Plan Review Details - Permit 99100473
Plan Review Stops For Permit 99100473
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 19:41 Rev Time 0.00
Received By dpalmer Date 1999-10-19 Time 19:41 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:AS PER ART:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT BEING
 INSTALLED (MAINS AND BRANCH BREAKERS)
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART;210-52D PLEASE HAVE
 BATH CIRCUT LISTED ON PANEL SCHEDULE.
 3)NOTE:AS PER ART:210-63 A WP GFI RECEPT
 IS REQ`D FOR A/C UNIT AND IS TO BE
 WITHIN 25`.
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By jleech Date 1999-10-19 Time 15:21 Rev Time 0.50
Received By jleech Date 1999-10-19 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-16 Cont ID  
Sent By pschmitz Date 1999-10-16 Time 14:12 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-29 Cont ID  
Sent By jcaloger Date 1999-10-29 Time 11:43 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-14 Cont ID  
Sent By gjoyce Date 1999-10-14 Time 17:35 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***