Plan Review Details - Permit 99100790
Plan Review Stops For Permit 99100790
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By bstaples Date 1999-10-19 Time 11:40 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE 99090252 FOR NOTES FOR FOUNDATION
 PERMIT

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-05-15 Cont ID  
Sent By dpalmer Date 2000-05-15 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2000-05-15 Time 08:54 Sent To  
Notes
2001-01-08 00:00:00ELEC REVISION SUBMITTED BY MERIT ELEC.
 NEEDS TO BE SEPARATE PERMIT APPLICATION.
 PLANS NEED TO BE SIGNED AND SEALED BY
 AN ENGINEER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-26 Cont ID  
Sent By dpalmer Date 2000-02-26 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2000-02-26 Time 11:39 Sent To  
Notes
2001-01-08 00:00:00SPEC BOOKS ON LIGHTING BEING INSTALLED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By dpalmer Date 2000-01-07 Time 15:17 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 12:51 Rev Time 0.00
Received By cthirben Date 2000-08-14 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 REVIEWED BY NCD AND CT AND INSERT DOCU-
 MENT SHEET IN PLANS......

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-01-11 Cont ID  
Sent By ndenmark Date 2000-01-11 Time 15:21 Rev Time 1.00
Received By ndenmark Date 1999-10-05 Time 15:20 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) PROTECT OPEN ENDS OF DUCTS THAT ARE
 INSTALLED AT THIS PHASE
 2) OUTSIDE AIR OPENINGS ARE NOT TO BE
 LOCATED WITHIN 10 FT OF EXHAUST AIR OUT-
 LETS OR PLUMBING VENT STACKS
 3) APPLIANCES ON ROOF SHALL BE MIN. 18"
 ABOVE ROOF SURFACE. THIS DISTANCE IS
 MEASURED TO THE BOTTOM OF THE SUPPORT
 STRUCTURE OF THE STAND, NOT TO THE TOP
 4) NO OUTSIDE AIR INFORMATION IS PROVIDE
 WITH THIS PLAN. PROVIDE OUTSIDE AIR
 CALCULATIONS PER ASHRAE 62-89 AND AIR
 BALANCE SCHEDULE WITH PLANS FOR INTERIOR
 BUILD-OUT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-01-25 Cont ID  
Sent By ndenmark Date 2000-01-25 Time 15:46 Rev Time 1.00
Received By ndenmark Date 2000-01-25 Time 15:46 Sent To  
Notes
2001-01-08 00:00:00SEE ATTACHED LETTER OF EXPLANATION FROM
 THERMALTECH ENGINEERING
 THIS INFORMATION IS FOR PERMIT NUMBER
 99090252 BUILDOUT PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-01-25 Cont ID  
Sent By ndenmark Date 2000-01-12 Time 09:18 Rev Time 1.00
Received By ndenmark Date 2000-01-12 Time 09:18 Sent To  
Notes
2001-01-08 00:00:00******CORRECTED BY LETTER ATTACHED******
 EXHAUST FANS ARE NOT ALL INDICATED ON
 ROOF PROVIDE LOCATION FOR EACH FAN.
 PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 EXHAUST AIR TOTALS IN BUILDING DOES NOT
 MATCH FAN CAPACITY ON SCHEDULE
 THIS INFORMATION IS FOR PERMIT NUMBER
 99090252 BUILDOUT PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-16 Cont ID  
Sent By ndenmark Date 1999-12-16 Time 08:03 Rev Time 1.00
Received By ndenmark Date 2000-01-12 Time 09:17 Sent To  
Notes
2001-01-08 00:00:00ADDENDUM NO. 8 REVISIONS OKAY
 THIS INFORMATION IS FOR PERMIT NUMBER
 99090252 BUILDOUT PERMIT

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-24 Cont ID  
Sent By tlarge Date 2000-02-24 Time 08:51 Rev Time 1.50
Received By tlarge Date 2000-02-24 Time 08:51 Sent To  
Notes
***NONE***