Plan Review Details - Permit 99101150
Plan Review Stops For Permit 99101150
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-04-20 Cont ID  
Sent By dpalmer Date 2000-04-20 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2000-04-20 Time 20:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-04-13 Cont ID  
Sent By dpalmer Date 2000-04-13 Time 19:06 Rev Time 0.00
Received By dpalmer Date 2000-04-13 Time 19:06 Sent To  
Notes
2001-01-08 00:00:00STILL NEED TO ADDRESS FIRST PROVISO.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-07 Cont ID  
Sent By dpalmer Date 2000-03-07 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-01 Cont ID  
Sent By dpalmer Date 1999-11-01 Time 08:04 Rev Time 0.00
Received By dpalmer Date 1999-11-01 Time 08:04 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:PLEASE SUBMIT AIC RATING OF
 EQUIPMENT FIGURED FROM FAULT CURRENT
 CALCULATIONS.AS PER 110-9/215-5
 ALSO PLEASE LIST ON ALL PANEL SCHEDULES
 CIRCUTFOR BATH GFI`S AS PER 210-52D.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE ROUGH
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-29 Cont ID  
Sent By jleech Date 1999-10-29 Time 13:25 Rev Time 0.50
Received By jleech Date 1999-10-29 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 07:20 Rev Time 0.33
Received By tlarge Date 1999-10-28 Time 07:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-04-24 Cont ID  
Sent By jgomez Date 2000-04-24 Time 11:03 Rev Time 1.00
Received By jgomez Date 2000-04-24 Time 11:03 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST ON PRODUCT APPROVALS:
 1-PRODUCT APPROVAL FOR EXTERIOR DOORS
 AND WINDOWS IS NOT SIGNED, SEALED AND
 DATED BY THE PROFESSIONAL DESIGNER OF
 RECORD FOR THIS HOUSE. THE DESIGNER OF
 RECORD IS B.A.C. NOT SCOTT BLAKESLEE
 DISHER.
 2-PRODUCT APPROVAL FOR ENTRY DOOR WITH
 SIDELITE IS FOR AN OUTSWING DOOR,
 WHILE, ARCHITECT'S DRAWINGS CALL FOR
 AN IN-SWING DOOR. RESUBMIT PRODUCT
 APPROVAL.
 3-GARAGE DOOR DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 RESUBMIT PRODUCT APPROVAL.
 NOTE: ARCHITECT'S DRAWING D-2 ALSO
 CALLS FOR DADE COUNTY PRODUCT
 APPROVAL FOR GARAGE DOOR.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-15 Cont ID  
Sent By jgomez Date 1999-11-15 Time 13:11 Rev Time 1.50
Received By jgomez Date 1999-11-15 Time 13:11 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0". PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE FOOTING F-6. 16" MINIMUM DEPTH
 AS PER SEC. 1804.1.3 SBC 1997 AND SEC.
 1804.1.9 CITY AMENDMENTS TO SBC 1997.
 3-REVISE SIZE OF CEILING FANS AS PER
 TABLE 6-6 FLORIDA ENERGY CODE, 1997.
 4-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY.
 SEC. 1707.4 CITY AMENDMENTS.
 5-SEE COMMENTS ON PLANS AND REVISE ALL
 ORIGINAL DRAWINGS AS REQUIRED AND
 RESUBMIT TO THIS OFFICE.
 6-PROVIDE SIGNED AND SEALED SOIL TEST
 REPORT (ORIGINAL) AND COPIES OF THE
 TESTS PERFORMED.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-27 Cont ID  
Sent By gjoyce Date 1999-10-27 Time 08:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***