Plan Review Stops For Permit 99100534 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
1999-11-29 |
Time |
15:46 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
1999-11-29 |
Time |
15:51 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVIDE A SITE PLAN SO THAT COMPLIANCE | | WITH SBC T-600 MAY BE DETERMINED RE: | | THE GAS VENT AND HOOD EXHAUST.SEE ALSO | | SMC 506.1 RE: HOOD OUTLET | | SEENOTES ON PLANS.WRS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
1999-11-15 |
Time |
15:44 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
1999-11-30 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-11-30 |
Time |
11:56 |
Rev Time |
0.45 |
Received By |
jleahy |
Date |
1999-11-30 |
Time |
11:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-10-28 |
Time |
15:14 |
Rev Time |
1.15 |
Received By |
bstaples |
Date |
1999-10-28 |
Time |
15:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) LOAD CALCULATION NOT TO CODE60%???? | | | | 2) MAINS WILL HAVE TO BE GROUPED 230-72 | | | | 3) GROUND RODS TO BE TIED TOGETHER | | 250-83 | | | | 4) SERVICE ENTRANCE CONDUCTORS AT | | WEATHER HEAD ARE TO BE TIED INTO THE | | SAME DROP FROM FPL!!230-2 | | | | 5) BRANCH CIRCUIT NUMBERS ARE TO BE ON | | PLAN SHOWING WHICH OUTLET,LIGHT,AC | | ARE ON THE CIRCUIT.110-22 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
1999-11-03 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
1999-11-03 |
Time |
14:37 |
Rev Time |
0.10 |
Received By |
rturnque |
Date |
1999-11-03 |
Time |
14:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-11-30 |
Time |
07:46 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
1999-11-30 |
Time |
07:46 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO MECH INCLUDED | | NO MECH INFO INCLUDED FOR REVIEW | | SEE PRIOR LIST | | ALSO SEPARATE PERMITS REQUIRED FOR HOOD, | | SUPPRESSION SYSTEM, AND WALKIN COOLER. | | SUBMIT PLANS FOR WORK WITH MECHANICAL | | PERMIT APPLICATION |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
1999-12-01 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-10-29 |
Time |
11:43 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
1999-10-29 |
Time |
11:43 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ******NO MECH INCLUDED***************** | | PROVIDE INFORMATION ON MECHANICAL WORK | | SEPARATE PERMITS ARE REQUIRED FOR HOOD, | | COOLER, AND SUPPRESSION SYSTEM FOR HOOD | | PROVIDE PLANS AT TIME OF PERMIT APPLICA- | | TION FOR THESE SYSTEMS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
1999-11-29 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-11-29 |
Time |
11:17 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
1999-11-29 |
Time |
11:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
1999-11-23 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-11-23 |
Time |
17:12 |
Rev Time |
1.00 |
Received By |
tlarge |
Date |
1999-11-23 |
Time |
17:12 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | HEIGHT OF HANDICAP WATER CLOSET SHALL | | COMPLY W/FACBC SEC.4.16.3.(17"-19") | | | | CLEAR FLOOR SPACE UNDER LAV.SHALL COMPLY | | W/FACBC SEC.4.19.2.(29" MIN) | | | | SUBMIT CALCULATIONS FOR COMBUSTION AIR | | FOR WATER HEATER.COMPLY W/S.G.C.SEC.402 | | & NFPA 54. | | | | GREASE INTERCEPTOR SHALL BE LOCATED OUT- | | SIDE OF BUILDING PER SPC SEC.1004.1 | | | | SHOW FLOOR DRAINS ON RISER DIAGRAM. | | | | NOTE ON PLAN THAT GAS EQUIPMENT SHALL BE | | LISTED PER S.G.C. SEC.402.1,NFPA 54 | | SEC.5.3. | | | | ANSUL VALVE SHALL BE LOCATED BELOW | | CEILING AND BE EQUIPPED W/UNION DOWN- | | STREAM OF SHUT-OFF VALVE. | | | | SUBMIT A WATER RISER FOR REVIEW .SPC | | SEC.607.1,COUNTYWIDE AMENDMENTS TO STD. | | PLBG.CODE SEC.104.2.1. | | | | INDIRECT WASTE RECEPTORS SHALL COMPLY | | W/SPC SEC.807.1. | | | | GREASE INTERCEPTORS SHALL BE LOCATED ON | | THE EXTERIOR OF THE BUILDING PER SPC SEC | | 1004.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
1999-10-28 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-10-28 |
Time |
11:13 |
Rev Time |
2.75 |
Received By |
tlarge |
Date |
1999-10-28 |
Time |
11:13 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | HEIGHT OF HANDICAP WATER CLOSET SHALL | | COMPLY W/FACBC SEC.4.16.3. | | | | CLEAR FLOOR SPACE UNDER LAV.TO COMPLY W/ | | FACBC SEC.4.19.2. | | | | SUBMIT COMPLETE GAS DRAWING FOR REVIEW. | | SHOW TYPE OF PIPING,SIZES,BTU LOAD OF | | EACH APPLIANCE AND TOTAL LOAD ON SYSTEM. | | GAS SYSTEM SHALL BE SIZED IN ACCORDANCE | | W/STD.PLBG.CODE SECS.305.4 AND TABLES | | 305.4(A)- 305.4(F). | | | | GAS EQUIPMENT SHALL BE LISTED PER STD. | | GAS CODE SEC.402.1 AND NFPA 54 SEC.5.3 | | | | SUPPLY CALCULATIONS FOR COMBUSTION AIR | | PER STD.GAS CODE SEC.402.4. | | | | WALLS IN TOILET ROOMS SHALL BE NON- | | ABSORBENT MATERIAL TO A HEIGHT OF 4'PER | | SBC SEC.1204.2 | | | | MIN.SIZE GREASE TRAP SHALL BE 750 GALS. | | PER HEALTH DEPT.REQS.RULE 10D-6.055(5). | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | ROOMS PER SPC SEC.409.4.1.1. | | | | SUBMIT A WATER RISER DIAGRAM FOR REVIEW. | | COMPLY W/SPC SEC.607.1,104.2.1. | | | | SHOW LOCATION OF DRINKING FOUNTAION ON | | FLOOR PLAN.COMPLY W/FACBC SEC.4.1.3.(A). | | FOR HANDICAP ACCESSIBILITY. | | | | SHOW LOCATION AND SIZES OF ALL INDIRECT | | WASTES.COMPLY W/SPC SEC.801.3,804.1, | | 805.1. | | | | INDIRECT WASTE RECEPTORS SHALL COMPLY | | W/SPC SEC.807.1 | | | | NOTE:CONTACTED DEPT.OF BUS.REGULATION | | REGARDING THEIR APPROVAL OF PLANS.SPOKE | | W/MS.BARBARA GIBSON AND SHE STATED THEY | | WERE TOLD BY OWNER THAT 51% OR MORE OF | | HIS SALES WOULD BE FROM GROCERY SALES | | SO THEIR DEPT.DOESN'T HAVE JURISDICTION. | | DEPT.OF AGRICULTUREWILL INSPECT PRIOR | | TO OPENING. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
1999-12-02 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-12-02 |
Time |
09:10 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
1999-12-02 |
Time |
09:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
1999-11-23 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-11-23 |
Time |
15:57 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | STILL NO SITE PLAN |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
1999-11-08 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-11-08 |
Time |
16:41 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NEEDS PARKING PLAN |
|
|