2001-01-08 00:00:00 | ************UNSAT********************** |
| |
| 1)NOTE:AS PER 110-9/215-5 NEED TO SUBMIT |
| AIC RATING OF EQUIPMENT MAINS, BRKRS. |
| AIC RATING IS FIGURED FROM FAULT CURRENT |
| CALCULATIONS. |
| |
| 2)NOTE: AS PER 210-52D/215-5 NEED TO |
| SHOW BATH(S) DEDICATED GFI CIRCUT ON |
| PANEL SCHEDULE. |
| |
| 3)NOTE:AS PER 1993/1996 NFPA-72 |
| CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE |
| REQ`D INSIDE AND OUTSIDE ALL SLEEPING |
| ROOMS IN NEW DWELLINGS. |
| |
| 4)NOTE:RISER DIAGRAM SHOWS ALUM. AS PART |
| FO THE GROUNDING ELECTRODE,, AS PER |
| COUNTY AMENDMENT THIS IS NOT ALLOWED. |
| ONLY COPPER OR GALV. |
| |
| 5)NOTE:AS PER NEC TABLES 4/5 PIPE FILL |
| FOR THE CONDUIT FEEDING POOL PANEL |
| IS NOT LARGE ENOUGH. PLEASE CORRECT AND |
| CHANGE CONDUIT SIZE. |
| |
| 6)NOTE:AS PER 210-52E NEED TO HAVE REC. |
| IN FRONT OF DWELLING. |
| |
| 7)NOTE: NEC. REQ`S ROOM FOR TWO SPARE |
| CIRCUTS IN ALL PANELS OF NEW HOMES. |
| YOUR PLANS SHOW LOAD CALCULATION BEING |
| 123.8 AMPS AND UTILIZING 125 AMP PANEL. |
| THIS PANEL IS NOT LARGE ENOUGH AND NEEDS |
| TO INCREASE TO 150. ALSO THIS DOES NOT |
| EVEN INCLUDE POOL PANEL OPTION???!!!! |
| NEED TO SUBMIT LOAD CALCULATION SHOWING |
| POOL PANEL OPT. TO INCLUDE POOL HEATER, |
| POOL LIGHT, AND POOL PUMP ETC. |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW AND APPROVAL. IF THERE ARE |
| ANY QUESTIONS PLEASE CALL AT 659-8096 |
| EXT 8372 |