Plan Review Details - Permit 99110630
Plan Review Stops For Permit 99110630
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-03-08 Cont ID  
Sent By jgomez Date 2000-03-08 Time 18:31 Rev Time 2.00
Received By jgomez Date 2000-03-08 Time 18:31 Sent To  
Notes
2001-01-08 00:00:001-PRODUCT APPROVAL FOR EXTERIOR DOORS
 WINDOWS TO BE SITE SPECIFIC FOR EACH
 HOUSE AND SIGNED, SEALED AND DATED BY
 THE MANUFACTURER'S ENGINEER AND BY THE
 DESIGNER ENGINEER OF RECORD.
 2-GARAGE DOOR DRAWING # B-409367 DOESN'T
 MATCH SBCCI PRODUCT APPROVAL #9839 FOR
 ATTACHMENT OF GARAGE DOOR DIRECTLY TO
 THE STRUCTURE.
 3-BE AWARE THAT PRODUCT APPROVAL FOR
 INSWING ENTRY DOOR EXPIRES ON MARCH
 31ST OF YEAR 2000. UPDATED PRODUCT
 APPROVAL WILL BE REQUIRED PRIOR TO
 EXPIRATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-02-28 Cont ID  
Sent By jgomez Date 2000-02-28 Time 14:10 Rev Time 2.50
Received By jgomez Date 2000-02-28 Time 14:10 Sent To  
Notes
2001-01-08 00:00:001-SPECIFY THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS.SEC 104.2 CITY AMEND
 2-PRODUCT APPROVALS FOR DOORS AND
 WINDOWS TO BE SITE SPECIFIC FOR EACH
 HOUSE AND SIGNED, SEALED AND DATE BY
 THE MANUFACTURER'S ENGINEER AND BY THE
 DESIGNER ENGINEER OF RECORD.
 3-PROVIDE SOIL TEST REPORT AS PER CITY
 AMENDMENTS SECTION 1804.2.7.
 4-REVISE SHEET A-2:
 -SECTION 2 OF A-2 FOOTING TO HAVE 12"
 MIN BELOW GRADE.
 -INFILTRATION REQUIREMENTS NOTE IS NOT
 CLEAR. SEE FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION 1997
 EDITION. WHAT'S PRACTICE #2?
 5-ALL 4 SETS OF TRUSS DRAWINGS TO BE
 SIGNED, SEALED AND DATED. (EMBOSSED
 SEAL AND WET SIGNATURE-NO RUBBER).
 6-GARAGE DOOR:
 -SHEET T-1 CALLS FOR A DADE COUNTY
 PRODUCT APPROVAL, BUT, PRODUCT
 APPROVAL SUBMITTED IS FROM SBCCI.
 -SBCCI PRODUCT APPROVAL IS MISSING ONE
 PAGE OF THE DRAWINGS.
 -PROVIDE PRODUCT APPROVAL OF DOOR
 ATTACHED DIRECTLY TO STRUCTURE INSTEAD
 OF ATTACHED TO A SUB-BUCK.
 7-PRODUCT APPROVAL FOR ENTRY DOOR IS FOR
 AN OUTSWING DOOR AND FLOOR PLANS CALL
 FOR AN INSWING DOOR. RESUBMIT PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-02-23 Cont ID  
Sent By jgomez Date 2000-02-23 Time 18:32 Rev Time 2.50
Received By jgomez Date 2000-02-23 Time 18:32 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PRODUCT APPROVAL FOR DOORS AND WINDOWS
 TO BE SITE SPECIFIC AND SIGNED AND
 SEALED BY MANUFACTURER ENGINEER AND
 DESIGNER OF RECORD FOR THIS PROJECT.
 OR PROVIDE STANDARD PRODUCT APPROVAL
 BY SBCCI OR DADE COUNTY.
 2-DRAWING T-1 CALLS FOR DADE COUNTY
 PRODUCT APPROVAL FOR GARAGE DOOR.
 PRODUCT APPROVAL SUBMITTED IS FROM
 SBCCI. CLARIFY AND PROVIDE COMPLETE
 SPECIFICATIONS FOR DOOR FASTENINGS.
 NOTE THAT ENGINEER WANTS TO ATTACH THE
 DOOR DIRECTLY TO THE STRUCTURE WITHOUT
 BUCK SUPPORT.
 3-

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-01-06 Cont ID  
Sent By jcaloger Date 2000-01-06 Time 10:54 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00WALL SECTION 3/A2 & 2/A2, THE FOOTER IS
 REQUIRED TO BE A MININUM OF 12" BELLOW
 AND 4" ABOVE FINISH GRADE.
 SECT 1804.1.3 SBC 1997
  
 WALL SECTION 3/A2 SPECIFYS SIMULATED
 STUCCO, PROVIDE MORE INFO.THE MININUM
 STUCCO THICKNESS REQUIRED IS 5/8".
 CLARIFY THE WALL FINISH.
 SECT 2504.2.1SBC 1997
  
 WALL SECT 3/A2, PROVIDE FIREBLOCKING IN
 THE CONCEALED SPACE AT THE WALL CEILING
 CONNECTION.SECT 2305.1.1SBC 1997
  
 PLAN T1, SPECIFYS THE INCORRECT BUILDING
 CODE EDITION.
  
 SECTION 2/A2, SPECIFY WHICH METHOD OF
 ATTACHMENT WILL BE USED FOR INSTALLING
 THE ROOF TILE.NOTE THIS NEEDS TO BE
 COORDINATED WITH THE PRODUCT APPROVAL
 REQUIREMENTS.
  
  
 CLARIFY THE NAILING REQUIREMENTS FOR
 ATTACHING THE ROOF SHEATHING.NOTE THE
 CODE AMENDMENTS REQUIRE A MIN OF 8D
 COMMON NAILS EVERY 4"OC @ EDGES & 6"OC
 @ FIELD.SECT 2306.1 CITY AMEND
  
 THE NORANDEX WINDOWS AND DOORS ASSEMBLYS
 WILL BE REQUIRED TO BE PROVIDED WITH
 SITE SPECIFIC ENGINEERING WITH EACH
 PERMIT APPLICATION.SECT 1704.4 CITY AM
  
 PLAN A1,WINDOW & DOOR ATTACHMENT WILL BE
 AS REQUIRED BY THE SITE SPECIFIC ENGINEE
 RING. THE PLAN SHOULD CLEARLY SPECIFY
 THE SUB-BUCK ATTACHMENT TO THE STRUCTURE
 ONLY.
  
  
  
  
 PROVIDE ENGINEERING FOR THE BUTT GLAZED
 WINDOW SYSTEM. SECT 1707.4 CITY AMEND
  
 THE TRUSS ENGINEERING SHEETS ARE REQUIRE
 TO HAVE THE ORIGINAL PERSONAL SIGNATURE
 AND RAISED SEAL ON--EVERY-- SHEET. IN
 LIEW OF THIS A TRUSS DESIGN CERTIFICATIO
 FORM MAY BE SUBMITTED.ATTACHED IS A
 SAMPLE FORM.
  
 SEE PLAN REVIEW COMMENTS FROM ELECTRIC
 AND PLUMBING.
  
 THE PERMIT VALUE WILL BE AS PER THE
 FOLLOWING CALCULATIONS:
 A/C AREA 2547 X 67.20 =$171,158.40
 ROOF AREA 783 X 36.75 = 28,752.25
 TOTAL $199,911

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-18 Cont ID  
Sent By dpalmer Date 2000-02-18 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2000-02-18 Time 07:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-02-18 Cont ID  
Sent By dpalmer Date 1999-12-08 Time 07:06 Rev Time 0.00
Received By dpalmer Date 1999-12-08 Time 07:06 Sent To  
Notes
2001-01-08 00:00:00***************UNSAT********************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 2)NOTE: NEED TO INCLUDE AS PART OF THE
 GROUNDING ELECTRODE SYSTEM; GRND.ROD,
 BLDG.STEEL AND COLD WATER PIPE. AS PER
 250-81.
  
 3)NOTE: AS REQ`D BY 210-52D/215-5 NEED
 TO INCLUDE ON PANEL SCHEDULE BATH(S)
 DEDICATED 20AMP GFI CIRCUT(S).
  
 4)NOTE: AS PER NEC AND 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ANY
 QUESTIONS CALL 659-8096 EXT.8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By cthirben Date 1999-11-23 Time 14:41 Rev Time 0.75
Received By cthirben Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-19 Cont ID  
Sent By tlarge Date 2000-02-19 Time 05:57 Rev Time 0.50
Received By tlarge Date 2000-02-19 Time 05:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-19 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:03 Rev Time 0.33
Received By tlarge Date 1999-11-18 Time 20:03 Sent To  
Notes
2001-01-08 00:00:00WASHING MACHINE FIXTURE DRAIN SHALL
 CONNECT TO THE STACK.SPC SEC.409.12.2.
  
 DELETE VENT BY SHOWER IN M.B.PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SEC.
 911.1.1.