGE PD-E3.05
 STAIR TOWERS 1 AND 3 NEED EXIT LIGHT
 THAT ARE W/P110-3B,11
  
 2-PAGE PD-E5.01
 TRANSFER SWITCH NEEDS A DISCONNECT
 ON THE LINE SIDE OF THE TRANSFER
 SWITCH225-8
  
 3-PAGE PD-E5.03
 SUBMIT A LOAD CALCULATION PER 215-5
 FOR THE MAIN FEEDERS TO THE BUILDING
  
 4-PAGE PD-E4.03
 ALL OUTLETS OUTSIDE ON ROOF LEVEL TO
 BE G.F.C.I. PROTECTED.
  
 5-PROVIDE THIS INFORMATION PRIOR TO
 FIRST ELECTRICAL ROUGH INSPECTION!

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-05-09 Cont ID  
Sent By bstaples Date 2000-05-09 Time 10:16 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE M. CARSILLO DENIED REVIEW ATTACHED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-26 Cont ID  
Sent By bstaples Date 2000-01-19 Time 13:42 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PLANS FOR REQUIREMENTS AS PER
 MIKE CARSILLO
 OK FOR PERMIT M. CARSILLO TELEPHONE
 3/31/00. WRS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-05 Cont ID  
Sent By ndenmark Date 2000-06-05 Time 14:35 Rev Time 0.50
Received By ndenmark Date 2000-06-05 Time 14:35 Sent To  
Notes
2001-01-08 00:00:00REVISIONS OK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-05-04 Cont ID  
Sent By ndenmark Date 2000-05-04 Time 07:25 Rev Time 1.00
Received By ndenmark Date 2000-05-04 Time 07:25 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISIONS******************
  
 1)1997 SBC 411.5.4 REQUIRES GARAGES TO
 BE CONTINUOUSLY VENTILATED BY A MECHAN-
 ICAL SYSTEM WITH A POSITIVE MEANS FOR
 BOTH INLET AND EXHAUST OF AT LEAST 0.75
 CFM PER SQ FT OF FLOOR AREA, 411.4.2
 REQUIRES AT LEAST 6 AIR CHANGES PER HOUR
 F0R EACH LEVEL. PROVIDE CALCULATIONS
 SHOWING COMPLIANCE.
 2) MECHANICAL PLANS SHOW C02 SENSOR,
 CODE REQUIRES REMOVAL OF PRODUCTS OF
 COMBUSTION. IS THIS SUPPLIMENTAL TO
 CONTINUOUS VENTILATION AS REQUIRED ABOVE
 AND WHAT FUNCTION DOES TIME CLOCK HOLD?
 3) ACCESS DOORS REQUIRED FOR FIRE DAMPER
 ACCESS. PROVIDE DETAILS FOR REQUIRED
 FIRE DAMPER ACCESS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-01-10 Cont ID  
Sent By ndenmark Date 2000-01-10 Time 10:39 Rev Time 2.00
Received By ndenmark Date 2000-01-10 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1)PROVIDE CALCULATIONS SHOWING COMPLI-
 ANCE WITH 1997 SBC 411.4.2
 2)PROVIDE SEQUENCE OF OPERATON FOR REQ'D
 VENTILATION AND SYSTEM TO BE CONNECTED
 TO EMERGENCY POWER SYSTEM
 3)IS VENT SHAFT RATED? IF RATED PROVIDE
 DETAIL FOR PROTECTION OF OPENINGS AT
 EXHAUST FAN PENETRATION

Review Stop P PLUMBING
Rev No 8 Status P Date 2000-11-04 Cont ID  
Sent By pschmitz Date 2000-11-04 Time 08:27 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION,ROOF DRAIN CALCULATIONS.

Review Stop P PLUMBING
Rev No 7 Status P Date 2000-09-26 Cont ID  
Sent By tlarge Date 2000-09-26 Time 08:46 Rev Time 1.50
Received By tlarge Date 2000-09-26 Time 08:46 Sent To  
Notes
2001-01-08 00:00:00SIGNED AND SEALED ROOF DRAIN CALCULATION

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-07-15 Cont ID  
Sent By pschmitz Date 2000-07-15 Time 08:25 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-06-19 Cont ID  
Sent By tlarge Date 2000-06-19 Time 15:51 Rev Time 3.50
Received By pschmitz Date 2000-06-19 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00ALL SHEETS OF THE STORM DRAINAGE
 CALCULATIONS SHALL BE SIGNED AND SEALED
 BY DESIGN PROFESSIONAL OF RECORD PER FL.
 ADMIN.CODE.
  
 THE GROUND LEVEL AREA DRAINS USED TO
 COLLECT THE STORM DRAINAGE OVEREFLOW
 FROM THE 5TH LEVEL SHALL BE SIZED PER
 SPC SEC.1109.3 & FIGURE 1109.3.THE SQ.
 FOOT AREA OF THE 5TH LEVEL MUST BE USED
 IN CONJUNCTION WITH THE FORMULA IN THE
 SPC.SEE SPC SEC.1108.2 AND TABLE 1108.2

Review Stop P PLUMBING
Rev No 4 Status N Date 2000-06-19 Cont ID  
Sent By tlarge Date 2000-06-13 Time 11:27 Rev Time 1.00
Received By tlarge Date 2000-06-13 Time 11:27 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 SUBMIT SIGNED AND SEALED DETAIL FOR
 ROOF SECONDARY EMERGENCY DRAINAGE
 LOCATED AT DESIGNATED COLUMNS.
  
 SUBMIT SIGNED AND SEALED CALCULATIONS
 FOR OVERFLOW DRAINAGE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 12:12 Rev Time 1.50
Received By tlarge Date 2000-06-01 Time 12:12 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW PROVISIONS FOR OVERFLOW
 DRAINAGE PER SPC 1109.1-1109.3.SUBMIT
 DETAILS OF OVERFLOW OPENINGS.PLANS SHOW
 SCUPPER DETAILS BUT NO DIMENSIONS.SHOW
 LOCATION OF SCUPPERS ON PLANS.
  
 SUBMIT CALCULATIONS FOR INCLUSION OF 1/2
 THE AREA OF ANY VERTICAL WALL WHICH
 DIVERTS RAIN WATER TO THE ROOF.SPC SEC.
 1108.3.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-04-06 Cont ID  
Sent By tlarge Date 2000-04-06 Time 10:21 Rev Time 2.50
Received By tlarge Date 2000-04-06 Time 10:21 Sent To  
Notes
2001-01-08 00:00:00SHT.PD-P3.01-MAX.20,700 SQ.FT.PERMITTED
 ON 10" RWL AT 1/8" PER FT.(SEE COLS.B-2
 C-2,C-8.)COMPLY W/SPC 1108.2.
  
 SHT.PD-P3.01-PLANS SHOW 15"RWL DRAINING
 INTO 10" LINE.SPC SEC.307.5,709.1.SEE
 COL.C-5.2.
  
 SIZE THE UNDERGROUND HORIZONTAL SECTIONS
 FOR ALL THE STORM RISERS.COMPLY W/SPC
 SEC.1108.2 AND TABLE 1108.2.
  
 CLEARLY SHOW PROVISIONS FOR OVERFLOW
 DRAINAGE PER SPC 1109.1-1109.3.SUBMIT
 DETAILS OF OVERFLOW OPENINGS.
  
 SUBMIT CALCULATIONS FOR INCLUSION OF
 1/2 THE AREA OF ANY VERTICAL WALL WHICH
 DIVERTS RAIN WATER TO THE ROOF.SPC SEC.
 1108.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-01-13 Cont ID  
Sent By tlarge Date 2000-01-13 Time 12:36 Rev Time 3.75
Received By tlarge Date 2000-01-13 Time 12:36 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW LOCATION OF SCUPPERS ON
 PLANS.SIZE AND NUMBER SHALL COMPLY W/SBC
 SEC.1517.6.4.,1517.6.4.2, AND SPC SEC.
 1109.1- 1109.3.,& APPENDIX "A".
  
 SHT.PD-P3.01-15" STORM DRAIN IS DRAINING
 INTO A 10"LINE.SPC 307.5.,709.1.(SEE
 COLS.C-5.2).
  
 SIZE THE UNDERGROUNDHORIZONTAL SECTION
 FOR ALL THE STORM RISERS.COMPLY W/SPC
 SEC.1108.2 AND TABLE 1108.2.
  
 CLEARLY SHOW ON PLAN THAT CALCULATIONS
 FOR STORM DRAINAGE HAVE INCLUDED 1/2 THE
 AREA OF ALL PARAPET WALLS PER SPC SEC.
 1108.3.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-09 Cont ID  
Sent By bstaples Date 2000-01-19 Time 13:43 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY DENNIS CAMPBELL
 1/27/00 DENIED EASEMENT FOR DUCT BANK
 AND ENTRANCE SHOWN FORM SAPODILLA TO
 GARAGE.