Plan Review Details - Permit 99101147
Plan Review Stops For Permit 99101147
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-11 Cont ID  
Sent By dpalmer Date 2000-04-11 Time 08:22 Rev Time 0.00
Received By dpalmer Date 2000-04-11 Time 08:22 Sent To  
Notes
2001-01-08 00:00:00RISER ONLY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-10 Cont ID  
Sent By dpalmer Date 2000-02-10 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2000-02-10 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By dpalmer Date 1999-11-02 Time 06:39 Rev Time 0.00
Received By dpalmer Date 1999-11-02 Time 06:39 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS.AS PER 110-9/215-5
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:PLEASE SHOW ON PANEL SCHEDULE
 CIRCUT REQ`D FOR BATHS REQ`D AS PER ART;
 210-52D
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-13 Cont ID  
Sent By jleech Date 1999-11-13 Time 10:12 Rev Time 0.50
Received By jleech Date 1999-11-13 Time 10:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 07:02 Rev Time 0.33
Received By tlarge Date 1999-10-28 Time 07:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-15 Cont ID  
Sent By jgomez Date 1999-11-15 Time 16:09 Rev Time 1.50
Received By jgomez Date 1999-11-15 Time 16:09 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0". PROVIDE ELEVATION
 CERTIFICATE.
 2-REVISE FOOTING F-6. 16" MINIMUM DEPTH
 SEC 1804.1.3 SBC 1997 AND SEC 1804.1.9
 CITY AMENDMENTS TO SBC 1997.
 3-REVISE SIZE OF CEILING FANS. TABLE 6-6
 FLORIDA ENERGY CODE, 1997 EDITION.
 4-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AND
 PRODUCT APPROVAL FOR FRENCH DOOR AT
 MASTER SUITE.
 5-SEE COMMENTS ON PLANS AND REVISE ALL
 ORIGINAL DRAWINGS AS REQUIRED AND
 RESUBMIT TO THIS OFFICE.
 6-PROVIDE SIGNED, SEALED AND DATED SOIL
 TEST REPORT (ORIGINAL) AND COPIES OF
 THE TESTS PERFORMED.
 7-STORM PANELS:
 REVISE INSTALLATION SCHEDULE AND KEY
 PLAN TO MATCH ARCHITECT'S PLANS.
 HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TO BE USED ON THIS PROJECT.
 USE CITY UPDATED INSTALLATION
 SCHEDULE SAMPLE. (ATTACHED).
 8-REVISE SURVEY. ARCHITECT'S PLANS DON'T
 SHOW EXTENDED PATIO.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-27 Cont ID  
Sent By gjoyce Date 1999-10-27 Time 08:21 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***