Plan Review Details - Permit 99110631
Plan Review Stops For Permit 99110631
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-02-10 Cont ID  
Sent By jgomez Date 2000-02-10 Time 09:03 Rev Time 2.00
Received By jgomez Date 2000-02-10 Time 09:03 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 1-VALUATION OF BUILDINGS WILL BE UPDATED
 FOR APPLICATIONS SUBMITTED AFTER FEB.
 01 OF YEAR 2000.
 2-PRODUCT APPROVALS FOR EXTERIOR DOORS
 AND WINDOWS TO BE SITE SPECIFIC
 ENGINEERING AND THE PRODUCT APPROVAL
 FORM TO BE SIGNED AND SEALED BY THE
 MANUFACTURER'S ENGINEER AND THE
 DESIGNER OF RECORD.
 3-PROVIDE SOIL TEST REPORT AS PER CITY
 AMENDMENTS SECTION 1804.2.7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-12-16 Cont ID  
Sent By jcaloger Date 1999-12-16 Time 13:39 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE PERCENTAGE OF WALL OPENINGS EXCEED
 THE AMOUNT ALLOWED BY TABLE 600.
 PLAN A3 SIDE ELEVATION, WALL AREA
 388SF X 20%= 77.6SF ALLOWED
 OPENINGS:8X4'6= 36
 4X4'6= 18
 3X4'6= 13.5
 DOOR4'6X7= 31.5
 4X4'6= 18
 TOTAL117SF
 117-77.6= 39.5SF OVER ALLOWED AMOUNT
  
 ENCLOSED LANI SIDE:
 ADD 12X8X20%=19.2SF ADD TO 77.6= 96.8
 117-96.8= 20.2SF OVER ALLOWED AMOUNT
  
 PROVIDE SITE SPECIFIC ENGINEERING
 CALCULATIONS FOR THE EXTERIOR WINDOWS &
 SLIDING GLASS DOORS WITH EACH PERMIT
 APPLICATION.
  
 SEE COMMENTS FROM PLUMBING AND ELECTRIC
 REVIEW.
  
 PLAN SD1, SD2, SD3, SD4 UPDATE PLAN DATE
  
 REMOVE OLD MASTER PERMIT NUMBER FROM
 PLAN SD2 AND SD4.
  
 PROVIDE A TRUSS DESIGN CERTIFICATION
 FORM FOR THE TRUSS ENGINEERING. ATTACHED
 IS A COPY OF THE FORM.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 10:04 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 10:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-01-19 Time 06:26 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE:GROUNDING ELECTRODE CONDUCTOR IS
 TO GO TO TWO METHODS OF GROUNDING
 ELECTRODES!! TO GROUND ROD,,,AND BLDG.
 STEEL AND ALL COLD WATER PIPES IN ANY
 DWELLING MUST BE BONDED TO THE ELEC.
 SYSTEM.**250-80**250-81-A** PLEASE SHOW
 ALL ON RISER DIAGRAM 215-5.
  
 2)NOTE:SMOKE DETECTORS NEED TO BE MOVED
 TO BE INSIDE BEDROOMS. AS REQ`D BY 1993/
 1996 NFPA-72 2-2.1.1.1.
  
 JUST NOTE IF PVC CONDUIT IS USED BETWEEN
 MAIN DISC. AND PANEL ??? THEN AN EQUIP.
 GROUNDING CONDUCTOR NEEDS TO BE SIZED
 AND INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFROMATION
 FOR REVIEW AND APPROVAL BEFORE MASTER
 IS ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-02-05 Cont ID  
Sent By dpalmer Date 1999-12-07 Time 16:33 Rev Time 0.00
Received By dpalmer Date 1999-12-07 Time 16:33 Sent To  
Notes
2001-01-08 00:00:00************UNSAT**********************
  
 1)NOTE:AS PER 110-9/215-5 NEED TO SUBMIT
 AIC RATING OF EQUIPMENT MAINS, BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 2)NOTE: AS PER 210-52D/215-5 NEED TO
 SHOW BATH(S) DEDICATED GFI CIRCUT ON
 PANEL SCHEDULE.
  
 3)NOTE:AS PER 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS IN NEW DWELLINGS.
  
 4)NOTE:RISER DIAGRAM SHOWS ALUM. AS PART
 FO THE GROUNDING ELECTRODE,, AS PER
 COUNTY AMENDMENT THIS IS NOT ALLOWED.
 ONLY COPPER OR GALV.
  
 5)NOTE:AS PER NEC TABLES 4/5 PIPE FILL
 FOR THE CONDUIT FEEDING POOL PANEL
 IS NOT LARGE ENOUGH. PLEASE CORRECT AND
 CHANGE CONDUIT SIZE.
  
 6)NOTE:AS PER 210-52E NEED TO HAVE REC.
 IN FRONT OF DWELLING.
  
 7)NOTE: NEC. REQ`S ROOM FOR TWO SPARE
 CIRCUTS IN ALL PANELS OF NEW HOMES.
 YOUR PLANS SHOW LOAD CALCULATION BEING
 123.8 AMPS AND UTILIZING 125 AMP PANEL.
 THIS PANEL IS NOT LARGE ENOUGH AND NEEDS
 TO INCREASE TO 150. ALSO THIS DOES NOT
 EVEN INCLUDE POOL PANEL OPTION???!!!!
 NEED TO SUBMIT LOAD CALCULATION SHOWING
 POOL PANEL OPT. TO INCLUDE POOL HEATER,
 POOL LIGHT, AND POOL PUMP ETC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL AT 659-8096
 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By cthirben Date 1999-12-08 Time 08:37 Rev Time 0.75
Received By cthirben Date 1999-11-23 Time 11:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-15 Cont ID  
Sent By tlarge Date 2000-01-15 Time 05:36 Rev Time 0.33
Received By tlarge Date 2000-01-15 Time 05:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-15 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:11 Rev Time 0.33
Received By tlarge Date 1999-11-18 Time 20:11 Sent To  
Notes
2001-01-08 00:00:00WASHING MACHINE FIXTURE DRAIN SHALL
 CONNECT TO THE STACK PER SPC SEC.
 409.12.2.
  
 SIZE ALL DRAINS IN GUEST BATH.COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.

Review Stop Z ZONING
Rev No 1 Status N Date 2000-02-28 Cont ID  
Sent By jgomez Date 2000-02-10 Time 09:02 Rev Time 0.00
Received By fknapp Date 2000-02-10 Time 09:02 Sent To  
Notes
***NONE***