Plan Review Details - Permit 99100534
Plan Review Stops For Permit 99100534
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-12-01 Cont ID  
Sent By hpiskura Date 1999-11-29 Time 15:46 Rev Time 1.00
Received By bstaples Date 1999-11-29 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00PROVIDE A SITE PLAN SO THAT COMPLIANCE
 WITH SBC T-600 MAY BE DETERMINED RE:
 THE GAS VENT AND HOOD EXHAUST.SEE ALSO
 SMC 506.1 RE: HOOD OUTLET
 SEENOTES ON PLANS.WRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By lmartine Date 1999-11-15 Time 15:44 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-11-30 Cont ID  
Sent By jleahy Date 1999-11-30 Time 11:56 Rev Time 0.45
Received By jleahy Date 1999-11-30 Time 11:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By jleahy Date 1999-10-28 Time 15:14 Rev Time 1.15
Received By bstaples Date 1999-10-28 Time 15:09 Sent To  
Notes
2001-01-08 00:00:001) LOAD CALCULATION NOT TO CODE60%????
  
 2) MAINS WILL HAVE TO BE GROUPED 230-72
  
 3) GROUND RODS TO BE TIED TOGETHER
 250-83
  
 4) SERVICE ENTRANCE CONDUCTORS AT
 WEATHER HEAD ARE TO BE TIED INTO THE
 SAME DROP FROM FPL!!230-2
  
 5) BRANCH CIRCUIT NUMBERS ARE TO BE ON
 PLAN SHOWING WHICH OUTLET,LIGHT,AC
 ARE ON THE CIRCUIT.110-22

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-03 Cont ID  
Sent By rturnque Date 1999-11-03 Time 14:37 Rev Time 0.10
Received By rturnque Date 1999-11-03 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 1999-12-01 Cont ID  
Sent By ndenmark Date 1999-11-30 Time 07:46 Rev Time 0.25
Received By ndenmark Date 1999-11-30 Time 07:46 Sent To  
Notes
2001-01-08 00:00:00NO MECH INCLUDED
 NO MECH INFO INCLUDED FOR REVIEW
 SEE PRIOR LIST
 ALSO SEPARATE PERMITS REQUIRED FOR HOOD,
 SUPPRESSION SYSTEM, AND WALKIN COOLER.
 SUBMIT PLANS FOR WORK WITH MECHANICAL
 PERMIT APPLICATION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-12-01 Cont ID  
Sent By ndenmark Date 1999-10-29 Time 11:43 Rev Time 0.25
Received By ndenmark Date 1999-10-29 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00******NO MECH INCLUDED*****************
 PROVIDE INFORMATION ON MECHANICAL WORK
 SEPARATE PERMITS ARE REQUIRED FOR HOOD,
 COOLER, AND SUPPRESSION SYSTEM FOR HOOD
 PROVIDE PLANS AT TIME OF PERMIT APPLICA-
 TION FOR THESE SYSTEMS

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-29 Cont ID  
Sent By tlarge Date 1999-11-29 Time 11:17 Rev Time 0.33
Received By tlarge Date 1999-11-29 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-23 Cont ID  
Sent By tlarge Date 1999-11-23 Time 17:12 Rev Time 1.00
Received By tlarge Date 1999-11-23 Time 17:12 Sent To  
Notes
2001-01-08 00:00:00HEIGHT OF HANDICAP WATER CLOSET SHALL
 COMPLY W/FACBC SEC.4.16.3.(17"-19")
  
 CLEAR FLOOR SPACE UNDER LAV.SHALL COMPLY
 W/FACBC SEC.4.19.2.(29" MIN)
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR WATER HEATER.COMPLY W/S.G.C.SEC.402
 & NFPA 54.
  
 GREASE INTERCEPTOR SHALL BE LOCATED OUT-
 SIDE OF BUILDING PER SPC SEC.1004.1
  
 SHOW FLOOR DRAINS ON RISER DIAGRAM.
  
 NOTE ON PLAN THAT GAS EQUIPMENT SHALL BE
 LISTED PER S.G.C. SEC.402.1,NFPA 54
 SEC.5.3.
  
 ANSUL VALVE SHALL BE LOCATED BELOW
 CEILING AND BE EQUIPPED W/UNION DOWN-
 STREAM OF SHUT-OFF VALVE.
  
 SUBMIT A WATER RISER FOR REVIEW .SPC
 SEC.607.1,COUNTYWIDE AMENDMENTS TO STD.
 PLBG.CODE SEC.104.2.1.
  
 INDIRECT WASTE RECEPTORS SHALL COMPLY
 W/SPC SEC.807.1.
  
 GREASE INTERCEPTORS SHALL BE LOCATED ON
 THE EXTERIOR OF THE BUILDING PER SPC SEC
 1004.1

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 11:13 Rev Time 2.75
Received By tlarge Date 1999-10-28 Time 11:13 Sent To  
Notes
2001-01-08 00:00:00HEIGHT OF HANDICAP WATER CLOSET SHALL
 COMPLY W/FACBC SEC.4.16.3.
  
 CLEAR FLOOR SPACE UNDER LAV.TO COMPLY W/
 FACBC SEC.4.19.2.
  
 SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 SHOW TYPE OF PIPING,SIZES,BTU LOAD OF
 EACH APPLIANCE AND TOTAL LOAD ON SYSTEM.
 GAS SYSTEM SHALL BE SIZED IN ACCORDANCE
 W/STD.PLBG.CODE SECS.305.4 AND TABLES
 305.4(A)- 305.4(F).
  
 GAS EQUIPMENT SHALL BE LISTED PER STD.
 GAS CODE SEC.402.1 AND NFPA 54 SEC.5.3
  
 SUPPLY CALCULATIONS FOR COMBUSTION AIR
 PER STD.GAS CODE SEC.402.4.
  
 WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT MATERIAL TO A HEIGHT OF 4'PER
 SBC SEC.1204.2
  
 MIN.SIZE GREASE TRAP SHALL BE 750 GALS.
 PER HEALTH DEPT.REQS.RULE 10D-6.055(5).
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 SUBMIT A WATER RISER DIAGRAM FOR REVIEW.
 COMPLY W/SPC SEC.607.1,104.2.1.
  
 SHOW LOCATION OF DRINKING FOUNTAION ON
 FLOOR PLAN.COMPLY W/FACBC SEC.4.1.3.(A).
 FOR HANDICAP ACCESSIBILITY.
  
 SHOW LOCATION AND SIZES OF ALL INDIRECT
 WASTES.COMPLY W/SPC SEC.801.3,804.1,
 805.1.
  
 INDIRECT WASTE RECEPTORS SHALL COMPLY
 W/SPC SEC.807.1
  
 NOTE:CONTACTED DEPT.OF BUS.REGULATION
 REGARDING THEIR APPROVAL OF PLANS.SPOKE
 W/MS.BARBARA GIBSON AND SHE STATED THEY
 WERE TOLD BY OWNER THAT 51% OR MORE OF
 HIS SALES WOULD BE FROM GROCERY SALES
 SO THEIR DEPT.DOESN'T HAVE JURISDICTION.
 DEPT.OF AGRICULTUREWILL INSPECT PRIOR
 TO OPENING.

Review Stop Z ZONING
Rev No 3 Status P Date 1999-12-02 Cont ID  
Sent By gjoyce Date 1999-12-02 Time 09:10 Rev Time 0.25
Received By gjoyce Date 1999-12-02 Time 09:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 1999-11-23 Cont ID  
Sent By gjoyce Date 1999-11-23 Time 15:57 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00STILL NO SITE PLAN

Review Stop Z ZONING
Rev No 1 Status F Date 1999-11-08 Cont ID  
Sent By gjoyce Date 1999-11-08 Time 16:41 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS PARKING PLAN