Plan Review Details - Permit 99110353
Plan Review Stops For Permit 99110353
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By dpalmer Date 1999-12-06 Time 06:45 Rev Time 0.00
Received By dpalmer Date 1999-12-06 Time 06:44 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS. TO INCLUDE BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQUESTED AS PER 110-9/
 215-5
  
 2)NOTE: AS PER 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS IN
 NEW DWELLINGS.
  
 3)NOTE:AS REQ`D PER ARTS:210-52D/215-5
 PLEASE INCLUDE DEDICATED BATH GFI CIRCUT
 (S) ON PNAEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICALINSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-19 Cont ID  
Sent By cthirben Date 2000-01-19 Time 11:52 Rev Time 1.00
Received By cthirben Date 2000-01-19 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00N

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-11-16 Cont ID  
Sent By tlarge Date 1999-11-16 Time 08:29 Rev Time 0.50
Received By tlarge Date 1999-11-16 Time 08:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-19 Cont ID  
Sent By jcaloger Date 1999-12-09 Time 16:04 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS NEED ARCHITECT ORIGINAL SIGN

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-12 Cont ID  
Sent By gjoyce Date 1999-11-12 Time 08:46 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***