Plan Review Details - Permit 99100480
Plan Review Stops For Permit 99100480
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-30 Cont ID  
Sent By bstaples Date 2000-03-30 Time 08:51 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS FOR A DECK BRIDGE TO PARKING
 DECK 3/30/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By bstaples Date 1999-11-02 Time 11:42 Rev Time 6.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. IMPACT FEES MUST BE PAID
 2. STAIR ON SOUTH EAST CORNER OF GARAGE
 MUST CONTINUE TO THE ROOF DECK
 PARKING LEVEL.
 3. EXTERIOR WALL ON NORTH, SOUTH AND
 WEST ELEVATION TO BE 2HR RATED WITH
 1&1/2HR OPREANING PROTECTIVE DEVICES.
 ON NORTH AND SOUTH ELEVATION 2 HR
 PROTECTION REQUIRED WHERE BUILDING JOIN
 AND MUST EXTEND A MINUMIN OF TEN FEET
 PAST THE POINT OF ATTACHMENT.
 4. CODE COMPLIANCE CERTIFICATION AS PER
 FLORIDA STATUTE 553.79.
 5. SOIL REPORTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-18 Cont ID  
Sent By jleahy Date 1999-10-18 Time 08:35 Rev Time 1.30
Received By jleahy Date 1999-10-18 Time 08:35 Sent To  
Notes
2001-01-08 00:00:00***********PROVISO*********************
 E-5
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 MAINS,PANELS ETC.FIGURED FROM FAULT
 CURRENT CALCULATIONS.REQ`D AS PER
 110-9/10
 2)NOTE:NEED TO HAVE PLAGUES FOR SERVICE.
 REQ`D AS PER 230-2B.
  
 E-1
  
 NOTE:ACCESS TO WIREAND SUPPORT OF
 FIXTURE AS PER 410-16 A/B

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By bstaples Date 1999-11-01 Time 12:27 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTES DATED 10-19-99

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-10-18 Cont ID  
Sent By ndenmark Date 1999-10-18 Time 08:32 Rev Time 0.33
Received By ndenmark Date 1999-10-18 Time 08:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-03 Cont ID  
Sent By tlarge Date 1999-12-03 Time 10:54 Rev Time 1.50
Received By tlarge Date 1999-12-03 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-20 Cont ID  
Sent By tlarge Date 1999-10-20 Time 07:35 Rev Time 4.00
Received By tlarge Date 1999-10-20 Time 06:39 Sent To  
Notes
2001-01-08 00:00:00 
 PIPING PENETRATIONS THROUGH WALLS/FLOORS
 SHALL COMPLY W/STD.BLDG.CODE SEC.705.4.1
 705.5, 705.6.(SEE NOTE # 20 ON SHT.P-1.)
  
 WORK SHALL COMPLY W/1994 EDITION OF THE
 STANDARD PLBG.CODE.(SEE NOTE # 1 ON SHT.
 -1.)
  
 SHT.P-1-BRANCH LINES FOR HOSE BIBBS
 SHALL BE VALVED PER SPC SEC.610.4.1,
 610.4.2.
  
 SHT.P-3-8" STORM DRAIN SHALL BE SLOPED
 PER TABLE 1108.2.(EXCEEDS LIMITS)
  
 WATER PIPING SHALL BE PROTECTED AGAINST
 HAZARD AND NOISE PER SPC SEC.607.8.
  
 SECONDARY DRAINAGE SHALL BE PROVIDED
 FOR ROOF AREA PER SPC SEC.1109.1 AND
 APPENDIX "A".

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-03 Cont ID  
Sent By bstaples Date 1999-11-01 Time 12:29 Rev Time 0.30
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENNIS CAMPBEL 11/3/99