2001-01-08 00:00:00 | ***************PROVISO***************** |
| |
| 1)NOTE:NEED TO SUBMIT AIC RATING OF |
| EQUIPMENT MAINS AND BRKRS. AIC RATING IS |
| FIGURED FROM FAULT CURRENT CALCULATIONS. |
| AS PER ART; 110-9/215-5 |
| |
| 2)NOTE:AS PER 1993/1996 NFPA-72 2-2.1.1 |
| .1 SMOKE DETECTORS ARE REQ`D INSIDE AND |
| OUTSIDE ALL SLEEPING ROOMS OF NEW |
| DWELLINGS. |
| |
| 3)NOTE:AS PER 210-52D PLEASE INCLUDE |
| BATH(S) GFI CIRCUT ON PANEL SCHEDULE. |
| 20 AMP,#12 AWG. DEDICATED. |
| |
| 4)NOTE:AS PER 210-8-A-6 ALL RECEPTS. |
| SERVING KITCHEN COUNTERSPACE ARE TO BE |
| GFI/GFI PROTECTED. |
| |
| 5)NOTE: PLANS SHOW MAIN DISCONNECT NEXT |
| TO METERCAN,,,,,POWER RISER SHOWS NO |
| MAIN?? WHICH IS IT? ALSO IF 200 AMP |
| SERVICE IS GOING TO BE AN OPTION THEN |
| DRAW SECOND RISER WITH WIRE SIZES, |
| CONDUIT SIZE, AND APPRO. GROUND. |
| |
| 6)NOTE: AS PER 250-81/215-5 PLEASE INCL. |
| COLD WATER PIPE AS PART OF THE GROUNDING |
| SYSTEM. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW AND APPROVAL BEFORE FIRST ROUGH |
| ELECTRICAL INSPECTION IS CALLED IN. THIS |
| WOULD INCLUDE GROUND ROUGH IF ANY. |