Plan Review Details - Permit 99110346
Plan Review Stops For Permit 99110346
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-10 Cont ID  
Sent By ndenmark Date 1999-11-10 Time 14:39 Rev Time 0.50
Received By ndenmark Date 1999-11-10 Time 14:39 Sent To  
Notes
2001-01-08 00:00:00PROVISO
 REQUIREMENTS OF CHAPTER 11 1997 SMC
 LEVEL 1 MACHINERY ROOM TO BE COMPLIED W/
 1)OPENINGS INTO ADJACENT ROOMS ARE PROHI
 BITED (SEAL 100%)
 2) REFRIGERANT LEAK DETECTOR REQUIRED
 3) NO OPEN FLAMES USING COMBUSTION AIR
 PERMITTED WITHIN THE ROOM
 4) SIGNS SHALL BE POSTED PROHIBITING
 UNAUTHORIZED ACCESS AND EXPLAINING PROCE
 DURE
 5) VENTILATION PER 1105.7.5 TO BE PROVID
 ED SUPPLY CALCULATIONS
 6) RELIEF DEVICES TO BE INSTALLED PER
 SMC 1105.9
 7) BREATHING APPARATUS NOT REQUIRED PRO
 VIDED SIGNAGE IS INCLUSIVE OF PROCEEDURE
 IF LEAK OCCURS
 8) REFER TO 1997 SMC FOR CLARIFICATION
 OF ABOVE ISSUES
 9) PROVIDE PRESSURE TEST PRIOR TO INSULA
 TING PIPING


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved