Plan Review Stops For Permit 99110346 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-11-10 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-11-10 |
Time |
14:39 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
1999-11-10 |
Time |
14:39 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO | | REQUIREMENTS OF CHAPTER 11 1997 SMC | | LEVEL 1 MACHINERY ROOM TO BE COMPLIED W/ | | 1)OPENINGS INTO ADJACENT ROOMS ARE PROHI | | BITED (SEAL 100%) | | 2) REFRIGERANT LEAK DETECTOR REQUIRED | | 3) NO OPEN FLAMES USING COMBUSTION AIR | | PERMITTED WITHIN THE ROOM | | 4) SIGNS SHALL BE POSTED PROHIBITING | | UNAUTHORIZED ACCESS AND EXPLAINING PROCE | | DURE | | 5) VENTILATION PER 1105.7.5 TO BE PROVID | | ED SUPPLY CALCULATIONS | | 6) RELIEF DEVICES TO BE INSTALLED PER | | SMC 1105.9 | | 7) BREATHING APPARATUS NOT REQUIRED PRO | | VIDED SIGNAGE IS INCLUSIVE OF PROCEEDURE | | IF LEAK OCCURS | | 8) REFER TO 1997 SMC FOR CLARIFICATION | | OF ABOVE ISSUES | | 9) PROVIDE PRESSURE TEST PRIOR TO INSULA | | TING PIPING |
|
|
|