Plan Review Details - Permit 99101350
Plan Review Stops For Permit 99101350
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By dpalmer Date 1999-11-02 Time 07:15 Rev Time 0.00
Received By dpalmer Date 1999-11-02 Time 07:15 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS, AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE: PLEASE SHOW ON PANEL SCHEDULE
 BATH CIRCUT(S) REQ`D AS PER ART:210-52D
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROAVL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-13 Cont ID  
Sent By jleech Date 1999-11-13 Time 10:51 Rev Time 0.50
Received By jleech Date 1999-11-13 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 06:20 Rev Time 0.33
Received By tlarge Date 1999-10-28 Time 06:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By jcaloger Date 1999-11-30 Time 10:19 Rev Time 1.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-27 Cont ID  
Sent By gjoyce Date 1999-10-27 Time 09:24 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***