Plan Review Details - Permit 99101250
Plan Review Stops For Permit 99101250
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-11 Cont ID  
Sent By dpalmer Date 2000-04-11 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2000-04-11 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-04 Cont ID  
Sent By dpalmer Date 2000-04-04 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2000-04-04 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By dpalmer Date 1999-10-28 Time 10:27 Rev Time 0.00
Received By dpalmer Date 1999-10-28 Time 10:27 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT BEING INSTALLED. AIC RATINGS
 ARE FIGURED FROM FAULT CURRENT CALCU-
 LATIONS. ABOVE PER ARTS:110-9/215-5
 2)NOTE:AS PER ART:250-81 NEED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 GROUND ROD AND BUILDING STEEL ALSO.
 3)NOTE:PANEL SCHEDULE TO SHOW CIRCUT
 REQ`D FOR BATH(S) CIRCUT AS PER ART:
 210-52D.
 4)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:AS PER 1996 NFPA-72 CHAPTER ;
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN CONSTRUCTION OF NEW HOMES.
  
 NEED TO REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-30 Cont ID  
Sent By jleech Date 1999-11-30 Time 12:34 Rev Time 0.35
Received By jleech Date 1999-11-30 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-01 Cont ID  
Sent By jleech Date 1999-11-01 Time 14:50 Rev Time 0.50
Received By jleech Date 1999-11-01 Time 14:50 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 SUBMIT A/C PLAN LIKE FLOOR PLAN BEFORE
 ROUGH A/C INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 09:45 Rev Time 0.75
Received By tlarge Date 2000-01-04 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-04 Cont ID  
Sent By tlarge Date 1999-10-28 Time 07:07 Rev Time 0.33
Received By tlarge Date 1999-10-28 Time 07:06 Sent To  
Notes
2001-01-08 00:00:00SANITARY ISOMETRIC SHALL CORRELATE W/
 FLOOR PLAN.SPC SEC.104.2.1.
  
 OPTIONAL LAUNDRY TRAY SHALL BE SHOWN ON
 FLOOR PLAN.SPC 104.2.1.
  
 MODEL 2069-R.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By jcaloger Date 1999-12-10 Time 11:50 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS MANUAL J CALCULATIONS
  
 PROVDE PRODUCT APPROVAL FOR THE FRONT
 ENTRY DOOR
  
 TRUSS ENGINEERING NEEDS ORIGINAL
 ENGINEER SIGNATURE

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-27 Cont ID  
Sent By gjoyce Date 1999-10-27 Time 08:40 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***